WOOD GASIFYING BOILER ATTACK DP STANDARD / PROFI INSTRUCTIONS FOR USE W W W . A T T A C K . S K...
Page 3
ATTACK DP - Wood gasifying boiler - Assembly, pre-heating and training of the attendance is perfomed by an assembly technician trained by the manufacturer, who also fills in a document on the installation of the boiler. -During wood gasifying, tar and condensates (acids) are created in the fuel bin. Therefore behind the boiler the mixing appliance regumat must be installed to keep the minimum temperature of return water of 65°C into the boiler.
3 Content 4 Introduction, general description 5 Technical parameters 6 Dimensions of the boilers 7,8 Control board of ATTACK DP STANDARD, PROFI 9 Purpose of use, technical parameters, operational rules 10 Warning 11 Technical description of DP PROFI 12 Overheating of the boiler, the ways of regulation, displaying faults...
Page 5
ATTACK DP wood gasifying boiler is designed for economic and ecological heating of family houses, bungalows, small plants, workshops and similar objects. Specified fuel for ATTACK DP boilers is dry wood, e.g. logs of lengths, depending on the type of boiler. The wood gasifying boiler is the holder of 101 5 certificate.
(PROFI version) Specified min.temperature of returnable water in operation is 65°C. Specified temperature of water during operation in the boiler is 80-90°C. ATTACK, s.r.o. producer reserves the right to change technical parameters and dimensions of boilers without previous warning.
Control board – ATTACK DP STANDARD Wood gasifying boiler "ATTACK DP Standard" is controlled by a boiler and flue gas thermostat. ATTACK DP 25-45 1 - Reset 2 - Fuse 3 - The main switch 4 - Flue gas thermostat...
Page 9
ATTACK PROFI The ATTACK PROFI boiler version in comparison to the ATTACK STANDARD version represents higher comfort of attendance, possibility of output regulation and possibility to connect control and regulation elements. Boiler temperature is kept at the level set at by user by means of control of the flue gas ventilator´s rotations.
Page 10
Technical description and ways of regulation of the ATTACK PROFI boiler Boiler temperature is kept at the level set at by user by means of control of the flue gas ventilator´s rotations. Regulator measures temperature of water in boiler, indicates it on display and controls suction fan and circuiting pump.
Page 11
Actual value of this setting can be also checked in the temperature display mode. If the flue gas temperature is in the operation mode after burning-up lower than the value set by the button of additional thermostat, then the suction fan and the circuiting pump are blocked, which is signalized by flickering of additional thermostat´s control light.
Page 12
Required boiler temperature [C 80] - is temperature that the regulator tries to reach in the operation mode. It is set by direct turning of button of the boiler thermostat and it is indicated by short displaying. Set temperature of the flue gas / room thermostat [100C] - this parameter indicates temperature set by additional flue gas / room thermostat.
Page 13
Schedule: List of service parameters Production Parameter Display Step settings Max. Operation output of ventilator or max. output, when ∏100 ∏r 0-10 n 40 Minimum output of ventilator ∏h 10 Ventilator speed, decrease of coefficient ∏r 1 Automatic control of fan rotations and time of fan start - -, 0 ∏n 5 Time of ventilator operation...
Page 14
Operation parameters of flue gas fan Fan output [Π100] - this value defines fan output. When the "Πr" is on "0-10", it is max. fan output that can be reached during automatic fan operation. Minimum fan output [n 40] - the lowest fan output, that can be used, when are the fan rotations controlled automatically and when the fan rotations continually increase during boiler start-up.
Page 15
Time of pause of the C.H. pump [Pc --] - when the boiler temperature exceeds the temperature set by parameter [P 65] and operation mode stops the pump (e.g. when the contacts of thermo- stat are open or when the fan is stopped), can the pump be regularly started for 30 seconds to pump water into the heating system.
Additional output. Mode of additional output [Ar 0] - regulator is equipped with the multi-purpose output that can work under one of the following outputs: Mode [Ar 0] – can control oil or gas boiler, if it is connected into the heating system. When the regulator is started by the main switch, the additional boiler is stopped and it is started again, when there is already no fuel in the solid fuel boiler.
Page 17
control light of the room thermostat will shine, because the boiler should keep the temperature set by the boiler thermostat. When the room temperature exceeds the set temperature, control light of the room thermostat expires and the boiler switches into the mode of fire keeping at minimum boiler temperature.
Page 18
Connection of module UM-1 Regulator Regulator Gas boiler, electric boiler Alarm, other devices...
Page 19
Purpose of use Ecological hot-water boiler Attack DP is designed for heating of family houses and similar objects. The boiler is designed for burning wood only. Any dry wood can be used for burning, mainly logs. Also wood of bigger diameter, blocks, can be used, which reduces nominal output but prolongs burning time.
