ABB TPU2000 Technical Manual page 77

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

Notes
Register
Address
10513
87T Status
10514
87T Momentary
10515
87H Status
10516
87H Momentary
10517
51P-1 Status
10518
51P-1 Momentary Winding 1 Phase Time Overcurrent Control Enabled (Momentary)
10519
51P-2 Status
10520
51P-2 Momentary Winding 2 Phase Time Overcurrent Control Enabled (Momentary)
10521
51N-1 Status
10522
51N-1
Momentary
10523
51N-2 Status
10524
51N-2
Momentary
10525
50P-1 Status
10526
50P-1 Momentary
10527
50P-2 Status
10528
50P-2 Momentary 1
10529
50N-1 Status
10530
50N-1
Momentary
10531
50N-2 Status
10532
50N-2
Momentary
10533
150P-1 Status
10534
150P-1
Momentary
10535
150P-2 Status
10536
150P-2
Momentary
10537
150N-1 Status
10538
150N-1
Momentary
10539
150N-2 Status
10540
150N-2
Momentary
10541
46-1 Status
10542
46-1 Momentary
10543
46-2 Status
10544
46-2 Momentary
10545
ALT1 Status
10546
ALT1 Momentary
10547
ALT2 Status
10548
ALT2 Momentary
10549
ECI1 Status
10550
ECI1 Momentary
10551
ECI2 Status
10552
ECI2 Momentary
10553
WCI Status
10554
WCI Momentary
TPU2000/2000R Modbus/Modbus Plus Automation Guide
Item
2 or 3 Winding 3- Phase % Differential Current Control (Status)
2 or 3 Winding 3- Phase % Differential Current Control (Momentary)
2 or 3 Winding 3 Phase % High Set Instantaneous Differential Current
Control (Status)
2 or 3 Winding 3 Phase % High Set Instantaneous Differential Current
Control (Momentary)
Winding 1 Phase Time Overcurrent Control Enabled (Status)
Winding 2 Phase Time Overcurrent Control Enabled (Status)
Winding 1 Neutral Time Overcurrent Control Enabled (Status)
Winding 1 Neutral Time Overcurrent Control Enabled (Momentary)
Winding 2 Neutral Time Overcurrent Control Enabled (Status)
Winding 2 Neutral Time Overcurrent Control Enabled (Momentary)
st
1
Winding 1 Phase Time Instantaneous Control Enabled (Status)
st
1
Winding 1 Phase Time Instantaneous Control Enabled
(Momentary)
st
1
Winding 2 Phase Time Instantaneous Control Enabled (Status)
st
Winding 2 Phase Time Instantaneous Control Enabled
(Momentary)
st
1
Winding 1 Neutral Time Instantaneous Control Enabled (Status)
st
1
Winding 1 Neutral Time Instantaneous Control Enabled
(Momentary)
st
1
Winding 2 Neutral Time Instantaneous Control Enabled (Status)
st
1
Winding 2 Neutral Time Instantaneous Control Enabled
(Momentary)
nd
2
Winding 1 Phase Time Instantaneous Control Enabled (Status)
nd
2
Winding 1 Phase Time Instantaneous Control Enabled
(Momentary)
nd
2
Winding 2 Phase Time Instantaneous Control Enabled (Status)
nd
2
Winding 2 Phase Time Instantaneous Control Enabled
(Momentary)
nd
2
Winding 1 Neutral Time Instantaneous Control Enabled (Status)
nd
2
Winding 1 Neutral Time Instantaneous Control Enabled
(Momentary)
nd
2
Winding 2 Neutral Time Instantaneous Control Enabled (Status)
nd
2
Winding 2 Neutral Time Instantaneous Control Enabled
(Momentary)
Winding 1 Negative Sequence Control Enabled (Status)
Winding 1 Negative Sequence Control Enabled (Momentary)
Winding 2 Negative Sequence Control Enabled (Status)
Winding 2 Negative Sequence Control Enabled (Momentary)
Enable Alternate 1 Settings (Status)
Enable Alternate 1 Settings (Momentary)
Enable Alternate 2 Settings (Status)
Enable Alternate 2 Settings (Momentary)
Initiate Event Capture 1 (Status)
Initiate Event Capture 1 (Momentary)
Initiate Event Capture 2 (Status)
Initiate Event Capture 2 (Momentary)
Waveform Capture Initiate (Status)
Waveform Capture Initiate (Momentary)
Description
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents