Samsung MIM-D00 Installation Manual page 27

Dms data management server
Hide thumbs Also See for MIM-D00:
Table of Contents

Advertisement

Installation Errors
Check points when tracking fails and the installation information
of the indoor and outdoor units are not available.
1
Check the centralized controller and transmitter models.
2
Check the communication status between the centralized
controller and the transmitter.
Devices
Centralized
The indoor units are controlled
Controller
according to the on/off buttons
Transmitter
The 7-Segment display of the transmitter is as follow:
 Left : The main address of the indoor units are displayed
if the communication is normal.
 Right : The RMC address of the indoor units are
displayed followed by the following alphabets.
d - Displayed when waiting for communication
with the centralized controller
U - Displayed when the communication is normal
None - Communication with the centralized
controller broken  check the connection
status
3
Check the polarity of the communication cables between
the DMS and the centralized controllers.
(The 'RS485 Rx' LED on the DMS display is off if the
communication fails)
 Communication will fail if the C1, C2 polarity is changed.
 Check for broken wires.
If the communication is normal
'U' is displayed on the right side
of the 7-segment display
If the communication fails
The power LED and the room
LEDs flicker periodically
Nothing is displayed on the right
side of the 7-segment display
Only 'd' is displayed on the right
side of the 7-Segment display