Parameters – complete descriptions
Index Name/Selection
4008
0% VALUE
x...x
4009
100% VALUE
x...x
4010
SET POINT SEL
KEYPAD
AI1
AI2
COMM
COMM+AI1
COMM*AI1
DI3U,4D(RNC)
DI3U,4D(NC)
AI1+AI2
AI1*AI2
AI1-AI2
AI1/AI2
INTERNAL
DI4U,5D(NC)
FREQ INPUT
Actual signals and parameters
Description
Defines together with parameter
the PID controller's actual values.
Units (4006)
Scale (4007)
4009
4008
-1000%
Unit and range depend on the unit and scale defined by parameters
UNITS and
4007
UNIT SCALE.
Defines together with parameter
PID controller's actual values.
Unit and range depend on the unit and scale defined by parameters
UNITS and
4007
UNIT SCALE.
Selects the source for the process PID controller reference signal.
Control panel
Analog input AI1
Analog input AI2
Fieldbus reference REF2
Summation of fieldbus reference REF2 and analog input AI1. See section
Reference selection and correction
Multiplication of fieldbus reference REF2 and analog input AI1. See section
Reference selection and correction
Digital input 3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. The reference is not saved if the
control source is changed from EXT1 to EXT2, from EXT2 to EXT1 or from
LOC to REM.
Digital input 3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active reference (not reset by a stop command). The
reference is not saved if the control source is changed from EXT1 to EXT2,
from EXT2 to EXT1 or from LOC to REM.
Reference is calculated with the following equation:
REF = AI1(%) + AI2(%) - 50%
Reference is calculated with the following equation:
REF = AI(%) · (AI2(%) / 50%)
Reference is calculated with the following equation:
REF = AI1(%) + 50% - AI2(%)
Reference is calculated with the following equation:
REF = AI1(%) · (50% / AI2 (%))
A constant value defined by parameter
See selection DI3U,4D(NC).
Frequency input
4009
100% VALUE the scaling applied to
+1000%
Internal scale (%)
0%
100%
4008
0% VALUE the scaling applied to the
on page 249.
on page 249.
4011
INTERNAL SETPNT
Def, FbEq
0
4006
100
4006
AI1
0
1
2
8
9
10
11
12
14
15
16
17
19
31
32