ADEMCO Vista-32FB Installation And Setup User's Manual
ADEMCO Vista-32FB Installation And Setup User's Manual

ADEMCO Vista-32FB Installation And Setup User's Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for Vista-32FB:
Table of Contents

Advertisement

9
,
6
7
$



)
%
9
,
6
7
$



)
%
&RPPHUFLDO)LUHDQG%XUJODU\
3DUWLWLRQHG6HFXULW\6\VWHP
ZLWK6FKHGXOLQJ
,QVWDOODWLRQDQG6HW8S*XLGH
FIRE
FIRE
PULL
K3521 3/99
www.PDF-Zoo.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Vista-32FB and is the answer not in the manual?

Questions and answers

Summary of Contents for ADEMCO Vista-32FB

  • Page 1 &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ ,QVWDOODWLRQDQG6HW8S*XLGH FIRE FIRE PULL K3521 3/99 www.PDF-Zoo.com...
  • Page 2: Recommendations For Proper Protection

    Recommendations for Proper Protection The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help Provide Proper Coverage For The Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    Table of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Recommendations for Proper Protection ......................ii How To Use This Manual ............................ix Conventions Used in This Manual........................x...
  • Page 4 VISTA-32FB Installation and Set-Up Guide Checkout Procedure for Hardwired Zones.......................6–6 Section 7 - 2-Wire Polling Loop Expansion ....................7–1 Polling Loop Overview ............................7–1 Common Characteristics of Polling Loop Zones....................7–1 Wiring/Addressing RPM Devices ........................7–2 Polling Loop Supervision ..........................7–5 Programming Polling Loop Zones ........................7–5 Checkout Procedure for Polling Loop Zones....................7–5...
  • Page 5 Table of Contents Section 14 - External Sounders........................14–1 General Information ............................14–1 Bell Circuit Supervision..........................14–1 Wiring Bell Outputs............................14–2 Compatible Alarm-Indicating Devices......................14–2 Programming the Bell Outputs ........................14–3 Section 15 - Auxiliary Relay..........................15–1 Relay Functions...............................15–1 Section 16 - Dialer Outputs ...........................16–1 Dialer Outputs Available..........................16–1 Telephone Line Connections...........................16–1 Telephone Line Supervision ...........................16–1 Dialer Operation..............................16–2...
  • Page 6 VISTA-32FB Installation and Set-Up Guide Zone Type Defaults ............................22–2 Section 23 - Data Field Descriptions ......................23–1 Section 24 - Scheduling Options ........................24–1 Introduction to Scheduling ..........................24–1 Time Window Definitions ..........................24–3 Open/Close Definitions ...........................24–4 Scheduling Menu Mode...........................24–6 Scheduling Menu Structure..........................24–7 Time Windows ..............................24–8 Daily Open/Close Schedules ...........................24–9...
  • Page 7 Table of Contents Panic Keys ...............................29–5 Speed Key [D] (Macros)...........................29–5 Manual Relay Activation Mode (#70 Mode) ....................29–6 Section 30 - Testing the System ........................30–1 Battery Test ..............................30–1 Dialer Test ...............................30–1 Fire Drill Test ([code] + [#69]) ........................30–2 One-Man Fire Walk-Test ([code] + [#68]) ......................30–2 Burglary Walk-Test (Code + TEST [5]) ......................30–3 Armed Burglary System Test .........................30–4 Trouble Conditions ............................30–4...
  • Page 8: List Of Figures

    Figure 17-1: Event Log Printer Connections ....................17–2 Figure 18-1: Wiring the 4100APG Without the Serial Printer...............18–2 Figure 18-2: Wiring the 4100APG With the Serial Printer ................18–3 Figure 25-1: Direct Wire Downloading Connections ..................26–4 VISTA-32FB Summary of Connections ..............Inside Rear Cover viii www.PDF-Zoo.com...
  • Page 9: How To Use This Manual

    Each of the sections covering the installation of peripheral devices includes the programming for that device. If you are an experienced user of ADEMCO products, you may choose to wire and then program the entire system at once. If so, refer to The Mechanics of Programming and Data Field Descriptions in the Programming Guide that has been supplied after the hardware setup is complete.
  • Page 10: Conventions Used In This Manual

    These prompts are shown in a single-line box. = Quit) When programming the system, data fields are indicated by a “star” ( ) followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent ADEMCO products. www.PDF-Zoo.com...
  • Page 11: Section 1 - General Description

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General The VISTA-32FB is a 2-partition, UL listed commercial fire and burglary control panel that supports up to 32 zones using basic hardwired, polling loop, and wireless zones. It also includes zones for supervision of bells, phone lines, keypads, RF receivers, and relays.
  • Page 12 VISTA-32FB Installation and Set-Up Guide Wireless Expansion Supports up to 32 wireless zones using 5881 type RF receiver (fewer if using hardwire and/or polling loop zones). Wireless zones have the following characteristics: • Supervised by control panel for check-in signals (except certain nonsupervised transmitters).
  • Page 13 Section 1 – General Description • All zones (except fire) that can be assigned to either of two partitions. • Fire zones must be assigned to Partition 1. • Keypads that can be assigned to either of two partitions or to Master Partition 3 to view system status.
  • Page 14 Arm and disarm security system. • Control relays. The 4285/4286 VIP Module is not Listed for use with the VISTA-32FB Control Panel in a UL commercial installation . Optional 24-Volt Power Supply Compatible with the PS24 Power Supply Module, which supplies two 24VFW, 1.7A full- wave- rectified, unfiltered outputs.
  • Page 15 Supports use of 5140DLM Backup Dialer for connecting to a second supervised telephone line. Optional Keyswitch Supports the ADEMCO 4146 Keyswitch on any one of the system's 2 partitions. If used, zone 7 is no longer available as a protection zone. Voltage Triggers Provides a trigger connector whose pins change state for different conditions.
  • Page 16 • UL864-NFPA 72 Local, Central Station, and Remote Station. Burglary The below listings apply when the VISTA-32FB is used with the optional VISTA-ULKT enclosure kit and optional 1451 transformer. • UL609 Grade A Local Mercantile Premises and Mercantile Safe and Vault.
  • Page 17: Section 2 - Planning A Partitioned System

    S E C T I O N Planning a Partitioned System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Theory of Partitioning Setting Up a Partitioned System...
  • Page 18: Setting Up A Partitioned System

    VISTA-32FB Installation and Set-Up Guide Setting Up a Partitioned System The basic steps to setting up a partitioned system are described below. If more information on how to program the prescribed options is required, see Section 20: The Mechanics of Programming as well as each corresponding section's programming procedure.
  • Page 19 Section 2 – Planning a Partitioned System c. Arming the partition that is programmed to arm the lobby will cause the system to automatically attempt to arm the lobby. If any faults exist in the lobby partition, or another partition that affects the lobby is disarmed, the lobby cannot be armed, and the message UNABLE TO ARM LOBBY PARTITION will be displayed.
  • Page 20 VISTA-32FB Installation and Set-Up Guide In the tables below, the notations in parentheses ( ) indicate the current status of the other partition when the user takes action. Sequence #1: Office 1 Office 2 Lobby Action Disarms (Armed) Disarms User #1:...
  • Page 21: Master Keypad Setup And Operation

    Section 2 – Planning a Partitioned System • Wireless Button. • Wireless Keypad. Arming/Disarming Remotely If arming or disarming remotely (through Compass downloading software), the lobby will not automatically follow another partition that is programmed to arm or disarm the lobby. The lobby must be armed separately, after arming all affecting partitions first.
  • Page 22 VISTA-32FB Installation and Set-Up Guide Pressing [ ] will cause the following display to appear at Partition 1's keypad(s): FAULT 002 LOADING DOCK WINDOW Additional zone faults will be displayed one at a time. To display a new partition's status, press [ ] + [Partition No.].
  • Page 23: Section 3 - False Alarm Reduction Features

    Dialer reports will be sent to the central station if programmed: • Exit Error by User (not sent if using ADEMCO High Speed format). • Exit Error by Zone (Sent as regular alarm if using ADEMCO High Speed format). • Bypass report. 3–1...
  • Page 24: Recent Close Report

