CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
External dimensions
Upper pipe draw-out port (Knockout hole)
Power supply wire take-in port (Knockout hole)
128
Remote controller wire take-in port
(Knockout hole)
84
Refrigerant pipe
Left drain size
(Liquid side ØC)
B (Hanging position)
Refrigerant pipe (Gas side ØD)
Hanging bolt
Ceiling surface
Unit
A
11-EN
Installation Manual
210
Pipe draw-out port (Knockout hole)
216
167
Drain port VP20
110
76
105
(Inner dia. Ø26, hose attached)
Drain pipe
75
97
connecting port
146
Remote controller wire take-in port
Power supply wire take-in port (Knockout hole)
347
Remote controller wire take-in port
262
(Knockout hole)
135
Outside air take-in port (Knockout hole Ø92)
Pipe hole on wall (Ø100 hole)
Drain left pipe draw-out port
(Knockout hole)
A
B
Wireless sensor
SM56 type
910
855
mounting section
SM80 type
1180
1125
SM110, SM140 type 1595
1540
Ceiling Type
Installation of hanging bolt
• Consider the piping / wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer
to the external view and installation pattern.
Procure hanging bolts washer and nuts for installing
the indoor unit (these are not supplied).
Hanging bolt
M10 or W3/8
(Unit: mm)
Nut
M10 or W3/8
How to use attached installation pattern
Using the pattern, positioning of the hanging bolt and
pipe hole can be performed.
* As an error to some degree may generate on the
pattern size due to temperature and humidity, be
sure to confirm the size.
Installation
pattern
84
C
D
Ø6.4 Ø12.7
Ø9.5 Ø15.9
– 6 –
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
Indoor
unit
Ceiling
surface
Hanging bracket
4 pieces
New concrete slab
12 pieces
Install the bolts with insert brackets or anchor bolts.
(Slide type
(Blade type
(Pipe hanging
bracket)
bracket)
anchor bolt)
Steel flame structure
Use existing angles or install new support angles.
Hanging bolt
Ceiling surface
Wall face
Hanging bolt
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Installation Manual
Rubber
Anchor bolt
Support angle
EN