Page 1
PN: 52750:A ECN 05-680 Fire Alarm Control Panel MS-9200UDLS MS-9200UDLSE IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. Document #52750 11/04/05 Revision:...
Page 2
While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control panel with remote notifi- termined rate or reaches a predetermined level.
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to of power before servicing.
Page 9
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ). MS-9200UDLS PN 52750:A 11/04/05...
Page 10
CAUTION! HIGH VOLTAGE TRANSFORMER 2 TRANSFORMER 1 MS-9200UDLS PN 52750:A 11/04/05...
Compatible with Fire-Lite’s newer series devices (refer to SLC Wiring Manual for a list of compatible addressable devices) • Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices) •...
Page 14
Battery (Lead Acid Only) - J9 Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UDLS cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box.
Style Z XRM-24(E) transformer. (Class A) circuits, each 3.0 amps max. with only circuit can handle 2.5 standard transformer installed. amps maximum. Refer to the battery calculations section for additional information. Figure 1.1 Current Availability MS-9200UDLS PN 52750:A 11/04/05...
• Escape key • Mode key • Four cursor keys (up, down, left and right) • Enter key Local Piezo Sounder A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions. MS-9200UDLS PN 52750:A 11/04/05...
Cabinet See Page The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
1.6.3 300 Series Intelligent Addressable Devices Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices.
The PK-CD Programming Utility can be used to program an MS-9200UDLS directly from most IBM compatible computers, including laptops and portables, equipped with a serial port. MS-9200UDLS program files can also be created and stored on the PC and then downloaded to the control panel. The PK-CD Kit includes the MS- 9200UDLS Windows-based Programming Utility software on CD-ROM with on-line help file.
1.8.4.2 CHG-120F Battery Charger The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
LEDs. In Canada, this module must be used to annunciate the fire alarm input points/zones only. * In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output. MS-9200UDLS PN 52750:A 11/04/05...
Enter Autoprogramming (refer to "Autoprogram" on page 47) • Resolve Programming Conflicts • Go to Point Program to Enter Specific Data (refer to "Point Program" on page 48). Use the right and left arrow keys to navigate between devices. MS-9200UDLS PN 52750:A 11/04/05...
Fire•Lite Alarms, Inc. One Fire-Lite Place Northford, CT 06472 (203) 484-7161 Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL00B9200UD Ringer Equivalence: 0.0B Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX.
FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre- mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant. MS-9200UDLS PN 52750:A 11/04/05...
Radio Interference Regulations of the Canadian Department of Communications.” Representative: NOTIFIER/FIRE•LITE, CANADA 24 Viceroy Road Concord, Ontario L4K2L9 Phone: (905) 660-7210 FAX: (905) 660-7204 IC Certificate Number: Ringer Equivalence Number (REN): 1.3B Load Number: 2 MS-9200UDLS PN 52750:A 11/04/05...
Mark and drill the left and right upper and lower mounting holes Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting Install remaining fasteners and tighten Main Circuit Board on chassis mounting studs mounting slots grounding stud Backbox Figure 2.1 MS-9200UDLS Chassis Removal MS-9200UDLS PN 52750:A 11/04/05...
7. Connect the Optional XRM-24 Transformer plug to Transformer 2 Connector J11 on the FACP main circuit board. 8. Complete the installation as detailed in the following sections. Optional XRM-24 Transformer Standard XRM-24 Transformer Mounting Studs Mounting Slot Figure 2.2 MS-9200UDLS Main Board/Chassis Installation MS-9200UDLS PN 52750:A 11/04/05...
Page 29
Mounting Transformer Installation Semi-Flush Mounting Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box. Figure 2.3 MS-9200UDLS Cabinet Mounting MS-9200UDLS PN 52750:A 11/04/05...
2.3.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, LCD DISPLAY 60 Hz, 3.0 amps for the MS-9200UDLS or 240 VAC, 50 Hz, 1.5 amps for the MS-9200UDLSE. TB11 Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes.