    VISTA-32FB Installation and Set-Up Guide Recent Close Report Another report, designed to notify the central station that an alarm has occurred within 5 minutes of arming, is called the Recent Close report. This report, as well as the Exit Error reports, are programmed in Report Code Programming Mode (refer to # 93 Menu Mode in the Quick Start Guide).
  • Page 25: Call Waiting Defeat Logic

    Section 3 – False Alarm Reduction Features Conditions That Affect Cross-Zone Operation 1. In the event of a continuous fault (lasting at least 5 minutes) on one of the paired zones, a fault on the second zone will cause an alarm immediately. 2.
  • Page 26 VISTA-32FB Installation and Set-Up Guide 3–4 www.PDF-Zoo.com...
  • Page 27: Section 4 - Installing The Control

    DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED. Installing the Cabinet Lock Use an ADEMCO No. N6277 Cam Lock and No. N6277-1 Clip supplied with the panel. RETAINER CLIP (NOTE POSITION) 1.
  • Page 28: Grade A Mercantile Premises Listing

    VISTA-ULKT enclosure kit) to the cabinet's right-side wall as shown in the diagram below, and wire it to zone 6. • Use a bell with a tamper-protected housing such as the ADEMCO AB12. The bell housing's tamper switch and inner tamper linings must also be wired to zone 6. •...
  • Page 29: Grade A Mercantile Safe And Vault Listing

    Follow the instructions given above for Mercantile Premises listing. • The back of the panel’s box must have pry-off tamper supervision. Mount an ADEMCO No. 112 Tamper Switch (not supplied with the VISTA-ULKT enclosure kit) into the hole provided in the back of the panel box. This switch must be wired to zone 6. This switch...
  • Page 30: Connecting The Ac Transformer And Battery

    VISTA-32FB Installation and Set-Up Guide Connecting the AC Transformer and Battery As shipped, the VISTA-32FB is supplied with a built-in 18VAC transformer. This transformer must be hard-wired into the premises’ electrical system. The optional 1451 18VAC transformer, along with the optional VISTA-ULKT enclosure kit, must be used for UL listed commercial burglary installation.
  • Page 31: Section 5 - Installing The Keypads

    S E C T I O N Installing the Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Keypads That May Be Used Wiring to the Keypads...
  • Page 32: Using A Supplementary Power Supply To Power Additional Keypads

    VISTA-32FB Installation and Set-Up Guide 3. Run field wiring from the control to the keypads (using standard 4-conductor cable of the wire gauge determined in step 1). 4. If only one keypad is being used, it may be connected to either Keypad Port 1 or 2, and must be mounted on, or within 3 ft.
  • Page 33: Mounting The Keypads

    Section 5 - Installing The Keypads SUPPLEMENTARY COMMUNICATOR POWER SUPPLY TERMINAL STRIP – AUX AUX. DATA DATA – IMPORTANT: MAKE CONNECTIONS DIRECTLY TO SCREW IMPORTANT: TERMINALS AS SHOWN. Make connections directly to screw terminals. Make no connection to the keypad blue wire (if present). Figure 5-2: Using a Supplementary Power Supply for Keypads Mounting the Keypads Mount the keypads at a height that is convenient for the user.
  • Page 34 VISTA-32FB Installation and Set-Up Guide If the READY message does not appear on any of the keypads in the system (in either of the partitions), or a NOT READY message is displayed, check the keypad wiring connections. Make sure each of the 8 basic hardwired zones has a 2000-ohm resistor connected across its terminals.
  • Page 35: Common Characteristics Of Hardwired Zones 1-8

    S E C T I O N Basic Hardwired Zones 001-008 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Common Characteristics of Hardwired Zones 1-8 Wiring Burglary and Panic Devices to Zones 1-8...
  • Page 36 VISTA-32FB Installation and Set-Up Guide The maximum zone resistance is 100 ohms for zones 1, 2, and 8, and 300 ohms for all other zones (excluding the 2K EOL resistor). Wiring 2-Wire Smoke Detectors to Zones 1 and 2 Zones 1 and 2 have the added capability of supporting 2-wire smoke detectors. Each zone provides enough standby current (2mA) to power up to sixteen of the smoke detectors listed below.
  • Page 37 Photoelectric duct detect. System Sensor 2451 w/DH400 base These smoke detectors are UL Listed for use with the VISTA-32FB and are the only 2-wire smoke detectors that may be used. Wiring 4-Wire Smoke Detectors to Zones 1-8 When programmed for fire warning usage, all zones can monitor 4-wire smoke detectors (zone types 9, 16), N.O.
  • Page 38: Figure 6-2: 4-Wire Smoke Detector Connections (Zones 1-8)

    This feature eliminates false alarms due to electrical or physical transients. Zone 6 Tamper Configuration Zone 6 may be used as a tamper loop for the VISTA-32FB Cabinet Door Tamper Switch and for the ADEMCO AB12 Grade A Burglary Bell Box Tamper Switches and Tamper Liner.
  • Page 39 Section 6 – Basic Hardwired Zones when more than one burglary partition is used. Enable the Zone 6 Alternate Tamper Function (program field 3 17). When set in this manner, the zone will trigger a trouble when the panel is disarmed and an alarm when the panel is armed, when the zone senses either an open or a short, or when an earth ground fault caused by drilling through the AB12 housing is detected.
  • Page 40: Checkout Procedure For Hardwired Zones

    VISTA-32FB Installation and Set-Up Guide You can use detectors that exceed 1.1k ohms in alarm, provided they maintain a voltage drop of less than 3.8 volts in alarm. Programming Hardwired Zones Each zone must be programmed into the system, which assigns characteristics that define the way the system responds to faults on that zone.
  • Page 41: Section 7 - 2-Wire Polling Loop Expansion

    S E C T I O N 2-Wire Polling Loop Expansion (Zones 009 - 032) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Polling Loop Overview Common Characteristics of Polling Loop Zones...
  • Page 42 VISTA-32FB Installation and Set-Up Guide Wiring/Addressing RPM Devices All devices on the polling loop must be wired in parallel to the [+] and [-] polling loop terminals of the control panel (28 and 29). You can wire from device to device, or have multiple branches connected directly to the control panel in a star configuration, as shown in Figure 7-1.
  • Page 43: Figure 7-1: Polling Loop Connections

    Certain polling loop devices have a DIP switch that can be used either to select the device's zone number or to select the enrolling of a unique, embedded serial number by the control panel. When used with VISTA-32FB, these devices must be set for the serial number mode of operation.
  • Page 44: Figure 7-2A: Polling Loop Connections Using One 4297 Extender Module

    VISTA-32FB Installation and Set-Up Guide Notes: - Do not use the 4197 module. - Refer to 4297 instructions for more detailed installation information. The limits shown below supercede the limits described in the 4297 instructions. - Do not connect 4297 modules in series.
  • Page 45 Section 7 – 2-Wire Polling Loop Expansion Polling Loop Supervision A short on the polling loop is indicated by a trouble condition on its supervisory zone (zone 997). This reports as a trouble condition only. As such, a polling loop should be assigned either zone type 05 or type 19, if annunciation as a trouble condition is desired.
  • Page 46 The 4190WH/SN right loop must not be used, and the left loop must be EOLR-supervised. • The 4278 Auxiliary Sensor Loop cannot be used. • The 4297 must be powered from the VISTA-32FB Auxiliary Power Output or from a UL Listed supplementary power supply. Compatible Polling Loop Devices •...
  • Page 47 Section 7 – 2-Wire Polling Loop Expansion Compatible Polling Loop Devices (continued) • 4275EX Vplex PIR Dual element PIR with built-in RPM (connects directly to the polling loop). • DIP switch-programmable. • Includes mirrors for both wide-angle and curtain/long-range applications and can use the 1875PA Pet Alley mirror.
  • Page 48 VISTA-32FB Installation and Set-Up Guide Compatible Polling Loop Devices (continued) • 5192SD Photoelectric Smoke Low profile. Detector • One-piece photoelectric smoke detector with built-in Vplex communication circuitry • 5192SDT Photoelectric Smoke Low profile. Detector, with Heat • One-piece photoelectric smoke detector Detector with built-in heat detector 135°F (57°C)
  • Page 49: Section 8 - Wireless Zone Expansion

