Test Run

Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistance
of 1 MΩ or more exists between the terminal
block 1 to 3 and the earth (grounding).
If resistance of less than 1 MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
Execute a test run
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
Wired remote controller
1,5
1
Push
button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
33-EN
Installation Manual
2
Push
button.
3
Select the operation mode with
button, [
Cool] or [
Heat].
• Do not run the air conditioner in a mode other
than [
Cool] or [
Heat].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
4
After the test run, push
stop a test run.
(Display part is same as procedure 1.)
5
Push
button to cancel (release from) the
test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
2, 4
3
Ceiling Type
– 17 –
Wireless remote controller
Always select
[
HIGH] air volume.
1
1
1
Push
(ON / OFF) button on the remote
controller, select [
with
(MODE) button, and then select
[
HIGH] with
2
Cooling test run:
Set the temperature to 18 °C with
buttons.
Heating test run:
Set the temperature to 30 °C with
button to
buttons.
3
Cooling test run:
After confirming a signal receiving sound "beep"
immediately set the temperature to 19 °C with
(temp. setup) buttons.
Heating test run:
After confirming a signal receiving sound "beep"
immediately set the temperature to 29 °C with
(temp. setup) buttons.
4
Cooling test run:
After confirming a signal receiving sound "beep"
immediately set the temperature to 18 °C with the
temp. setup buttons.
Heating test run:
After confirming a signal receiving sound "beep"
immediately set the temperature to 30 °C with the
temp. setup buttons.
5
Repeat procedures
Indicators "Operation", "Timer", and "Ready" in the
wireless receiver section flash in approx. 10
seconds, and the air conditioner starts operation.
If any of these indicators does not flash, repeat
1
from procedure
6
Upon completion of the test run, push
(ON / OFF) button to stop operation.
Overview of test run operations using the wireless
remote controller
Cooling test run:
2, 3,
ON / OFF → 18 °C → 19 °C → 18 °C → 19 °C →
4, 5
18 °C → 19 °C → 18 °C → (test run) → ON / OFF
Heating test run:
1,6
ON / OFF → 30 °C → 29 °C → 30 °C → 29 °C →
30 °C → 29 °C → 30 °C → (test run) → ON / OFF
COOL] or [
HEAT]
(FAN) button.
(temp. setup)
(temp. setup)
3
4
5
6
.
.
Installation Manual
34-EN