Serial communication dedicated commands
Function
User frame
Read
registered data
Register data
Delete
registered data
Global
Initialize transmission sequence
Switch mode
Programmable
Register
controller CPU
monitoring
Deregister
On-demand

Commands for 2C frame

The following shows the commands for 2C frame.
The commands for 4C/3C frame are equivalent to the following device access commands and subcommands.
Function
Batch read
Batch read in
and write
bit units
Batch read in
word units
Batch write in
bit units
Batch write in
word units
Random read
Random read
and write
in word units
Random write
in bit units
(test)
Random write
in word units
(test)
Monitor
Register
device
monitor data
memory
Monitor

Commands for 1C/1E frame

For the commands for 1C/1E frame, refer to the following sections.
• Page 349 Command and Function Lists for 1C Frame
• Page 396 Commands and Function List for 1E Frame
7 COMMANDS AND FUNCTIONS
66
7.1 Command List
Command
Description
0610
Read the contents of registered user frames.
1610
Register user frames to C24.
Delete the registered user frame.
1618
Turn ON/OFF the global signal (X1A/X1B).
This can be performed to a connected station and multidrop connection station.
1615
Terminate a current processing request, and place C24 into the wait state to
receive commands.
This can be performed to a connected station and multidrop connection station.
1612
Switch the operation mode and transmission specifications of the specified
interface.
This can be performed to a connected station and multidrop connection station.
0630
Register the conditions to monitor and start the programmable controller CPU
monitoring.
0631
End the programmable controller CPU monitoring.
2101
Issue a transmission request to C24 from CPU module, and transmit data to
external devices.
2C frame
4C/3C frame
command
command subcommand
1
0401
0001
2
0000
3
1401
0001
4
0000
5
0403
0000
6
1402
0001
7
0000
8
0801
0000
9
0802
0000
Description
Read values from devices in bit units.
Read the values in batch with specifying the consecutive device points.
Read values from devices in word units.
Read the values in batch with specifying the consecutive device points.
Write values to devices in bit units.
Write the consecutive devices in batch with specifying the consecutive
device points.
Write values to devices in word units.
Write the consecutive devices in batch with specifying the consecutive
device points.
Read values from devices in word or double-word units.
Read device values with specifying device numbers.
Discontinuous device numbers can be specified.
Write values to devices in bit units.
Write device values with specifying device numbers.
Discontinuous device numbers can be specified.
Write values to devices in word or double-word units.
Write device values with specifying device numbers.
Discontinuous device numbers can be specified.
Register the devices to be monitored.
Read the values of registered devices.
Subcommand
0000
0000
0001
0000
0001
0000
0000
0000
0000

Advertisement