    The following receivers may be used with this system. Each may support the number of zones shown below. Note that the VISTA-32FB can support up to a maximum of 32 zones so the number of wireless zones that can be used will be decreased by the number of hardwire and polling loop zones that are defined.
  • Page 50: Rf System Operation And Supervision

    VISTA-32FB Installation and Set-Up Guide 5800 Series Recvr Zones 5881L up to 8 5881M up to 16 5881H up to 32 5881EH up to 32 (use w/UL864 installations) In Canada, 5800 systems must use 5882 Series receivers: 5882L/5882H. Information in this manual relative to the 5881 receivers applies as well to the 5882 receivers.
  • Page 51: Rf System Installation Advisories

    Section 8 – Wireless Zone Expansion • Two identical receivers can be used to provide either a greater area of coverage or redundant protection. • Any zone from 1 to 32 can be used as a 5800 Series wireless zone. RF System Installation Advisories •...
  • Page 52: Installing The 5800Tm Module

    VISTA-32FB Installation and Set-Up Guide 4. Set the receiver’s DIP switches for an address (01-07) that is not being used by another device (i.e., keypads, relay modules, etc.). Take note of the address selected for the RF receiver, as this address must be enabled in the system’s Device Programming in # 93 Menu Mode ( refer to the Quick Start Guide ).
  • Page 53: 5800 Series Transmitter Setup

    Section 8 – Wireless Zone Expansion 5800 Series Transmitter Setup 5800 Series transmitters have built-in serial numbers that must be enrolled by the system using # 93 Menu Mode Programming (refer to the Quick Start Guide) or input to the control via the downloader.
  • Page 54 VISTA-32FB Installation and Set-Up Guide Transmitter Battery Life • Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.
  • Page 55 Section 8 – Wireless Zone Expansion Compatible 5800 Series Transmitters (continued) • 5802MN Miniature (Personal UR or RF Has single pushbutton Emergency Transmitter) • Usually programmed for a response type of 24 Hr. Audible or 24 Hr. Silent (other zone responses are possible).
  • Page 56: Programming Wireless Zones

    VISTA-32FB Installation and Set-Up Guide Compatible 5800 Series Transmitters (continued) • 5819 Shock Sensor Shock sensor analyzer for ADEMCO Inertial Cross-Bar, Ultrak, Litton, Inertiaguard shock sensors. • Built-in Reed magnetic contact. • Programmable analyzer responses. • 5827 Wireless Keypad House ID Can be used to turn the burglary protection on and off.
  • Page 57: Checkout Procedure For Wireless Zones

    Section 8 – Wireless Zone Expansion Checkout Procedure for Wireless Zones Transmitter ID Sniffer Mode Use the Transmitter Sniffer Mode to test that transmitters have all been properly programmed. 1. Enter [Installer Code] + [#] + [3]. Keypad(s) will display all zone numbers of wireless units programmed for that partition.
  • Page 58 VISTA-32FB Installation and Set-Up Guide 8–10 www.PDF-Zoo.com...
  • Page 59: Section 9 - Relay Outputs

    S E C T I O N Relay Outputs • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Relay Basics Wiring the 4204 and 4204CF Relay Modules...
  • Page 60: Programming Relays

    VISTA-32FB Installation and Set-Up Guide 3. Homerun each remotely mounted module back to the control. The table below shows the maximum wire run lengths from the control to each 4204. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.
  • Page 61: Figure 9-1B: 4204Cf Relay Module

    Section 9 – Relay Outputs SWITCH 4 2 0 4 C F A D D R E S S S E T T I N G S POSITION ("—" means "OFF") — — — — — — — — — —...
  • Page 62 VISTA-32FB Installation and Set-Up Guide 9–4 www.PDF-Zoo.com...
  • Page 63: Section 10 - 4285/4286 Vip Module

    S E C T I O N 4285/4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section General Information Mounting the VIP Module...
  • Page 64 VISTA-32FB Installation and Set-Up Guide Mounting the VIP Module The VIP Module may be mounted in the control cabinet if space is available or, if this is not possible, on the side of the cabinet or adjacent to it. Pry off the VIP Module's cover before wiring.
  • Page 65: Figure 10-1: 4285/4286 Vip Module Connections

    Section 10 – 4285/4286 VIP Module ANSWERING MACHINE NOT INSTALLER ADJUSTABLE Figure 10-1: 4285/4286 VIP Module Connections 1. Make all connections exactly as shown in Figure 10-1 . This is essential, even if the system is not connected to a central station. The 4285/4286 will not function if this is not done. If the leads on the cable are too short to reach their assigned terminals, splice additional wires to them, as required.
  • Page 66 VISTA-32FB Installation and Set-Up Guide 10–4 www.PDF-Zoo.com...
  • Page 67: Section 11 - Audio Alarm Verification (Aav) Unit

    S E C T I O N Audio Alarm Verification (AAV) Unit • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section General Information AAV Module Operation...
  • Page 68: Audio Alarm Verification Module Connections

    VISTA-32FB Installation and Set-Up Guide and send the new Fire Alarm report, then re-trigger the AAV Mode. All other dialer messages triggered during ongoing conversation will be held until either the AAV Module signals that it is inactive, or the 15-minute timeout occurs.
  • Page 69: Figure 11-1: Audio Alarm Verification Module Connections

    Section 11 – Audio Alarm Verification GRAY RJ31X INCOMING CONTROL JACK TELCO LINE BROWN GREEN EAGLE JACK 11 12 13 14 SUPPLIED CABLE CALLER ID UNIT CONTROL/ DIALER HEADER 4204 RELAY 1 BROWN SHOWN PREMISES DIP Switch ANSWERING MACHINE AND NO NC C PHONES ANSWERING...
  • Page 70 VISTA-32FB Installation and Set-Up Guide 11–4 www.PDF-Zoo.com...
  • Page 71: Section 12 - J2 Trigger Outputs

    • UL Listed keyswitch. • 5140LED Indicator Module. • Auxiliary alarm signaling equipment such as an ADEMCO Long Range Subscriber Radio. • Event logging serial printer (via the 4100SM Interface Module). • PC computer used to direct-wire download the panel's programming information (via the 4100SM Interface Module).
  • Page 72: Remote Keypad Sounder Operation And Wiring

    Figure 12-2: Remote Keypad Sounder Wiring Remote Keyswitch Operation and Wiring An optional UL Listed remote keyswitch, such as the ADEMCO 4146, can be used for remote arming/disarming of the burglary portion of the system and for remotely silencing alarms. If used, the following must be programmed: 12–2...
  • Page 73: Figure 12-3: Remote Keyswitch Wiring

    4146 KEYSWITCH Figure 12-3: Remote Keyswitch Wiring Keyswitch Operation The VISTA-32FB allows two modes of keyswitch operation. When field 15 is set to a partition (1-2), the keyswitch operates as follows: With System Disarmed and No Alarms Present A momentary short across zone 7 will arm the partition in the AWAY mode, and a short held for more than 10 seconds will arm the partition in the STAY mode.
  • Page 74: 5140Led Indicator Module

    VISTA-32FB Installation and Set-Up Guide With Alarms Present A momentary short across zone 7 will silence alarm bell and keypad sounds, and will disarm the partition if it was armed. The keyswitch LEDs provide a memory of alarm indication (see table below).
  • Page 75: Auxiliary Alarm Signaling Equipment

    • Opening/closing (arming/disarming). These triggers may be used to trip auxiliary alarm signaling equipment such as ADEMCO’s 7720, 7720ULF, and 7920SE Long Range Radios, 7820 Transmitter (when set to the zone mode), and 7835 Tranceiver (when set to the zone mode). Note that not all of these triggers are available for all settings of field 3 20.
  • Page 76: Figure 12-5A: Connections To 7720 Long Range Radio

    VISTA-32FB Installation and Set-Up Guide armed, and HIGH when any enabled partition is disarmed. The remaining triggers are normally LOW and go HIGH when the corresponding condition occurs in at least one enabled partition. The fire and burglary/audible panic alarm triggers remain HIGH until a [User Code] + [OFF] is entered in all enabled partitions that display these conditions.
  • Page 77: Figure 12-5B: Connections To 7720Ulf Long Range Radio