Warning! After the first heating up, there can be condensation and condensate may leak. This is not a defect Condensation disappears after longer heating. When burning smaller wooden waste it is necessary to check the temperature of flue gas which must not overcome 320°C. Otherwise the fan can be damaged. Creation of tar and condensate in the feed hopper is a phenomenon accompanying wood gasifying.
Technical description of ATTACK DP PROFI: During the operation, the display is showing the current temperature of outlet heating water. Speed of the fan are controlled in this way: - if during burning up proces the boiler temperature is lower than 45 °C, the fan works with the output set up by the turning of burning up button situated in rear side of regulator in the range of 40 - 100 %.
Page 22
If the temperature falls under 60 °C, the regulator comes into the burning up mode. The options of boiler regulation ATTACK DP PROFI The boiler enables regulation of room temperature as well as connecting the sensor of room temperature.
Page 23
Permanent-heat operation Permanent-heat operation of the boiler means that the fire can be kept during the night without heating up daily, but only in winter. This way of operation shortens the service life of the boiler. For permanent-heat operation prepare the boiler this way: - Put a few bigger logs (4-6)on the glowing layer - Get the mixing valve ready.
Note Logs of bigger dimensions is necessary to cut into halves or quarters (because of the requirement of operation to nominal output). You can burn hard as well as soft wood. Wood must be dried! Boiler output depends on the moisture content of wood. Output and function of the boiler is guaranteed for maximum moisture content of 20%.
(according to STN EN 60 335-1 + A11:1997). Installation of the boiler to the heating system The ATTACK DP boiler only by a company certified for the installation and assembly of heating equipment. Before the installation there must be a project responding to valid regulations. Before installing the boiler to the old heating system, the installing company must sluice out the whole system to clean it.
Protection of boiler against corrosion Suitable solution to this problem is mixing appliance Regumat ATTACK-OVENTROP, which enables separated boiler and heating circuit. This way you can prevent undercooling of boiler under 65°C and also decrease condensation of steam, acids and tars in the feed hopper.
Installation and exchange of the heatproof shaped piece ( version 1) The back part of the ash pan pos. 1 insert into the lower chamber and push to stop to the back plate. Insert the front part of the ash pan pos. 2 and push to stop to the back part of the ash pan. Put the super-structure of the ash pan pos.
The variants of connections The variant of connection with the regulating system REGUMAT ATTACK-OVENTROP Heating system The pump Regumat ATTACK- Expansion vessel -OVENTROP ATTACK Return flap Return Flap boiler...
Page 29
The advantage of this solution consists in its compactness, simplicity of attendance and in guarranteed protection of the boiler thermal exchanger. Regumat for the boiler Ordering code ATTACK DP25, DP35 (DN25) DPP25003 ATTACK DP45, DP75, DP95 (DN32) DPP25006...
By the operation with several heating ups at full performance, accumulation tanks will be heated for the temperature of 90-100°C. Heating with accumulation tanks in connection with the ATTACK DP boilers bring more advantages. Among the main advantages belong enlargement of the boiler life and in the end result also lower consumption of fuel.
The advantages The boiler installation together with the accumulation tank offers several advantages: - lower fuel consumption (up to 30%). The boiler works in full output to fuel burn-up when the optimal operation is observed - High chimney and boiler durability and minimum formation of acids and condensate - Possibility of combination with another heating sources ( solar panels...) - conjunction of boiler and floorheating - confortable and ecological heating...
Scheme of dependency of resistance on the temperature of heating water by the thermal probe ( DP PROFI ) Resistance Temprerature kOhm °C 1009 1000 1030 1059 1105 1135 1165 1218 1247 1277 1338 1367 1396 1467 1495 1523 1603 1630 1656 1748...
Page 34
The schemes of electrical connection of ATTACK DP STANDARD, PROFI boilers ATTACK DP STANDARd 25 - 75 TC 95°C KEY FOR DP BOILERS HV - Main switch ST - Flue gas thermostat KT - Boiler thermostat BT - Safety thermostat...
Page 38
RECORD ON PUTTING THE BOILER TO OPERATION Data on the customer (llegible) Production number......Name and surname: Date of putting to operation............Service organization: Street: ............Post code, town:. .Stamp, signature ....................Tel. No......Obligatory service examination after the 1st year of operation Date : ........
Page 40
E-mail: export@attack.sk Slovakia Web: www.attack.sk Výrobca ATTACK s.r.o. si vyhradzuje právo technických zmien výrobkov bez pred- chádzajúceho upozornenia. • ATTACK, s.r.o. producer reserves the right to change technical parameters and dimensions of boilers without previous warning. • Der Hersteller ATTACK, s.r.o. behält sich das Recht der technischen Veräderungen an Produkten ohne eine vorige Warnung.
Need help?