Series field charger/power supplies. The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9200UDLS main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs"...
Key-slot slot as illustrated to the right. It is keyed to prevent incorrect insertion. Top edge of MS-9200UDLS Main Circuit Board NACKEY card slot Figure 2.7 NAC Configuration Using NACKEY 2.5.2 Style Y (Class B) NAC Wiring...
FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB2 of the MS-9200UDLS to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics, the signal on NAC1.
All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-9200UDLS is shown below. Figure 2.11 Typical UL Power-limited Wiring Requirements Power-limited Circuits...
Note:Shorting bars SEC. ACTIVE PRI. ACTIVE inside RJ31X Jack removed during male plug insertion 7 foot Cable MCBL-7 (ordered separately) PRI. PHONE LINE SEC. PHONE LINE Modular Female Connectors Male Plug Connectors Figure 2.13 Wiring Phone Jacks MS-9200UDLS PN 52750:A 11/04/05...
1 2 3 CUT TO MONITOR 4XTMF KISSOFF SEC. ACTIVE PRI. ACTIVE LCD DISPLAY KEYPAD TB11 MINI DIN PRI. PHONE LINE SEC. PHONE LINE HOT NEUT EARTH BATTERY KEYBOARD CONN. Mounting Screw Access Holes Figure 2.14 Keypad/Display Removal MS-9200UDLS PN 52750:A 11/04/05...
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
Page 39
4XTMF module 3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-9200UDLS main circuit board, being careful not to bend any pins 4. Secure 4XTMF module to standoffs with supplied screws. 5. Reapply power to the FACP 6.
Installation of either device requires panel programming to allow the FACP to communicate with the device. CAUTION! Do not connect a printer or PC to the MS-9200UDLS FACP if a ground fault (zero impedance to ground) exists on the control panel. Circuit damage may result.
The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to "Annunciators/UDACT" on page 96 for information on annunciator programming. Make certain to program the annunciator addresses that have been physically installed on the system.
1 to 99 within a 24 hour period 3.1 Programming Data Entry Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board.
User Programming Programming 3.2 User Programming The MS-9200UDLS is completely field programmable and requires no special software skills. While programming the MS-9200UDLS, the fire protection capabilities of the ! ! ! control panel are enabled. Site-specific programming may be accomplished in three ways: •...
ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved. MS-9200UDLS PN 52750:A 11/04/05...
Page 45
If the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. MS-9200UDLS PN 52750:A 11/04/05...
Autoprogram Result Screen #1 In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules installed. Pressing the ESC key will return the display to Programming Screen #1. MS-9200UDLS PN 52750:A 11/04/05...
When the last digit is keyed-in, the following screen will be displayed: DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION) Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector. MS-9200UDLS PN 52750:A 11/04/05...
017. When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device with the highest address that is installed will be displayed. MS-9200UDLS PN 52750:A 11/04/05...
Page 50
V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector and 017 = Detector Address 017) MS-9200UDLS PN 52750:A 11/04/05...
Page 51
The control panel will display the device type and address which has been disabled and Edit Detector Screen #2 will turn on the Trouble LED and Disable LED. MS-9200UDLS PN 52750:A 11/04/05...
Page 52
Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause 3=PRE-SIGNAL the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on Edit Detector Screen #3 page 139. MS-9200UDLS PN 52750:A 11/04/05...
Page 53
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose) Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre- signal delay timer to some value MS-9200UDLS PN 52750:A 11/04/05...
Page 54
Pressing 1 while viewing Edit 1=NOUN/ADJECTIVE Detector Screen #5 will cause the following screen to be displayed: 2=DESCRIPTION ***************** Edit Detector Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:A 11/04/05...
Page 57
0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow) • The above increment function may be repeated with each press of the zero key MS-9200UDLS PN 52750:A 11/04/05...
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005. When the last digit is keyed-in, the following screen will be displayed: ADD MODULE 1=CONTROL 2=MONITOR Add Module Screen #2 MS-9200UDLS PN 52750:A 11/04/05...