    Section 12 – J2 Trigger Outputs 7720 ULF WIRING DIAGRAM J2 CONNECTOR RADIO FAULT (PROGRAM FOR SHORT ON FAULT) SEE 7720 ULF INSTRUCTIONS FOR 7720 ULF RADIO MORE DETAILED INSTALLATION 4142TR INFORMATION CABLE 4142TR CABLE FAULT WIRE FAULT COLORS - CUT RESISTOR JUMPERS Z1-Z5. - DO NOT USE 2k EOL RESISTOR.
  • Page 78: Event Log Printer Connections

    1. An earth ground fault indication can be received when the 4100SM Module is clipped directly onto a side-wall of the VISTA-32FB cabinet. If this occurs, use an insulator to insulate the 4100SMs clip-on bracket from the VISTA-32FB cabinet sidewall. Later- production versions of the 4100SM have the clip-on bracket isolated from the circuit ground (Terminal 7) and will not have this problem.
  • Page 79: Section 13 - 7820/7835/7835C Long Range Radio

    11 is not, zone 10 will report via the LRR but zone 11 will not. The priority of events from most to least important, transmitted from the VISTA-32FB to the LRR, is: Fire Alarms, Panic Alarms, Burglary Alarms, Fire Troubles, Non-Fire Troubles, Bypasses, Openings/Closings, Test messages, and all other types of reports.
  • Page 80: Figure 13-1: Long Range Radio To Keypad Terminals

    The control will then proceed to the next event in the queue. If split reporting is selected for the VISTA-32FB, then the LRR will follow that option. The radio will send the appropriate reports to the primary and secondary central stations.
  • Page 81: Trouble Messages

    Section 13 – 7820 Long Range Radio Trouble Messages The following messages will be displayed on the 6139 Alpha Keypad when a problem exists in the Long Range Radio: 1. LRR Battery: The battery connected to the radio is low. 2.
  • Page 82 VISTA-32FB Installation and Set-Up Guide 13–4 www.PDF-Zoo.com...
  • Page 83: Section 14 - External Sounders

    Selectable for no timeout or timeout of 2-30 minutes. The optional PS24 Power Supply Module may be used to convert one or both of the VISTA-32FB 12VDC, 1.7A supervised bell outputs to 24VFW, 1.7A supervised bell outputs. The PS24 module must be used with the optional VISTA-ULKT enclosure kit (PS24 mounts in this kit’s enclosure)
  • Page 84: Wiring Bell Outputs

    Note that a local burglary Grade A listing requires that a bell in a tamper-protected housing be used (such as ADEMCO AB12) and that bell wiring be run in conduit. By default, Bell 2 is set to operate as a supervised fire bell output. Note that the panel supervises this wiring for open, short, and earth ground faults.
  • Page 85: Programming The Bell Outputs

    Section 14 – External Sounders AB12 WIRING NOTES: • Disconnect the AB12’s factory-wired connection from its terminal #4 to its outer box. • Set field 3 17 to “1” to enable zone 6 tamper function. AB12 BELL/BOX WIRING • Assign zone 6 to a burglary partition. Program it for day trouble/night alarm response (type 05) when this bell is used by only one burglary partition.
  • Page 86 VISTA-32FB Installation and Set-Up Guide 14–4 www.PDF-Zoo.com...
  • Page 87: Section 15 - Auxiliary Relay

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Relay Functions The VISTA-32FB provides a built-in Form C relay with contacts rated at 28VAC/VDC, 2.8 amps max. This relay may be programmed for one of the functions below (determined by program field 3 61): •...
  • Page 88: Figure 15-2: Auxiliary Relay Used For Resetting 4-Wire Smoke Detectors

    VISTA-32FB Installation and Set-Up Guide Trouble/Supervisory Activation (3 61 = 0): Steady activation in response to any zone or system-related trouble condition or to any fire supervisory condition. Remains activated until all fault conditions have been corrected and the [User Code] + [OFF] has been entered.
  • Page 89: Section 16 - Dialer Outputs

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Dialer Outputs Available The VISTA-32FB provides one main built-in dialer for communication to the central station and one optional 5140DLM Backup Dialer, both supervised for voltage and current on the phone lines.
  • Page 90: Dialer Operation

    When both main and backup dialers are enabled ([1,1] in field 3 30), the VISTA-32FB will attempt to route all calls over the main output until a fault is detected, at which time it will attempt to use the backup output. Line faults will result in a zone 974-DIALER 1 FAULT or a zone 975-DIALER 2 FAULT display.
  • Page 91: Section 17 - Event Log Options

    3 19 must be set to 1. This setting overrides the functions selected for INPUT 1 and OUT 2 made in field 3 20. Connect a UL EDP Listed serial printer to the J2 connector using an ADEMCO 4100SM Interface Module as shown in Figure 17-1.
  • Page 92: Figure 17-1: Event Log Printer Connections

    The 4100SM Module is supplied with a 10-foot RS232 cable. A longer cable or an extension cable can be used if the VISTA-32FB and serial printer are separated by more than 10 feet, but the total cable length should be less than 50 feet.
  • Page 93: Programming Event Log Options

    Section 17 – Event Log Options Programming Event Log Options 1. With at least one alpha keypad (6139/6139R) wired and set to a proper address, temporarily apply power to the system. 2. Enter Data Field Programming Mode: [Installer Code] + [8 0 0]. 3.
  • Page 94 VISTA-32FB Installation and Set-Up Guide The system allows viewing of any partition's event log. Enter SCAN LOG BY PART the partition number for the partition whose events are to be 0=NO 1-2=PART # displayed. Entering 0 (NO) will display all events that occurred in the system, regardless of partition.
  • Page 95 Section 17 – Event Log Options Press 1 if Event Log Clear function is to be performed. Clearing CLEAR EVENT LOG the event log does not erase any events from the system 0=NO 1=YES memory. All events in the log will still be displayed if the COMPLETE option is selected.
  • Page 96 VISTA-32FB Installation and Set-Up Guide 17–6 www.PDF-Zoo.com...
  • Page 97: Section 18 - 4100Apg Pager Interface

    If the 4100APG cannot make contact with the paging service, it will retry up to 10 times. If the interface loses contact with the VISTA-32FB, it will send a message to the paging service to notify the user.
  • Page 98: Wiring The 4100Apg

    Wiring the 4100APG Without the Event Log Printer The 4100APG connects to the VISTA-32FB via the 4100SM. The 4100SM is wired to the J2 connector on the control via the 4142TR Cable. See Figure 18-1. Connecting the 4100SM to the control 1.
  • Page 99: Programming The Control For The Pager

    Section 18 – 4100APG Pager Interface With the Event Log Printer The VISTA-32FB will support the 4100APG and serial printer. See Figure 18-2. The serial printer must be configured for 1200 baud rate, seven data bits, even parity, and one stop bit.
  • Page 100: 4100Apg Led Indications

    VISTA-32FB Installation and Set-Up Guide • In field 70 enter the Pager ID number of the paging service for Bypass reports. This is the PIN number. Up to 10 digits may be entered. • In field 71 enter the phone number of the paging service for Open/Close reports. Up to 17 digits may be entered.
  • Page 101: Section 19 - Final Power-Up Procedure

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Connecting the AC Transformer The VISTA-32FB has a built-in , enclosed AC power transformer with manually resettable circuit breaker protection, located in the lower left-hand corner of the control’s cabinet.
  • Page 102: Earth Ground Connections

    Backup Battery Calculations In the event of an AC power loss, the VISTA-32FB must be supported by a 12VDC, 7AH min/34.4 max sealed lead acid battery. As shipped, the VISTA-32FB enclosure can house up to 14AH batteries (i.e., two 7AH batteries wired in parallel).
  • Page 103: Total Control Panel Load Worksheets

