JSPR Joslyn S U R G E S U R G E P R O T E C T I O N P R O T E C T I O N Installation, Operation and Maintenance Manual PN 750-0100-001 Surge Protective Devices...
. When shortcuts are taken or installation procedures are not followed, the JSP Series may become damaged or may not provide adequate protection . It is extremely important to follow these installation procedures carefully .
Pre-Installation Checklist product label are consistent with the voltage and service configuration of the facility . A model number is on the right side of the JSP Series unit . Each model number corresponds to the configurations printed in Table 1:...
JOSLYN , JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Figures 1–5 show the electrical relationship between JSP Series unit Service Configurations and these five basic service configurations: 1-Phase, 2-Wire; 2-Phase, 3-Wire; 3-Phase Wye, 4-Wire; 3-Phase Delta, 3-Wire and 3-Phase High-Leg Delta, 4-Wire .
10' conductor lengths. The factors listed above should be addressed during the design of an installation to reserve a suitable place for the JSP Series unit next to its point of connection to the electrical system . The selected mounting location should allow for the shortest possible conductor runs and a direct route with a minimum of bends .
• Terminals are identified with markers (Phase A, B, C, Line 1, Line 2, Neutral or Ground) The JSP Series unit is a Type 1 SPD which is suitable for use in both Type 1 Upstream Overcurrent and Type 2 SPD applications . The JSP Series unit is a one-port SPD and is Protection Device to be connected in parallel with the electrical system .
Indoor vs. Outdoor Installations steel) enclosures are suitable for corrosive environments as well . For direct sunlight applications, Joslyn suggests shading the monitoring components . All conduits and fittings must be rated and properly installed so that the final installation maintains the NEMA rating .
Page 9
JOSLYN , JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® CAUTION: Careful consideration must be made when selecting Conduit Openings an area for conduit entry. There are several components inside the (continued) enclosure that may interfere with the conduit entry path, therefore, ensure the path is clear of all objects before drilling.
. On all high-leg delta systems, the high-leg (208V LN) must be connected to the Phase B of the SPD . (Color coded orange according to NEC) . *The 3-Wire + Ground Delta JSP Series units do not have a neutral conductor. tnbpowersolutions.com/joslynsurge...
JOSLYN , JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Units that come with Form “C” dry relay contacts provide status of the surge Connecting Form “C” protective device . These contacts are for connection to a user-provided remote Dry Contacts alarm and monitoring circuit .
, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® W A R N I N G ! It is recommended that the cover of the JSP Series Verification and Power Up unit along with its associated cabling be installed prior to applying power.
Monday through Friday, 8:00 a.m. to 5:00 p.m. (EST) at 800.238.5000 or 804.236.3300 joslyn@tnbpowersolutions.com JSP Series units are warranted for a period of 10 years from date of purchase . In the event that any module or subassembly within the SPD fails to perform as specified during the warranty period, call our Technical Support at 800 .238 .5000 .
Thomas & Betts Power Solutions, LLC, A Member of the ABB Group (“Seller”) Warranty Statement warrants that your Joslyn surge protective device (the “Product”), shall meet applicable industry standards and specifications and be free from defects in materials and/or workmanship . Should any failure of the Product to conform to this warranty appear within the standard warranty period, Seller shall either repair or replace the defective Product, or part thereof, upon return to Seller’s...