Operator's Manual
Extinguishing Control Panel

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the V5 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vanguard V5

  • Page 1 Operator’s Manual Extinguishing Control Panel...
  • Page 2: Table Of Contents

    O&M-V5-ECP-R0 Page 1 of 13 CONTENTS 1. GENERAL 1.1 Introduction 1.2 System Description 1.2.1 Extinguishing Control Module 1.2.2 System Control Module 2. OPERATING INSTRUCTIONS 2.1. Normal Operating Conditions 2.2. Fire Alarm Condition 2.2.1. Silencing the Alarm Bells / Sounders 2.2.2.
  • Page 3: General

    Inspection, please refer to the section covered in this manual. 1.2 System Description This Fire Extinguishing System utilises the V5 Extinguishing Control Panel. The system comprises an Extinguishing Control Panel which performs the task of processing the input signals and thereafter transmits the output signals or initiates other auxiliary functions.
  • Page 4: Extinguishing Control Module

    O&M-V5-ECP-R0 Page 3 of 13 1.2.1 Extinguishing Control Module Station Gas Control Module - GCM Detection Zone Indicators and Control (Detectors and Remote Manual release) a) Fire (Red) : Zone in fire condition b) Fault (Amber) : Zone detection circuit open/short fault condition...
  • Page 5: System Control Module

    O&M-V5-ECP-R0 Page 4 of 13 1.2.2 System Control Module Model No. Model No. System Control Module - SCM System Control Module - SCM System Control Module - SCM Indicators a) Power On (Green) : System energised by Mains and/or Standby Battery...
  • Page 6: Operating Instructions

    O&M-V5-ECP-R0 Page 5 of 13 2. OPERATING INSTRUCTIONS 2.1 Normal Operating Conditions Under normal operating conditions a) The green “POWER ON” LED lighted b) Countdown timer display indicating the Pre-set time eg : 30 for 30 sec time delay before firing...
  • Page 7: Silencing The Alarm Bells / Sounders

    O&M-V5-ECP-R0 Page 6 of 13 2.2.1 Silencing the Alarm Bells / Sounders It is a requirement under the Singapore standard Code of Practice CP 10: 2005 that the first alarm can only be silenced after 3 minutes of continuous operation and any subsequent alarms may be silenced immediately.
  • Page 8: Resetting The System

    O&M-V5-ECP-R0 Page 7 of 13 2.3.2 Resetting the System The cause of the fault should be investigated and rectified. If it is due to a mains supply failure, the system will normalise when the mains supply resumes. Some faults are internal to the system and are not covered in this manual.
  • Page 9: Routine Maintenance

    O&M-V5-ECP-R0 Page 8 of 13 3. ROUTINE MAINTENANCE 3.1 Introduction To ensure continuous reliability of the fire extinguishing system, regular testing and servicing shall be carried out. Only trained and competent personal are allowed to performance the routine testing and maintenance.
  • Page 10: Weekly Test

    O&M-V5-ECP-R0 Page 9 of 13 d) If possible, determine the cause of the fault or note the activities immediately prior to the area affected. e) Silence the fault buzzer. f) Inform the maintenance contractor responsible for servicing and arrange for repair.
  • Page 11 O&M-V5-ECP-R0 Page 10 of 13 e) Disconnect the battery supply. The “POWER ON” and “BATTERY FAULT” indicators should be lighted and the buzzer sounding. Connect back the battery and system should normalise itself. f) Switch off incoming mains supply. The “POWER ON”, “MAINS FAULT” and “CHARGER FAULT”...
  • Page 12: Annual Test

    O&M-V5-ECP-R0 Page 11 of 13 3.4.4 Annual Test The annual checks should include all the inspections and testing procedures specified in sections 3.4.1, 3.4.2, 3.4.3. and the following: a) The maintenance/servicing personnel should arrange to check the operation of all the detectors in an installation each year.
  • Page 13: Fault Finding Tips

    O&M-V5-ECP-R0 Page 12 of 13 4. FAULT FINDING TIPS CHECK LIST ACTION SHOULD FAULT Specific BE TAKEN Possible Causes Indication Zone / Manual Release - Manual Release - Vandalise - Inspect the alarm Station Fire Station - Glass Broken activated zone...
  • Page 14 O&M-V5-ECP-R0 Page 13 of 13 CHECK LIST ACTION SHOULD FAULT Specific BE TAKEN Possible Causes Indication Earth Fault Earth “+VE” (Red) - One or more Field - Shorted to Chassis / 1. Press “Buzzer (@ EBM) “+VE” line and/or Trucking / Conduit Silence”...