    Section 19 – Final Power-Up Procedure Polling Loop Current Draw Worksheet Refer to the Polling Loop Expansion section for device restrictions for fire and burglary usage. RPM DEVICE CURRENT # OF UNITS TOTAL 4192SD Photo Smoke 0.4mA 4192SDT Smoke w/Heat 0.4mA 4192CP Ion Smoke 0.4mA...
  • Page 104 VISTA-32FB Installation and Set-Up Guide 2. Enter devices used AUX. POWER 2 OUTPUT Total Current on Aux. Power 2 Device Model # Device Current X # of Units = Standby Alarm output, calculate standby and alarm currents, then add to get Aux. Power 2 current subtotal.
  • Page 105 5140DLM Backup Dialer Module 15mA (inactive) (inactive) *5140DLM actually draws 55mA when active. However, since VISTA-32FB PCB current includes built-in main dialer current, and since main dialer is inactive when 5140DLM is active, 5140DLM imposes only 15mA added current on power supply.
  • Page 106: Making The Battery Connections

    VISTA-32FB Installation and Set-Up Guide 10. Using the battery Battery Selection Table capacity value from Capacity Recommended Battery Comments step 9, select the 7 AH Yuasa NP7-12 appropriate battery. 12 AH Yuasa NP12-12 Fits in VISTA-ULKT enclosure only. 14 AH...
  • Page 107: Battery Supervision

    Black to the negative (-) terminal on the battery. Battery Supervision The VISTA-32FB runs a brief battery test once a minute to determine if battery leads are connected, and runs an extended battery test every 24 hours to determine if battery capacity is low (less than approximately 11.5VDC).
  • Page 108 VISTA-32FB Installation and Set-Up Guide 19–8 www.PDF-Zoo.com...
  • Page 109: Section 20 - The Mechanics Of Programming

    • There are four sets of pre-programmed communication defaults available, including Low Speed, 4+2 Express, ADEMCO High Speed, and ADEMCO Contact ID. Loading one of these defaults automatically programs industry standard codes that will suit most needs. •...
  • Page 110: Entering Data Field Programming Mode

    VISTA-32FB Installation and Set-Up Guide The factory-loaded defaults ( 97) enable keypad addresses 00-01 only. A keypad set to one of these addresses must be used to program the system. Entering Data Field Programming Mode Enter Program Mode using either method A or B: A.
  • Page 111: Entry Errors

    Section 20 – The Mechanics of Programming Entry Errors • If an invalid address is entered, the keypad will display FC. • If a program entry is improperly entered (for example, a number larger than permitted), the entry position of the keypad display will go blank. •...
  • Page 112: # 93 Menu Mode Programming

    VISTA-32FB Installation and Set-Up Guide 2. Enter a partition-specific field number (e.g., 09) to begin programming. When the first field’s entry is completed, the next partition-specific field will automatically be displayed. When all partition-specific fields are programmed, the system returns to the global programming fields (page 1 fields).
  • Page 113: Section 21 - Zone Type Definitions

    S E C T I O N Zone Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Zone Number Designations Zone Type Definitions...
  • Page 114 VISTA-32FB Installation and Set-Up Guide Type 02: Entry/Exit #2 Burglary This zone type provides a secondary entry delay whenever the zone is faulted if the panel is armed in the AWAY or STAY Mode. When the panel is armed in the INSTANT or MAXIMUM Mode, no entry delay is provided.
  • Page 115 Section 21 – Zone Type Definitions Type 16: Fire With Verification This zone type is used when smoke alarm verification is desired on hardwire and polling loop zones containing only 2-wire or 4-wire smoke detectors. An open will initiate a trouble response and a short will initiate a fire alarm response.
  • Page 116 VISTA-32FB Installation and Set-Up Guide 21–4 www.PDF-Zoo.com...
  • Page 117: Section 22 - Zone Index/Zone Type Defaults

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone Index The VISTA-32FB has 32 protection zones, as well as supervisory zones for relays, ECP devices (devices that communicate through the keypad terminals), and system troubles.
  • Page 118: Zone Type Defaults

    Zone 977 is assigned to the J2 LRR Output Triggers for the purpose of allowing the operation of the outputs to be bypassed. Zone Type Defaults Following are the zone type defaults for zones on the VISTA-32FB: Zone # Zone Type...
  • Page 119: Section 23 - Data Field Descriptions

    S E C T I O N Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • The following is a description of all data fields provided by this control.
  • Page 120 VISTA-32FB Installation and Set-Up Guide [04] 13 BELL 1 TIMEOUT (partition-specific) Defines the length of time Bell Output 1 and the keypad's sounder will sound for all audible alarms (about 1-2 minutes). Arm the panel and fault the polling loop zone.
  • Page 121 Section 23 – Data Field Descriptions 23 MULTIPLE ALARMS (partition-specific) Determines whether or not more than one alarm can be sounded in a given zone during an armed period. Note that multiple alarm soundings will not occur more frequently than allowed by the programmed alarm sounder duration. This selection applies to local sounding and has no impact on the number of communication messages transmitted.
  • Page 122 If selecting TouchTone, make sure the subscriber has requested and is paying for Touch-tone service. Note that whether or not Touch-tone dialing for call placement is permitted, communication by the use of DTMF signaling (ADEMCO High Speed) will still take place. See field 1 33 TouchTone W/Rotary Backup.
  • Page 123 Section 23 – Data Field Descriptions 35 DOWNLOAD PHONE NUMBER | | | | | | | | | | | | | | | | This field is applicable only if downloading will be utilized. Enter the downloading phone number, up to 17 digits, 0-9; enter #11 for , #12 for #, and #13 for a 2-sec.
  • Page 124 Enter the appropriate number for the primary format as follows: 0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed; 3=ADEMCO Express 46 LOW SPEED FORMAT (PRIMARY) Enter the appropriate value: 0=ADEMCO Low Speed; 1=Sescoa/Radionics 47 SECONDARY FORMAT This field selects the reporting format for the secondary telephone number.
  • Page 125 Section 23 – Data Field Descriptions [0,0] 49 CHECKSUM VERIFICATION Enter 1 for either or both primary/secondary formats to send a verification digit to validate the message at the receiver without having to send two message rounds. Selection is valid for 3+1, 4+1, and 4+2 reports. Enter 0 if not desired.
  • Page 126 VISTA-32FB Installation and Set-Up Guide 58 LONG RANGE RADIO CENTRAL STATION #1 CATEGORY ENABLE Trbl Opn/Cls Syst Test Enter 1 to enable reports for primary Subscriber ID of Long Range Radio. Otherwise, enter 0. 59 LONG RANGE RADIO CENTRAL STATION #2 CATEGORY ENABLE...
  • Page 127 Section 23 – Data Field Descriptions 71 PAGER PHONE NUMBER FOR OPENS/CLOSES | | | | | | | | | | | | | | | | This field is used to enter the alphanumeric paging service phone number for Open/Close reports.
  • Page 128 VISTA-32FB Installation and Set-Up Guide 83 FIRST TEST REPORT TIME [00, 12, 00] Enter the day (00-07) and time (00-23 hours/00-59 min.) that the first Test report shall be transmitted. Enter 00 in all locations if the Test report is to be sent immediately upon exiting.
  • Page 129 Section 23 – Data Field Descriptions 1 17 LOBBY PARTITION Enter the Common Lobby Partition (1-2). Enter 0 if none. 1 18 AFFECTS LOBBY (partition-specific) Enter 1 if this partition affects the common lobby. The system will not arm the lobby unless this partition is armed already.
  • Page 130 VISTA-32FB Installation and Set-Up Guide 1 26 PANIC BUTTON OR SPEEDKEY [00,00,00,00] For each lettered key A-C, enter 00 to assign that key’s respective panic function, or enter a speedkey macro number 01-32 to assign a particular macro to that key. For the D key, enter 00 to use the D key to select a macro to execute when key is pressed, or enter a macro number 01-32 to execute a particular macro with the D key.
  • Page 131 Section 23 – Data Field Descriptions 1 33 TOUCH-TONE W/ROTARY BACKUP Enter 1 to enable rotary backup dialing if communicator is not successful in dialing using Touch-tone DTMF on first attempt. Enter 0 if this option is not desired. 1 34 COMM. SPLIT REPORT SELECTION This field allows certain reports to be directed to either the primary or secondary phone number.
  • Page 132 VISTA-32FB Installation and Set-Up Guide 1 48 WIRELESS KEYPAD ASSIGNMENT Enter the partition in which RF keypad is used, 1-2. Enter 0 if no RF keypad is used. 1 49 SUPPRESS TX SUPERVISION SOUND Enter 1 to disable trouble sounding for transmitter check-in failure.
  • Page 133 Enter the relay number (01-16) for the relay that will be used for access control. Enter 00 if not used in this partition. This function has not been UL Listed for use with the VISTA-32FB control. Must be 00 for commercial fire and UL. 1 77 LOG FIRST MAINTENANCE SIGNAL Enter 0 for no logging.
  • Page 134 VISTA-32FB Installation and Set-Up Guide Fields 2 05 – 2 08 must be set to 0 for UL installations. [15] 2 05 AUTO-ARM DELAY (partition-specific) Enter the time between the end of the arming window and the start of auto-arm warning time in values of 01-14 times 4 minutes.
  • Page 135 Section 23 – Data Field Descriptions 2 18 ENABLE GOTO FOR THIS PARTITION (partition-specific) Enter 1 if this partition is to be accessed from another partition's keypad using the GOTO command. Otherwise enter 0. 2 19 USE PARTITION DESCRIPTOR Enter 1 if partition descriptors will be programmed. If enabled, the normal keypad display will include a partition number and four-digit descriptor.
  • Page 136 VISTA-32FB Installation and Set-Up Guide 3 12 ZN TYPE 18 DELAY USE Enter 0 if there is to be no delay for zone type 18. Enter 1 to use delay set in field 3 16 for zone type 18. Note: For UL Listed installations, combined initiating device’s delay and this field’s delay cannot exceed 90 seconds.
  • Page 137 Section 23 – Data Field Descriptions 3 20 TRIGGER OUTPUTS FUNCTION SELECTION Enter 0 for Long Range Radio outputs and Remote Keypad Sounder. Enter 1 for limited LORRA outputs and Keyswitch LEDs. Enter 2 for LORRA Fire output only and 5140LED connection.
  • Page 138 VISTA-32FB Installation and Set-Up Guide 3 61 AUX RELAY FUNCTION SELECTION Select the condition that will trigger the auxiliary relay. Options are: 0 = Trouble/Supervisory; 1 = Alarm, silenced by [Code] + [OFF]; 2 = Smoke detector reset; 3 = Battery save; 4 = Alarm, silenced by [Code] + [#] + [67].
  • Page 139: Section 24 - Scheduling Options