3.6.2.2.3 Edit Module Screen for Monitor Module The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS Edit Module Screen MS-9200UDLS PN 52750:A 11/04/05...
Page 60
1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 012 = Module Address 012) W or * - indicates whether or not the device is programmed for Walktest (W = programmed for walktest, * = not programmed for walktest). MS-9200UDLS PN 52750:A 11/04/05...
Page 62
The display will return to the Edit Monitor Screen #2 which will show the new type selection. Table 3.1 on page 63 lists the Monitor Types and their respective functions. MS-9200UDLS PN 52750:A 11/04/05...
Page 63
HVAC OVRRIDE Switch Drill-Switch-AR Acts like panel Drill Key, nonlatching (tracking) Note: 1. For the PROCESS-MONITOR-AR selection, AR refers to AutoResettable 2. For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module Operation" on page 179 MS-9200UDLS PN 52750:A 11/04/05...
Page 64
Pressing 1 while viewing ***************** Edit Monitor Screen #5 will cause the following screen to be displayed: Edit Monitor Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:A 11/04/05...
Page 66
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit. MS-9200UDLS PN 52750:A 11/04/05...
Page 67
0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow) • The above increment function may be repeated with each press of the zero key MS-9200UDLS PN 52750:A 11/04/05...
ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from 000 - 099) 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module and 002 = Module Address 02) MS-9200UDLS PN 52750:A 11/04/05...
Page 69
Yes and Enabled No. If Enabled No is selected, the module will not be polled by the Edit Control Screen #2 control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled. MS-9200UDLS PN 52750:A 11/04/05...
Page 70
Ignore Open Circuit Strobe Circuit None Control None Resettable Power Relay Type - Ignore Open Circuit HVAC SHUTDN Relay Type - Ignore Open Circuit Note: For HVAC SHUTDN description, refer to "Control Module Operation" on page 179 MS-9200UDLS PN 52750:A 11/04/05...
Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displayed: Edit Control Screen #4 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:A 11/04/05...
Page 73
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit. MS-9200UDLS PN 52750:A 11/04/05...
Page 74
4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones MS-9200UDLS PN 52750:A 11/04/05...
Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 90 for a description of this feature. MS-9200UDLS PN 52750:A 11/04/05...
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central Station. MS-9200UDLS PN 52750:A 11/04/05...
CLIP mode while the newer devices are compatible with CLIP and LiteSpeed modes of operation. Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols. Device Addressing It is important to note that the MS-9200UDLS addressable device capacity is 99 MS-9200UDLS PN 52750:A 11/04/05...
99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS. Note that It is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are installed.
A maximum of 20 characters (including spaces) can be entered into each screen for a total of two lines with 40 characters. After entering up to 20 characters in the first screen, press Enter MS-9200UDLS PN 52750:A 11/04/05...
At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May. MS-9200UDLS PN 52750:A 11/04/05...
005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9200UDLS PN 52750:A 11/04/05...
25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9200UDLS PN 52750:A 11/04/05...
Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed, regardless of how the NACKEY card is installed. Their programming, however, will have no effect if the NACKEY card is installed for Class A operation. MS-9200UDLS PN 52750:A 11/04/05...
Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No. Note: The programming for NAC 1 will determine the operation of the remote power supply sync. MS-9200UDLS PN 52750:A 11/04/05...
Silence key is pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will turn off both audible and visual devices. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear: CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA Coding Screen #1 CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN Coding Screen #2 MS-9200UDLS PN 52750:A 11/04/05...
Page 90
Zone 99 or if the timer counts down to zero 8. Control modules that are programmed to the same zone as the activated input device will not be delayed for activation MS-9200UDLS PN 52750:A 11/04/05...
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded: System Sensor: 40 Strobes Wheelock: 25 Strobes Gentex: 23 Strobes MS-9200UDLS PN 52750:A 11/04/05...
