Combi Compact ECO RF 24 (G.C. 47-291-05) ECO RF 30 (G.C. 47-291-06) ECO RF 36 (G.C. 47-291-07) Installation, service and user instructions Please read these installation instructions carefully before installing and using the appliance. Keep these installation instructions with the appliance.
• R&TTE Directive (1999/5/EG) • Intergas declares that the materials used in the manufacturing of this appliance are non- hazardous and that no substances harmful to health are contained within the appliance. 1.2 Warnings Intergas accepts no responsibility for the unsatisfactory performance of the appliance or flue arising from the failure to comply with the installation and user instructions.
1.6 Abbreviations and descriptions used Description Referred to as High efficiency Intergas Combi Compact ECO RF wall mounted gas Appliance fired boiler Appliance plus pipe work for central heating CH installation Appliance plus pipe work for domestic hot water DHW installation 1.7 This manual...
The manufacturer Intergas Heating Ltd accepts no liability whatsoever for damage or injury caused by failure to adhere (strictly) to the safety regulations and instructions, or carelessness during installation of the Intergas Combi Compact ECO RF High Efficiency wall mounted gas fired boiler and any associated accessories.
(*) The maximum CH power is factory set at 70% of the highest value (See section §10.4, Setting maximum CH power). We have a policy for continual improvement and development, therefore we reserve the right to change specifications without prior notice. Intergas Heating Ltd...
Hot water sensor S3 Condensate trap Flow sensor Heat exchanger CH pressure sensor Operating panel and read-out Mains lead 230 V AC without plug (stripped) Ionisation / Ignition electrode Manual air bleed Position of data plate Sight glass Intergas Heating Ltd...
3 GENERAL BOILER INFORMATION 3.1 General The Intergas Combi Compact ECO RF wall mounted, gas fired boiler is a closed appliance. The appliance is designed to transfer heat to the water circuit in a CH system and the DHW installation.
4 OPERATION 4.1 General The Intergas Combi Compact ECO RF wall mounted, gas fired boiler is a modulating high efficiency boiler. This means that the power is adjusted in line with the desired heat requirement. The aluminium heat exchanger comprises of two separate copper circuits.
Page 11
During DHW operation the fan speed, and hence the power of the appliance, are controlled by the boiler controller so that the DHW water temperature reaches the DHW temperature setting. The water temperature can be set between 40°C and 65°C (See § 10.1.6). Intergas Heating Ltd...
The boiler controller is equipped with an interface for a PC, which can be connected by means of a special cable and associated Intergas Diagnostic Software (IDS). This facility allows the behaviour of the boiler controller, the appliance and the heating installation to be monitored over a longer period.
If you experience any problems please refer to the installation and commissioning • guidelines within the boiler instruction manual. If necessary, please contact Intergas Heating Ltd (See § 1.8). Remember it is a requirement to complete the Benchmark code of practice logbook before leaving the installation.
Proceed as follows: If cover plate (A), is used, remove to the front. • Unscrew the two screws (1) behind the appliance display window. • Pull the bottom of the front panel (2) forwards. • Intergas Heating Ltd...
Combi Compact ECO RF 36 Combi Compact ECO RF 30 Combi Compact ECO RF 24 7.3.2 Using the fixing strip + ROBO kit ( 8 or 12 litre) Position the fixing strip to the wall and drill the holes.
32mm diameter in order to prevent the condensate from freezing. 7.4.1 Fitting the cover plate (optional) Hang the flanged upper edge of the cover plate on the washers under the base of the appliance and slide the cover plate as far as possible towards the rear. Intergas Heating Ltd...
CH request for heat. Connection diagram for floor heating Boiler Pump Floor heating valve Non return valve (spring operated) Electrical valve 230 V AC Radiators G. Room thermostat Maximum thermostat Intergas Heating Ltd...
C = Combi Compact ECO RF 36 X. Bar Y. Litres per minute (*) The Combi Compact ECO RF 24 is equiped with a flow restrictor of 8 litres. When a DHW flow above 8 liters is required this flow restrictor has te be removed. 8.2.3...
Open Therm (OT) with 11 – 12 timer function Temperature control Connector X2 Notes Programmable Room 1 – 3 thermostat 230 V or Programmable external control 230 V Frost thermostat 230 V 1 – 3 03010015 Intergas Heating Ltd...
Page 23
For the heating line setting, see weather-dependent regulation (See § 10.6 ). The sensor should be fitted where possible on a north facing wall. 8.3.5 230 volt room thermostat with timer function To be connected to contacts 1 and 3 of connector X2. See electrical diagram. Intergas Heating Ltd...
Page 24
All controls/ zones should be connected in an external wiring centre and a switched live connected to 1 on X2. Set in-built timer to C-ON. Warning High Voltage Isolate the appliance from the electrical supply before connecting the thermostat. Intergas Heating Ltd...