    S E C T I O N Scheduling Options • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section Introduction to Scheduling Time Window Definitions...
  • Page 140 VISTA-32FB Installation and Set-Up Guide • Auto arming can be delayed three ways: by use of the auto arm delay, the auto arm warning, or by manually extending the closing (arming) time window with a keypad command. • The system can also automatically bypass any open zones when auto arming.
  • Page 141: Time Window Definitions

    Section 24 – Scheduling Options • If field 2 10 is set, it is highly recommended to set field 2 11 as well. This field allows the partition to be disarmed outside the arm/disarm time windows only if the partition is in alarm.
  • Page 142: Open/Close Definitions

    VISTA-32FB Installation and Set-Up Guide Scheduling Example To understand scheduling, take, for example, a store that has the following hours: Monday to Thursday: 9am to 6pm Friday 9am to 9pm Saturday 10am to 4pm Sunday Closed Holidays Closed Assume the owner desires the following time windows to allow time for employees to arm or...
  • Page 143 Section 24 – Scheduling Options • The opening and closing windows are programmed in the daily schedule, but the holidays themselves are defined in Holiday Schedule Programming in #80 Menu Mode. Temporary Schedule • The temporary schedule provides a method for the end user to override the daily and holiday schedules.
  • Page 144: Scheduling Menu Mode

    VISTA-32FB Installation and Set-Up Guide Scheduling Menu Mode The #80 Scheduling Menu Mode is used to program most of the scheduling and timed-event options. To enter this mode, the system must first be in the normal operating mode (all partitions disarmed). Enter [Installer Code] + [#] + [80].
  • Page 145: Scheduling Menu Structure

    Section 24 – Scheduling Options Use #80 Scheduling Menu Mode to perform the following functions: • Program the time windows. • Program the open/close schedules. • Program the time-driven events. • Program the access schedules. Scheduling Menu Structure To program schedules, enter Scheduling Program Mode: [Installer Code] + [#] +[80].
  • Page 146: Time Windows

    VISTA-32FB Installation and Set-Up Guide Time Windows The system provides 20 time windows that are defined with start and stop times. These windows are used for various open/close and access schedules, as well as for output controls, and are the basis of the scheduling system. These windows are shared among all 2 partitions.
  • Page 147: Daily Open/Close Schedules

    Section 24 – Scheduling Options Daily Open/Close Schedules Open/Close Schedule Worksheet Write in the previously defined time window numbers for open and close for each partition. Part Tues Thur Open/Close Schedule Programming Each partition can be assigned one daily open/close schedule, plus a holiday open/close schedule.
  • Page 148: Holiday Schedules

    VISTA-32FB Installation and Set-Up Guide Repeat the procedure for the holiday opening and closing time Hol P1 OP WIND.? windows. 00:00 00:00 Press the [ ] key to accept the entry. When the entries are completed, the PARTITION #? prompt is displayed again.
  • Page 149: Time-Driven Events

    Section 24 – Scheduling Options The HOLIDAY NUMBER? prompt will be displayed again. Repeat the procedure for each holiday to be programmed. Enter 0 at the QUIT ? prompt to return to the main menu Quit ? choices and continue programming. 1 = YES 0 = NO 0 Enter 1 to quit Scheduling Menu Mode.
  • Page 150 VISTA-32FB Installation and Set-Up Guide Arm/Disarm Commands Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for automatic arming and disarming functions. During can be used to arm or disarm the control for a specific time only. For example, if During is selected with Arm-STAY, the system will automatically Arm-STAY at the beginning of the window and automatically disarm at the end of the window.
  • Page 151 Section 24 – Scheduling Options 3) Enter the desired activation time, which refers to when the action is to take place relative to the time window. Select from: Activation Description time Beginning of time window End of time window During time window active period only (i.e., on at beginning of window, off at end).
  • Page 152 VISTA-32FB Installation and Set-Up Guide Enter the action code for this timed-event number from the list at 01 ACTION ? the left. This could be an output command, an arming command, none or any other time-driven event. Press [ ] to accept the entry. The prompt for the action specifier will display.
  • Page 153 Section 24 – Scheduling Options Action Codes: Action 50 Action Specifier: 50=Off-normal Reminder No action specifier is required for this action as the conditions for which this will occur are system-wide. Enter the time window number (01-20) for which this timed event 01 Time Window ? is to occur.
  • Page 154: Limitation Of Access Schedules

    VISTA-32FB Installation and Set-Up Guide Limitation of Access Schedules Limitation of Access is a means by which a user's access code is limited to working during a certain period of time. The system provides 8 Access Schedules, each of which consists of two time windows for each day of the week and two time windows for holidays (typically one for an opening time window and the second for a closing time window).
  • Page 155: Temporary Schedules

    Section 24 – Scheduling Options Enter the first time window number for holidays for this access Hol A1 Window 1 ? schedule. As the number is keyed in, the actual time that has 00:00 00:00 00 been stored for the window will be displayed. Press [ ] to continue.
  • Page 156 VISTA-32FB Installation and Set-Up Guide This prompt is for entering the start and end times of the Mon DISARM WIND. disarm (opening) window for Monday. 00:00AM 00:00AM Upon entry of this mode, the cursor will be positioned on the tens of hours digit of the start time of the disarm window.
  • Page 157: User Scheduling Menu Mode

    Section 24 – Scheduling Options User Scheduling Menu Mode The system provides up to 20 timers that will be available to the end user for the purpose of controlling output devices (4204 relay). These timers are comparable to the individual appliance timers that might be purchased at a department store.
  • Page 158 VISTA-32FB Installation and Set-Up Guide entered in the same manner. Pressing any key in the 0-9 range while the cursor is under the AM/PM position toggles the AM/PM indication. Press [Q] to continue. To select the days that are to be activated, enter 1-7 (Monday 06 DAYS? MTWTFSS = 1).
  • Page 159: Section 25 - System Communication