If the corresponding condition is cleared, the relay will return to its normal state without the necessity of resetting the control panel. MS-9200UDLS PN 52750:A 11/04/05...
When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as follows: ERASING HISTORY PLEASE WAIT Erase History Wait Screen After the History file has been erased, the display will return to the History Screen. MS-9200UDLS PN 52750:A 11/04/05...
Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. MS-9200UDLS PN 52750:A 11/04/05...
Enabled Yes and Enabled No. Notes: 1. *The LCD-80F is a Terminal Mode annunciator. To enable the MS-9200UDLS for LCD-80F operation, program Term Enabled to Yes. 2. The Terminal Mode annunciator (LCD-80F) and the Printer/PC use the same TB8 terminal block on the MS-9200UDLS main circuit board.
3.6.9.2.1 Onboard DACT Enable To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key. MS-9200UDLS PN 52750:A 11/04/05...
2=ROTARY 67/33 3=ROTARY 62/38 Secondary Phone Type Screen Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38. MS-9200UDLS PN 52750:A 11/04/05...
Master Programming Level Programming 3.6.9.2.4 Service Terminal The MS-9200UDLS can be programmed remotely from a PC using a modem and ON BOARD DACT telephone line. Information can also be retrieved from the FACP using the same 1=SERVICE TERMINAL 2=CENTRAL STATION method.
C = look for secondary dial tone for up to two seconds (then dial anyway) • D = three second pause • E = five second pause • F = end of phone number (F is automatically entered for unused entry positions) MS-9200UDLS PN 52750:A 11/04/05...
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle the display between Reporting Disabled and Reporting Enabled. MS-9200UDLS PN 52750:A 11/04/05...
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value. Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the Central Station an unlimited number of times. MS-9200UDLS PN 52750:A 11/04/05...
Page 103
CENTRAL STATION # 1=TEST TIME INT 2=ACCOUNT CODE 0000 3=24HR TST TIME 0021 Primary/Secondary Screen #1 CENTRAL STATION 1=PHONE NUMBER Primary/Secondary Screen #2 CENTRAL STATION 1=COMM FORMAT ADEMCO-CONTACT-ID Primary/Secondary Screen #3 CENTRAL STATION 1=EVENT CODES Primary/Secondary Screen #4 MS-9200UDLS PN 52750:A 11/04/05...
Page 104
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys. MS-9200UDLS PN 52750:A 11/04/05...
Page 105
9. Enter 9 followed by D for a three second pause or E for a five second pause then the phone number followed by an F to indicate the end of the number. MS-9200UDLS PN 52750:A 11/04/05...
Page 106
3=4P1S C19 A14 Comm Format Screen #3 COMM FORMAT 1=4P1E C19 A14 2=4P2S C18 A23 3=4P2E C18 A23 Comm Format Screen #4 COMM FORMAT 1=4P2S C19 A14 2=4P2E C19 A14 3=ADEMCO CONTACT ID Comm Format Screen #5 MS-9200UDLS PN 52750:A 11/04/05...
Event Code to be changed from the default value. PULL STATION ALARM Event Code Screen The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats. MS-9200UDLS PN 52750:A 11/04/05...
Page 108
TORNADO ALRT MON-USER-DEF-9 not used not used TAMPER MON-USER-DEF-11 MON SUPERVISORY MON-USER-DEF-12 MON SUPERV AUTO MON-USER-DEF-13 POWER MON MON-USER-DEF-14 TROUBLE MON POINT_FAULT code will always be transmitted MON-USER-DEF-15 POINT_FAULT code will always be transmitted PROCESS MON MS-9200UDLS PN 52750:A 11/04/05...
Page 110
TORNADO ALRT MON-USER-DEF-9 not used not used TAMPER MON-USER-DEF-11 MON SUPERVISORY MON-USER-DEF-12 MON SUPERV AUTO MON-USER-DEF-13 POWER MON MON-USER-DEF-14 TROUBLE MON POINT_FAULT code will always be transmitted MON-USER-DEF-15 POINT_FAULT code will always be transmitted PROCESS MON MS-9200UDLS PN 52750:A 11/04/05...