- the use of fittings, elbows etc should be kept to a minimum ans any internal ‘’burrs’’ on cut pipework should be removed so that the internal pipe section is as smoooth as possible. For more information about preventive measures against freezing please visit the HHIC website http://www.centralheating.co.uk/checklists/frozen-condensate-pipes. Intergas Heating Ltd...
6 Accessories. Note Only use approved Intergas flue products with this boiler, which can be sourced from the supplier of your boiler or Intergas stockist. The standard horizontal flue pipe is not supplied with the boiler and should be purchased separately from your supplier.
Page 27
The vertical flue system contains a flue adapter concentric 60/100 to replace the standard adapter on the boiler. Please note that the terminal is suitable for a flat or pitched roof and only approved Intergas flue products can be used with this boiler.
Page 28
1. Check condensate trap is filled with water and correctly connected to boiler. 2. All flue joints are correctly made, unstressed and adequately supported. 3. All parts of the flue can be visually inspected -ensure suitable access where flue is positioned within voids- Intergas Heating Ltd...
Do not adjust the air/gas ratio. Correct gas supply to obtain sufficient working pressure. Note. The inlet working pressure must be obtained with all other gas appliances at the property working. Intergas Heating Ltd...
Page 30
The flue termination should also be checked. Where suitable access for a visual inspection of an existing flue system has not been provided the appliance must not be commissioned and it must be disconnected from the gas supply. Intergas Heating Ltd...
This will occur at the the time of the last request for heat. To change this time the room thermostat should be turned up briefly at the desired time. The pump does not run during DHW operation. • Intergas Heating Ltd...
Check the nature of the fault on the basis of the fault codes in § 11.1 and resolve the cause of the fault if possible before resetting the appliance. Intergas Heating Ltd...
(end user setting) Min. outside temperature of the Adjustment range -9°C to 10°C heat curve Max. outside temperature of Adjustment range 15°C to 30°C the heat curve CH pump post purge period Adjustment range 0 to 15 minutes Intergas Heating Ltd...
Page 34
Anti cycle time Adjustment range 0 to 15 minutes (Delay time reacting on CH demand after exceeding maximum setting CH temp.) Ref. value DHW 24 = ECO RF 24 30 = ECO RF 30 36 = ECO RF 36 Intergas Heating Ltd...
It is not possible to adjust the CO percentage on test program H. When the CO percentage is not in accordance with the value as listed in the table please contact Intergas Technical Services 01527 888 000. No adjustment to the CO percentage should be made without permission from Intergas Technical Services.
Page 38
12. Reposition the front cover. CAUTION Check that the Flue sampling point X is gas tight after sampling. CAUTION Work on gas carrying parts may only be carried out by a qualified competent person. Intergas Heating Ltd...
Check that the measurement nipples used are gas-tight. CAUTION Check that the Flue gas sampling point and the Gas test point are gas-tight. No adjustment should be made to the gas valve without prior permission of Intergas Technical Services. Intergas Heating Ltd...
When the CO percentage at high setting is not within the prescribed tolerance band please contact Intergas Heating. 13. Place a sticker for the gas type set over the existing sticker next to the gas valve.
29,30 Gas valve relay faulty Replace boiler controller • CAUTION Always use original Intergas spare parts when replacing components. Failure to fit the sensors S1 and/or S2, or to fit them correctly can result in serious damage. CAUTION * The boiler is equipped with a non-return valve (A), positioned above the fan.
Page 42
Replace the weather-dependant adjustment. Check the wiring against the diagram. No current (24 V). Check the connector X4. Replace the faulty manager. Check the power supply. Check connector X2. Pump not running. Replace faulty pump. Intergas Heating Ltd...
Page 43
Set the hot water circuit, depending on the desired temperature. No heat transfer as a result of lime scale or Descale or flush the exchanger DHW side. fouling in the heat exchanger DHW side. Cold water temperature <10°C. Intergas Heating Ltd...
11.2 Cleaning Clean the heat exchanger from top to bottom with a plastic brush or compressed air. Clean the underside of the heat exchanger. Clean the condensate drain pan with water. Clean the condensate trap with water. Intergas Heating Ltd...
N.B. The picture is showing a front plate with 11 shoulder bolts (Kombi Kompakt ECO EF 30 or ECO RF 36). The front plate for the ECO RF 24 has 9 shoulder bolts. Fit the gas connection below the gas valve.
Conditions to the contrary are expressly rejected. The warranty is effective only if the annex to this warranty With due regard for the conditions indicated below, Intergas Heating certificate has been signed by the purchaser and returned to Ltd warrants to the authorised installer the soundness of the us within 8 days of the date of installation.
Page 52
Intergas boilers are manufactured in a Kiwa ISO 9001 certified production faccility. Intergas Heating Ltd 884587-01 Intergas Heating Limited Telephone : 01527 888000 Building 94 : 01384 279480 Bay 1 Vantage Point info@intergasheating.co.uk www.intergasheating.co.uk The Pensnett Estate Kingswinford DY6 7FS...