    S E C T I O N System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section A Successful Transmission Reporting Formats...
  • Page 160 75 users, to central stations equipped with the ADEMCO 685 receiver using software level 4.4 or higher. Must be level 4.7 or higher to fully support all new VISTA-32FB report codes. 685 software levels below 4.4 cannot support Contact ID reporting.
  • Page 161 [ ] + [#], or [B] = 999; [3] + [#], or [C] = 996; [1] + [ ], or [A] = 995; Duress = 992 ADEMCO Contact ID Reporting takes the following format: CCCC QEEE GG ZZZ where: CCCC = Customer (subscriber) ID...
  • Page 162: Loading Communication Defaults

    With ADEMCO High-Speed reporting, channels 9-15 cannot report troubles or bypasses. Use these channels for zones that will not report these conditions. • Only user numbers 1-15 can be uniquely reported with Open/Close reports in ADEMCO High-Speed. Loading Communication Defaults To help expedite the installation, the system provides 4 different communication defaults (Low Speed, ADEMCO Express, ADEMCO High-Speed and ADEMCO's Contact ID).
  • Page 163 • For expanded reporting, enable fields 52 and 53. • ADEMCO Selects ADEMCO Express reporting format, with checksum, for both phone numbers. Express • Report codes for zones 001-032, RF receiver, and keypad panics are sent as their ( 94 81) respective zone ID numbers.
  • Page 164 VISTA-32FB Installation and Set-Up Guide TABLE OF CONTACT ID EVENT CODES Code Definition Code Definition Fire Alarm Callback Requested Smoke Alarm (Fire w/Verification) Access Denied Water Flow Alarm Access Granted Duress Door Force Open Silent Panic Egress Denied Audible Panic...
  • Page 165 Bypass Trbl Opn/Cls Low Bat No checksum Primary Secondary Sescoa/Radionics Selection Radionics COMMUNICATION DEFAULTS for ADEMCO's CONTACT ID FORMAT (*94*83) Dual Reporting Primary Format ADEMCO Contact ID Standard/Expanded Reporting for Primary Low Speed Format (Prim.) ADEMCO Contact ID standard Secondary Format...
  • Page 166 VISTA-32FB Installation and Set-Up Guide COMMUNICATION DEFAULTS FOR ZONES ZONE # LOW SPEED EXPRESS HIGH SPEED CONTACT ID 25–8 www.PDF-Zoo.com...
  • Page 167 Section 25 – System Communication COMMUNICATION DEFAULTS FOR ZONES ZONE # LOW SPEED EXPRESS HIGH SPEED CONTACT ID ALARM RST. TROUBLE TRBLE. RST BYPASS BYP. RST. DURESS To program report codes, see Report Code Programming in #93 Menu Mode (refer to the Quick Start Guide). 25–9 www.PDF-Zoo.com...
  • Page 168 VISTA-32FB Installation and Set-Up Guide 25–10 www.PDF-Zoo.com...
  • Page 169: Section 26 - Downloading Primer

    3. COMPASS DOWNLOADING software may be purchased from ADEMCO. This software is available on 3-1/2" diskettes or CD ROM, and includes a complete User's Manual. It may also be downloaded from the ADEMCO web page. The web address is http://www.ademco.com.
  • Page 170: Getting On-Line With A Control Panel

    VISTA-32FB Installation and Set-Up Guide Getting On-Line with a Control Panel At the protected premises, the control panel must be connected to the existing telephone line (refer to Section 26: System Communication section). No programming of the panel is required before downloading to an initial installation.
  • Page 171: Access Security

    Connecting a 4100SM Module for Direct-Wire Downloading The VISTA-32FB can be downloaded without using a modem or telephone line, but by using a 4100SM Serial Module and Compass Downloading Software. The direct-wire downloading connection is to be temporary, and is not part of the permanent installation. Direct-wire downloading is meant as a tool for the installer during the installation process.
  • Page 172: Figure 25-1: Direct Wire Downloading Connections

    VISTA-32FB Installation and Set-Up Guide Remove the alphanumeric pager interface if it is installed while performing the direct-wire download. It may be reconnected once the direct-wire download is completed. 4100SM J2 CONNECTOR + (TO TERM 11) + PWR AUX PWR 1 –...
  • Page 173: Section 27 - Setting The Real-Time Clock

    S E C T I O N Setting the Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section General Information Setting the Time and Date...
  • Page 174 VISTA-32FB Installation and Set-Up Guide 27–2 www.PDF-Zoo.com...
  • Page 175: Section 28 - User Access Codes

    S E C T I O N User Access Codes • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section General Information User Codes and Levels of Authority...
  • Page 176 VISTA-32FB Installation and Set-Up Guide Auth Title Installer Master Manager Operator level A Operator level B Operator level C Duress Level 0: Installer (User 1) Codes • Programmed in field 00 (default = 5-1-4-0). Installer Open/Close reporting is selected in field 39.
  • Page 177 Section 28 – User Access Codes Level Title Functions Permitted Operator A Arm, Disarm, Bypass Operator B Arm, Disarm Operator C Arm, Disarm only if armed with same code • Operator C (sometimes known as the Babysitter Code) cannot disarm the system unless the system was armed with that code.
  • Page 178: To Add A Master, Manager, Or Operator Code

    5 cannot disarm the system unless armed by that user. ADEMCO Contact ID format is capable of reporting Users 01-75 uniquely. If any other report format is used, only user numbers 01 - 15 can uniquely report to the central station. Users 16 - 75 will report as User 15.
  • Page 179 Section 28 – User Access Codes † Master or Manager Code can be used instead of Installer Code. If used instead of an Installer Code, it must have a higher level of authority than the code being changed. For example, a Master Code can add a Manager or Operator-level Code, but cannot add another Master Code;...
  • Page 180: To Change A Master, Manager, Or Operator Code

    VISTA-32FB Installation and Set-Up Guide partition. Press 0 (NO) or 1 (YES), depending on whether this user will Part. 2 – SHOP ? have access to the displayed partition number. If NO, the 0 = NO , 1 = YES keypad displays this prompt for the next partition number in sequence.
  • Page 181: To Delete A Master, Manager, Or Operator Code

    Section 28 – User Access Codes To Delete a Master, Manager, or Operator Code Enter [your code]* +[8] + [User number (02-75)] + [your code again] * An Installer, Master, or Manager Code can be used instead of Installer Code. If used instead of an Installer Code, it must have a higher level of authority than the code being changed.
  • Page 182 VISTA-32FB Installation and Set-Up Guide 28–8 www.PDF-Zoo.com...
  • Page 183: Section 29 - Keypad Functions

    S E C T I O N Keypad Functions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section General Information Arming Functions...
  • Page 184: Arming Functions

    VISTA-32FB Installation and Set-Up Guide Arming Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. Before arming, the system must be in the READY condition (all Display Faulted zones must be intact).
  • Page 185: Global Arming

    Section 29 - Keypad Functions Global Arming If enabled for the user, the keypad will display the following: If NO, the keypad prompts for arming each partition ARM ALL individually. If YES, the system attempts to arm all partitions 0 = NO , 1 = YES allowed by this user.
  • Page 186: Partition "Goto" Commands

    VISTA-32FB Installation and Set-Up Guide Partition "GOTO" Commands Each keypad is assigned a default partition for display purposes, and will show only that partition's information. To see information for another partition, or perform system functions in another partition, use the GOTO command ([User Code] + [ ] + [partition number 1- 2]).
  • Page 187: Panic Keys

    Section 29 - Keypad Functions Panic Keys There are three panic key pairs (shown below) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key pair can be individually programmed for 24-Hour Silent, Audible or Auxiliary (Emergency) responses, as well as Fire. The panic function is activated when the appropriate key pair is pressed at the same time.
  • Page 188: Manual Relay Activation Mode (#70 Mode)

    VISTA-32FB Installation and Set-Up Guide Note that the D key is pressed after each command. Press D twice to complete the entry and exit. When defining Speed Key sequences, do not use the [#] key to represent Quick Arming. The system uses the code entered in response to the prompt to initiate commands in a Speed Key sequence, so the Quick Arm key is unnecessary.
  • Page 189 Section 29 - Keypad Functions Voice: “VOICE DESCRIPTOR” DEVICE “NN” ON/OFF. FOR nn DEVICE IS OFF “VOICE DESCRIPTOR” ON, ENTER 1; FOR “VOICE HIT 0=OFF , 1=ON DESCRIPTOR” OFF ENTER 0 Press 0 or 1 to turn the device off or on respectively. ‘”N”...
  • Page 190 VISTA-32FB Installation and Set-Up Guide 29–8 www.PDF-Zoo.com...
  • Page 191: Section 30 - Testing The System

