JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® Thank you for choosing the Joslyn series surge Protective Device (sPD) . ® Guide to Installation and Assistance We look forward to fulfilling your facilitywide surge protection needs . Should you have questions about installing the JSP please call Joslyn Technical Support at 800.238.5000 or 804.236.3300...
JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® confirm that the voltage(s) and service configuration shown on the JsP ✓ Pre-Installation Checklist product label are consistent with the voltage and service configuration of the facility . A model number is on the right side of the JsP unit . each model...
JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® Figures 1–5 show the electrical relationship between JsP and these five Service Configurations basic service configurations: 1-Phase, 2-Wire; split-Phase, 3-Wire; 3-Phase, 4-Wire Wye; 3-Phase, 3-Wire Delta and 3-Phase, 4-Wire High-leg Delta Figure 1...
(d) have sharp bends. For optimum performance never exceed 10' conductor lengths. Joslyn recommends installing the JsP unit by following conductor size for phase, ground and neutral connections . The conductor length should be as short as possible to ensure the maximum level of protection .
Indoor vs. Outdoor Installations steel) enclosures are suitable for corrosive environments as well . For direct sunlight applications, Joslyn suggests shading the monitoring components . All conduits and fittings must be rated and properly installed so that the final installation maintains the NeMA rating .
JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® units that come with Form “c” dry relay contacts provide status of the surge Connecting Form “C” protective device . These contacts are for connection to a user-provided remote Dry Contacts alarm and monitoring circuit . The relay contacts are rated 65VDc/150VAc with maximum switching power of 30WDc/60VA Ac .
JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® W A R N I N G ! It is recommended that the cover of the JSP unit along verification and Power Up with its associated cabling be installed prior to applying power. The monitoring harness, which exits the epoxy and connects to J2 on the monitor board, contains line voltage when power is applied to the unit.
. We will immediately ship a replacement for the defective parts free of charge (installation labor and site preparation excluded) . return the defective parts to Joslyn within 30 days of receiving the replacement . Failure to return the defective parts will result in billing for the replacement parts .
JoslyN iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl ® Thomas & Betts Power solutions warrants that your Joslyn surge protective device Warranty Statement “Product”), shall meet applicable industry standards and specifications (the and be free from defects in materials and/or workmanship . should any failure of the Product to conform to this warranty appear within the standard warranty period, Thomas &...