Vanguard V5 Operator's Manual

Fire alarm panel avf & lcd -
Hide thumbs Also See for V5:

Advertisement

V
5
Operator's Manual
Fire Alarm Panel
(AVF&LCD)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the V5 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vanguard V5

  • Page 1 Operator’s Manual Fire Alarm Panel (AVF&LCD)
  • Page 2: Table Of Contents

    O&M-V5-FAP-AVF-LCD R0 Pg 1 of 21 CONTENTS 1. GENERAL 1.1 Introduction 1.2 System Description 1.2.1 Zone Detection Module 1.2.2 System Control Module 1.2.3 LCD Event Logging Module 2. OPERATING INSTRUCTIONS 2.1. Normal Operating Conditions 2.2. Fire Alarm Condition 2.2.1. Silencing the Alarm Bells / Sounders 2.2.2.
  • Page 3: General

    1.2 System Description This Fire Alarm System utilises the V5 Fire Alarm Panel. The system may comprise one or more alarm panel networked together witch performs the task of processing the input signals and thereafter transmit the output signals or initiates other auxiliary functions.
  • Page 4: Zone Detection Module

    O&M-V5-FAP-AVF-LCD R0 Pg 3 of 21 1.2.1 Zone Detection Module Zone Detection Module - ZDM Indicators and Control a) Fire (Red) : Zone in fire condition b) Fault (Amber) : Zone detection circuit open/short fault condition c) Disable (Amber) : Zone in disabled condition d) Disable Switch (Blue) : To disable zone fire &...
  • Page 5 O&M-V5-FAP-AVF-LCD R0 Pg 4 of 21 d) Disabled (Amber) : General Disabled Indicator, system in disabled condition e) System Fault (Amber) : Indicate Programmable Micro Controller failure f) Fire Sent (Red) : Fire Signal to Alarm Remote Monitoring Station activated (Optional)
  • Page 6: Lcd Event Logging Module

    O&M-V5-FAP-AVF-LCD R0 Pg 5 of 21 1.2.3 LCD Event Logging Module FIRE ALARM SYSTEM 07/04/06 M000 20:06 LCD Event Logging Module - LLM LCD Event Logging Module - LLM Indicators a) Power On (Green) : System energised by Mains and/or Standby Battery...
  • Page 7: Fire Alarm Condition

    O&M-V5-FAP-AVF-LCD R0 Pg 6 of 21 2.2 Fire Alarm Condition The panel / system shall enter into an alarm condition when an input device (such as smoke/heat detector, call point; or pressure/flow switch) is activated. Under Fire Alarm conditions: a) Twin “FIRE” LEDs (Red) of the alarm zone lighted b) General, “FIRE “...
  • Page 8: Resetting The System

    O&M-V5-FAP-AVF-LCD R0 Pg 7 of 21 2.2.2 Resetting the System Before the system is reset, the cause of the alarm must be investigated and duly rectified. In the case of a false alarm, make sure that there is no incident of fire before resetting the system.
  • Page 9: Initiating Evacuate Alarm

    O&M-V5-FAP-AVF-LCD R0 Pg 8 of 21 2.4 Initiating Evacuate Alarm The system is provided with a “Sound Alarm” switch in the event of emergency. To sound alarms for emergency evacuate: a) Press “Sound Alarm” switch (Red) (6) b) Sound Alarm amber LED lighted c) External alarm bells/sounders activated 2.4.1 Silencing Evacuate Alarm...
  • Page 10: Lcd Event Logging Module (Llm)

    O&M-V5-FAP-AVF-LCD R0 Pg 9 of 21 d) No outputs are activated (FIRE output, external Alarm Bells/ Aux output) e) When Retard State (20 sec) lapses, Retard State LED go off f) “CONFIRMATION STATE” LED (Amber) lighted (120sec) During Confirmation State (120sec)
  • Page 11 O&M-V5-FAP-AVF-LCD R0 Pg 10 of 21 2.8.1.a VIEW FIRE ARCHIVE To view the recorded alarm zone event; a) Press “Menu” b) Select “VIEW FIRE ARCHIVE” by “Up” / “Down” key and press “Enter” 017TC FIRE M00-Z005 02/04/06 15:32:12 (017TC: Total Event Counter “017”, Fire) (017: 17 event of 017TC, M00-Z005: “Main”...
  • Page 12 O&M-V5-FAP-AVF-LCD R0 Pg 11 of 21 (1) PNL ADR: To set the Panel Address, select by “Up” / “Down” key and press “Enter” to save (e.g. M000: Main Panel Address 000, S001: Sub Panel Address 001) PANEL ADDRESS M000 PRESS ENTER TO SAVE (2) TIME: To set the Time, select the time by “Up”...
  • Page 13: Routine Maintenance

    O&M-V5-FAP-AVF-LCD R0 Pg 12 of 21 3. ROUTINE MAINTENANCE 3.1 Introduction To ensure continuous reliability of the fire alarm system, regular testing and servicing shall be carried out. Only trained and competent personal are allowed to performance the routine testing and maintenance.
  • Page 14: Weekly Test

    O&M-V5-FAP-AVF-LCD R0 Pg 13 of 21 d) If possible, determine the cause of the fault or note the activities immediately prior to the area affected. e) Silence the fault buzzer. f) Inform the maintenance contractor responsible for servicing and arrange for repair.
  • Page 15: Annual Test

    O&M-V5-FAP-AVF-LCD R0 Pg 14 of 21 d) Check charger voltage and battery terminals condition. Ensure that no faults signal are indicated on the panel. e) Disconnect the battery supply. The “POWER ON” and “BATTERY FAULT” indicators should be lighted and the buzzer sounding. Connect back the battery and system should normalise itself.
  • Page 16 O&M-V5-FAP-AVF-LCD R0 Pg 15 of 21 c) Where the heat-sensitive element of thermal detectors or the enclosure of other detectors are found to be coated with paint or any material likely to affect the operation of the detectors, such material should be cleaned off or if necessary have the detector replaced.
  • Page 17: Fault Finding Tips

    O&M-V5-FAP-AVF-LCD R0 Pg 16 of 21 4. FAULT FINDING TIPS CHECK LIST ACTION SHOULD FAULT Specific BE TAKEN Possible Causes Indication Zone Fire - Manual Call-point - Vandalise - Inspect the alarm (False Alarm) - Glass Broken activated zone IF FALSE ALARM 1.
  • Page 18 O&M-V5-FAP-AVF-LCD R0 Pg 17 of 21 CHECK LIST ACTION SHOULD FAULT Specific Possible Causes BE TAKEN Indication Earth Fault Earth “+VE” (Red) - One or more Field - Shorted to Chassis / 1. Press “Buzzer (@ FBM) “+VE” line and/or Trucking / Conduit Silence”...
  • Page 19 O&M-V5-FAP-AVF-LCD R0 Pg 18 of 21 CHECK LIST ACTION SHOULD FAULT Specific Possible Causes BE TAKEN Indication Fire Line Trouble “1” (Amber) - Open - Fire signal Line - Disconnected 1. Press “Buzzer (Alarm Monitoring (@ DIM) Silence” (Black-1) - Termination...
  • Page 20: Technical Specification & Installation Diagram

    O&M-V5-FAP-AVF-LCD R0 Pg 19 of 21 Technical Specification Installation Diagram Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
  • Page 21: Technical Specification

    O&M-V5-FAP-AVF-LCD R0 Pg 20 of 21 TECHNICAL SPECIFICATION Fire Alarm Panel End Of Line I/P – O/P Description Capacity / Rating Feature Resistor (EOLR) ZONE - Min 4 Zones 6.8K Ohm - Line Open / Short supervised (Multiple of 4 Zones)
  • Page 22 ALM-2 BELL AUXILIARY Vanguard FUSES G-RST For General Auxiliary Signal V5-FBM-1 Transformer BATTERY AC 230V 24V DC MAIINS Vanguard V5-PSM-1 AC 230V Mains Supply 24V DC Standby Battery Title: Filename: Typical terminal installation layout of Fire Base Module (V5-FBM-1) V5-FBM-1-TIL...

Table of Contents

Save PDF