Installation Errors
Check points when tracking fails and the installation information
of the indoor and outdoor units are not available.
1
Check the centralized controller and transmitter models.
2
Check the communication status between the centralized
controller and the transmitter.
Devices
Centralized
The indoor units are controlled
Controller
according to the on/off buttons
Transmitter
The 7-Segment display of the transmitter is as follow:
Left : The main address of the indoor units are displayed
if the communication is normal.
Right : The RMC address of the indoor units are
displayed followed by the following alphabets.
d - Displayed when waiting for communication
with the centralized controller
U - Displayed when the communication is normal
None - Communication with the centralized
controller broken check the connection
status
3
Check the polarity of the communication cables between
the DMS and the centralized controllers.
(The 'RS485 Rx' LED on the DMS display is off if the
communication fails)
Communication will fail if the C1, C2 polarity is changed.
Check for broken wires.
If the communication is normal
'U' is displayed on the right side
of the 7-segment display
If the communication fails
The power LED and the room
LEDs flicker periodically
Nothing is displayed on the right
side of the 7-segment display
Only 'd' is displayed on the right
side of the 7-Segment display
27
E-