Vision.net Touchscreens
Network Connections
Once the wiring is terminated to the Touchscreen Control PCB, proceed to connecting the touchscreen itself.
There are two connection options:
1) Connect the network cable from the RJ-45 port on the touchscreen to "Ethernet out" RJ-45 port on
Touchscreen Control PCB as shown in Figure 7. Connect Ethernet using Belden 1583A cable from the
SNV/IP network on the "Ethernet In" 8-pin connector.
OR
2) Connect a standard CAT5e cable from the SVN/IP network directly to the RJ-45 port on the touchscreen.
Note: The RJ-45 connections on the Control PCB are for convenience wiring only. It is only a pass through and does
not convert SVN/IP to SVN/485 or SVN/485 to SVN/IP. If the ethernet jack is used, a static IP address in the same
range must be configured for the jack to be active.
Network Option 2
Ethernet Network
(from SVN/IP network)
Touchscreen
COM Cable
Note: Connect Touchscreen Control PCB to Touchscreen COM Cable if not already connected as shown in Figure 7.
Network Option 1
Ethernet Network
(see connection chart)
OR
Table 2: Ethernet Wiring Connections*
Pin
1
2
3
4
Not Used
5
Not Used
6
7
Not Used
8
Not Used
* Required cable - Belden 1538A
Figure 7: Touchscreen Network Connection
Note:
Exploded view shown for clarity.
Signal
Color
RX +
White / Orange
RX -
Orange
TX +
White / Green
Not Used
Not Used
TX -
Green
Not Used
Not Used
Installation & User's Manual
Touchscreen
Control PCB
Touchscreen
Wiring and Connections