IRIG B is defined for code format sets identified by a three digit format number. Permissible format numbers for
the IRIG B subsets are:
IRIG B XYZ Where:
The first field "X" identifies the encoding type of the IRIG B signal. DPU/TPU/GPU products support Pulse Width
Code (X= 0), whereas, REL 3XX products having an IRIG B PONI Card support Pulse Width Code and Sine
Wave Amplitude Modulated, and REL5XX products support Sine Wave Amplitude Modulated IRIG. Manchester
Modulated code was added in IRIG Standard 200-98 Dated May 1998. It is not supported in the ABB protective
relay products which are IRIG B capable.
The second field "Y" determines if a carrier is included within IRIG B Data format.
The third field "Z" determines if a combination of the BCD time/Control Function/Straight Binary Time is included
within the IRIG B time frame. The inclusion or exclusion of any of the fields may cause errors in receivers not
designed for the field's inclusion/ exclusion.
The following combinations may seem daunting, but only a subset of the listed formats are actually defined within
the specification.
IF X =
0
= Pulse Width Code
1
= Sine Wave Amplitude Modulated
2
= Manchester Modulated Code
IF Y =
0
= No Carrier
2
=1Khz , 1mS
3
=10Khz, 0.1 mS
4
=100 Khz, 10 mS
5
=1Mhz, 1mS
IF Z=
0
=BCD Time,Control Function, Straight Binary Seconds
1
=Binary Coded Decimal Time, Control Function
2
=Binary Coded Decimal Time
3
=Binary Coded Decimal Time, Straight Binary Seconds
For the TPU/GPU/DPU2000/2000R products, IRIG B 000 and 002 formats are supported. Consult the IRIG B
generator manufacturer so that the correct IRIG B code format is supplied to the receiving devices.

Hardware Configuration

TPU2000/2000R Modbus/Modbus Plus Automation Guide
0
10
20
30
Seconds
Minutes
Hours
Days
Figure 4-10. IRIG B Frame Construction
1 Second Frame in 10 mS increments
40
50
60
70
Straight
Control Functions
Marker Pulses every 10 mS for an 8 mS duration
80
90
0
Binary
Time of
Day
31