Layout Of Electrical Terminals - Sanyo SHAKC64AGB Instruction Manual

Control system for spw air conditioner system's
Table of Contents

Advertisement

System Controller

Layout of Electrical Terminals

Ground for
power wiring
3
DC voltage pulse
Photocoupler input
Allowable contact voltage
and current : 24 V, 10 mA
Pulse width : 300 ms or more
No-voltage a-contact
static output
Allowable contact voltage
and current : 30 V, 0.5 A
Clamp for electrical wiring
CN02
U1
N
U2
L
C3
B3 B2 B1 A3 A2 A1
C4
How to connect electrical wiring
1)
Basic wiring
N:
Power supply
L:
U1:
Inter-unit control wiring. (Low voltage)
U2:
C3:
Auxiliary
C4:
Ground for inter-unit control wiring
2)
Terminals for remote monitoring
A1:
Input for turning on air conditioners concurrently.
A2:
Input for turning off air conditioners concurrently.
A3:
Common input for turning air conditioners on or off.
B1:
On operation state indicator output.
B2:
Alarm indicator output.
B3:
Common indicator output.
DC24V
COM
Digital
Input
.
Connector (CN02) for
weekly timer or schedule
timer (optional)
P.C. board
Fig. 3-58
(
50 Hz/60 Hz, 220 – 240 V)
SYSTEM CONTROLLER
A1
A2
TX
A3
B1
B2
B3
CX

Hide quick links: