Siemens MICROMASTER 440 Operating Instructions Manual page 85

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue B1
Input voltage range
Order No.
6SE6440- 2UC11
[kW]
Motor Output Rating
[hp]
Output Power
[kVA]
Output Current Max.
[A]
Input Current, 3 AC
[A]
Input Current , 1 AC
[A]
Recommended Fuse [A]
[mm
Input Cable Min.
[awg]
[mm
Input Cable Max.
[awg]
[mm
Output Cable Min.
[awg]
[mm
Output Cable Max.
[awg]
[kg]
Weight
[lbs]
w [mm]
h [mm]
d [mm]
Dimensions
w [inches] 2.87
h [inches] 6.81
d [inches] 5.87
MICROMASTER 440
Operating Instructions
6SE6400-5AC00-0BP0
1 AC 3 AC 200 V – 240 V, ± 10 % (Unfiltered)
2UC12
2UC13
-2AA0
-5AA0
-7AA0
0.12
0.25
0.37
0.16
0.33
0.5
0.4
0.7
1.0
0.9
1.7
2.3
0.6
1.1
1.6
1.4
2.7
3.7
10
10
10
3NA3803 3NA3803 3NA3803 3NA3805 3NA3805 3NA3807 3NA3807 3NA3810 3NA3812
2
1.0
1.0
1.0
]
17
17
17
2
2.5
2.5
2.5
]
13
13
13
2
1.0
1.0
1.0
]
17
17
17
2
2.5
2.5
2.5
]
13
13
13
1.3
1.3
1.3
2.9
2.9
2.9
73.0
73.0
73.0
173.0
173.0
173.0
149.0
149.0
149.0
2.87
2.87
6.81
6.81
5.87
5.87
7 MICROMASTER 440 specifications
2UC15
2UC17
2UC21
-5AA0
-5AA0
-1BA0
0.55
0.75
1.1
0.75
1.0
1.5
1.3
1.7
2.4
3.0
3.9
5.5
2.1
2.9
4.1
5.0
6.6
9.6
16
16
20
1.0
1.0
1.0
17
17
17
2.5
2.5
6.0
13
13
9
1.0
1.0
1.0
17
17
17
2.5
2.5
6.0
13
13
9
1.3
1.3
3.3
2.9
2.9
7.3
73.0
73.0
149.0
173.0
173.0
202.0
149.0
149.0
172.0
2.87
2.87
5.87
6.81
6.81
7.95
5.87
5.87
6.77
2UC21
2UC22
2UC23
-5BA0
-2BA0
-0CA0
1.5
2.2
3.0
2.0
3.0
4.0
3.2
4.6
6.0
7.4
10.4
13.6
5.6
7.6
10.5
13.0
17.6
23.7
20
25
32
1.5
2.5
4.0
15
13
11
6.0
6.0
10.0
9
9
7
1.0
1.0
1.5
17
17
15
6.0
6.0
10.0
9
9
7
3.3
3.3
5.5
7.3
7.3
12.1
149.0
149.0
185.0
202.0
202.0
245.0
172.0
172.0
195.0
5.87
5.87
7.28
7.95
7.95
9.65
6.77
6.77
7.68
85