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Battery Test When AC power is present, the VISTA-32FB will run a brief battery test every 60 seconds to determine if there is a battery connected, and will run an extended battery test every 24 hours to check on the battery’s condition.
  • Page 192: Fire Drill Test ([Code] + [#69])

    VISTA-32FB Installation and Set-Up Guide Fire Drill Test ([code] + [#69]) This test causes fire bells (or any bell having a non-zero response type in the #93 Menu Mode) to be activated (in either steady or pulsing manner, as programmed in field 3 15) for the purpose of conducting a fire drill or a bell test.
  • Page 193: Burglary Walk-Test (Code + Test [5])

    Chapter 30 – Testing The System Enter 1 (YES) to have the results of the test sent to the C.S. TRANSMIT? central station. This report will consist of a list of points 0 = NO 1 = YES that have been tested followed by a list of points that have not been tested.
  • Page 194: Armed Burglary System Test

    VISTA-32FB Installation and Set-Up Guide Armed Burglary System Test • Alarm messages will be sent to the central station during the following tests. Notify the central station that a test will be in progress. • A display of COMM. FAILURE indicates a failure to communicate (no kissoff by the receiver at the central station after the maximum number of transmission attempts is tried).
  • Page 195 Chapter 30 – Testing The System Other System Messages • COMM. FAILURE at the keypad indicates that a failure occurred in the telephone communication portion of your system. • LO BAT and a zone descriptor, accompanied by a once-per-minute beep at the keypad, indicates that a low battery condition exists in the wireless transmitter displayed.
  • Page 196: Turning The System Over To The User

    • Note your ADEMCO customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively. The user may contact Technical Support via Toll-Free Fax. Please include a return fax number.
  • Page 197: Appendix A - Regulatory Agency Statements

    • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UL Installation Requirements As shipped, the VISTA-32FB is suitable for use in listed commercial fire and non-listed commercial burglary installations. When used with the optional VISTA-ULKT attack- resistant enclosure kit and the optional 1451 wired-in transformer, the VISTA-32FB may also be used in listed commercial burglary installations.
  • Page 198: Ul609 Grade A Local Mercantile Premises/Local Mercantile Safe And Vault

    (Also see Mounting the Cabinet in Section 4: Installing the Control) • Wire an ADEMCO AB12 Grade A Bell/Box to the bell output. Bell wires must be run in conduit. Program the bell output for 16 or longer timeout and for confirmation of arming ding.
  • Page 199: California State Fire Marshal (Csfm) Requirements

    Appendix A – Regulatory Agency Statements • Program the control's dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports. For Grade AA Service: • Follow the instructions for Grade A service, except use the 7920SE in place of the 7720. California State Fire Marshal (CSFM) Requirements 24-hour backup: The California State Fire Marshal has published new regulations that require all residential fire alarm control panels installed after June 30, 1993 to be...
  • Page 200 VISTA-32FB Installation and Set-Up Guide FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information: This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception.
  • Page 201 Appendix A – Regulatory Agency Statements CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) STATEMENT NOTICE The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
  • Page 202 VISTA-32FB Installation and Set-Up Guide A–6 www.PDF-Zoo.com...
  • Page 203: Appendix B - Summary Of System Commands

    A P P E N D I X Summary of System Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Event Log Display = [Code] + [#] + [60] (Installer or Master Only) Event Logging Commands...
  • Page 204 VISTA-32FB Installation and Set-Up Guide Display User Self Help Hold Any Key for 5 Seconds. Programming Site-Initiated Download = [User Code] + [#] + [1]. Commands Direct-Wire Download Enable = [User Code] + [#] + [5]. Enter Program Mode = [Installer Code] + [8 0 0].
  • Page 205: Appendix C - Specifications

    UL864-NFPA 72 Local, Central Station, and Remote Station. 5140DLM BACKUP DIALER MODULE Physical: 2.75”H X 4”W X 1”D Mounts on VISTA-32FB main PC board shield using standoffs supplied. Connects to VISTA-32FB main PC board J3 header using ribbon cable supplied. FCC Registration: AC398U-62668-MO-N 5140LED ANNUNCIATOR MODULE Physical: 4.5”H X 2.75”W X 1.5”D...
  • Page 206 VISTA-32FB Installation and Set-Up Guide 6139(R) REMOTE KEYPADS Physical: Width: 6.25 inches Height: 4.75 inches Depth: 1.25 inches Electrical: Voltage Input: 12VDC Current Drain: 100mA Interface Wiring: RED: 12VDC input (+) auxiliary power BLUE: Not Used GREEN: Data to control panel...
  • Page 207: Index

    4297 Polling Loop Extender ........7–3 Ademco High Speed Reporting........25–3 4-Wire Smoke Detectors ..........6–3 Ademco Low Speed ..........20–1, 25–1 ADEMCO LOW SPEED ..........C–1 Ademco No. N6277 Cam Lock ........4–1 Ademco's Contact ID..........25–2 Affects Lobby..............2–2 5140DLM..............16–1 AFFECTS LOBBY ...........23–11 5140DLM BACKUP DIALER MODULE....
  • Page 208 VISTA-32FB Installation and Set-Up Guide Arm/Disarm Commands ......... 24–12 Arm-AWAY Type 21 ..........21–3 Arming Away ............29–2 California State Fire Marshal........A–3 Arming Functions ..........29–2, B–1 Call Waiting Defeat .............3–3 Arming Instant ............29–2 CALL WAITING DEFEAT........23–13 Arming Maximum............. 29–2 Callback..............26–2...
  • Page 209 Index Dialer Test..............30–1 EXIT DELAY RESET ..........23–11 DIGITAL COMMUNICATOR ........C–1 EXIT DELAY SOUNDING........23–13 DIP switches ............... 7–2 Exit Error .............1–6, 3–1 Direct Wire Downloading ......... 12–8 EXIT ERROR LOGIC ..........23–11 Direct-Wire Downloading ......... 26–3 Extend Closing Window ..........24–2 DISABLE DOWNLOAD CALLBACK....
  • Page 210 VISTA-32FB Installation and Set-Up Guide Installing the Cabinet Lock........4–1 MAIN DIALER (TOUCH-TONE OR ROTARY DIAL) Installing the Control ..........4–1 ................23–4 Installing the Control's Circuit Board ....... 4–3 Maintenance Signal Support........1–2 INTELLIGENT TEST REPORTING ....... 23–3 Manager Code ............28–2 Interior W/Delay Type 10 .........
  • Page 211 Index PAGER PHONE NUMBER FOR TEST....23–9 RESET ON SECOND OFF FOR BELL 2 ....23–19 PAGER PHONE NUMBER FOR TROUBLES..23–8 RESTORE REPORT TIMING.........23–10 PANIC BUTTON OR SPEEDKEY......23–12 Restrict Disarming ............24–2 Panic Keys..............29–5 RF RCVR SUPERVISION CHECK-IN INTERVAL23– Partitions..............
  • Page 212 VISTA-32FB Installation and Set-Up Guide Temporary Schedules Programming...... 24–17 TEST REPORT INTERVAL ........23–3 Testing The System ..........30–1 View Capabilities............28–1 Theory of Partitioning ..........2–1 Viewing Capabilities Of A User ........29–4 Time and Date............27–1 Viewing Data Fields ..........20–2 Time Driven Events..........
  • Page 213 WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.
  • Page 214 24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
  • Page 215: Vista-32Fb Summary Of Connections

    NOTE 2: TO OTHER DEVICES Ratings: 10 - 14VDC, 1.7A max. 2k EOLR is Ademco model 610-7 - Zones 1, 2, 8: 100 ohms max - 2mA max for smoke det. (up to 16 detectors See note 1, see instructions...
  • Page 216 165 Eileen Way, Syosset, New York 11791 Copyright © 1999 PITTWAY CORPORATION ¬.¦l K3521 3/99 www.PDF-Zoo.com...

Table of Contents

Save PDF