3 Commissioning
3.2.2.1
Commissioning with the BOP
NOTICE
♦
The BOP motor control functions are disabled by default. To control the motor
via the BOP, parameter P0700 should be set to 1 and P1000 set to 1.
♦
The BOP can be fitted to and removed from the inverter whilst power is
applied.
♦
If the BOP has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP is removed.
Table 3-2
Parameter
P0100
P0307
P0310
P0311
P1082
40
You can alter parameter values via the BOP. To set
parameters on this panel, you must remove the SDP and
attach the BOP (see Appendix 0).
The BOP features a five-digit, seven-segment display for
showing parameter numbers and values, alarm and fault
messages and setpoints and actual values. Parameter
information cannot be saved via the BOP.
Table 3-2 shows the factory default settings for operation
via the BOP.
Default settings for operation using the BOP
Meaning
Operating Mode Europe/US
Power (rated motor)
Motor frequency rating
Motor speed rating
Maximum Motor Frequency
Default Europe (North America)
50 Hz, kW (60Hz, hp)
Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
50 Hz (60 Hz)
1395 (1680) rpm [depending on variant]
50 Hz (60 Hz)
MICROMASTER 440
Issue A2
Operating Instructions
6SE6400-5AC00-0BP0