Page 112
TORNADO ALRT MON-USER-DEF-9 not used not used TAMPER MON-USER-DEF-11 MON SUPERVISORY MON-USER-DEF-12 MON SUPERV AUTO MON-USER-DEF-13 POWER MON MON-USER-DEF-14 TROUBLE MON POINT_FAULT code will always be transmitted MON-USER-DEF-15 POINT_FAULT code will always be transmitted PROCESS MON MS-9200UDLS PN 52750:A 11/04/05...
Pressing the Enter key will cause the number just entered to be dialed. Pressing 3 for Go On Hook will cause the DACT to hang-up, deselecting the previously selected phone line. The phone line’s red Active LED will turn off. MS-9200UDLS PN 52750:A 11/04/05...
Setting any option in the Printer/PC screen to Yes will disable communications with the LCD-80F. The printer must be installed in the same room and within 50 feet of the FACP. MS-9200UDLS PN 52750:A 11/04/05...
NEW MASTER PASSWORD IS 10101 PRESS ENTER IF OK Password Change Screen Pressing the Enter key will program the new password into the control panel and return the display to the Password Change Screen. MS-9200UDLS PN 52750:A 11/04/05...
WARNING! SYSTEM CHANGE PROCEED? 1=YES 2=NO Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared. MS-9200UDLS PN 52750:A 11/04/05...
Note: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC 2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in the test. MS-9200UDLS PN 52750:A 11/04/05...
Page 119
001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments. MS-9200UDLS PN 52750:A 11/04/05...
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen. PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP MS-9200UDLS PN 52750:A 11/04/05...
EDIT DETECTOR 1D001 1=ENABLED Enable/Disable Select Screen Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled MS-9200UDLS PN 52750:A 11/04/05...
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will cause the display to return to the History Screen without erasing the History file. MS-9200UDLS PN 52750:A 11/04/05...
(control module in this example) with an address of 001 on loop 1 but have not been programmed to any input devices. Use the up and down arrow keys to view all the zones without input assignments. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest. 3.7.5 System To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2. The following display will appear: SYSTEMS 1=TIME/DATE System Screen MS-9200UDLS PN 52750:A 11/04/05...
The cursor will move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date Screen which will show the new date. MS-9200UDLS PN 52750:A 11/04/05...
(00 - 99). After the second digit is entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to return to the previous screen. MS-9200UDLS PN 52750:A 11/04/05...
Page 127
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 90 for a description of this feature. MS-9200UDLS PN 52750:A 11/04/05...
It also performs a lamp test by turning on all LEDs (except the Ground LED), piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that exists after a reset will resound the system. MS-9200UDLS PN 52750:A 11/04/05...
This is a red LED that indicates the secondary phone line is active Kiss-off This is a green LED that blinks when a Central Station has acknowledged receipt of each transmitted message or when a portion of upload or download data has been accepted from a Service Terminal MS-9200UDLS PN 52750:A 11/04/05...
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 012102 The MS-9200UDLS performs the following functions at regular intervals while in Normal mode: Monitors AC input voltage and battery voltage Monitors and reports status of SLC loop, option cards and control panel Polls all devices on the SLC loop and flashes each device LED while checking for valid replies, alarms, troubles, etc.
Page 131
Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 Device Address; 1D001 in this example 1 represents SLC Loop, D represents a detector and 001 represents device address 001 MS-9200UDLS PN 52750:A 11/04/05...
Refer to "Edit Detector" on page 49, "Edit Module Screen for Monitor Module" on page 59 and "Edit Module Screen for Control Modules" on page 68 for information on additional device types. MS-9200UDLS PN 52750:A 11/04/05...
Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 132, for a description of the information displayed on the control panel LCD. MS-9200UDLS PN 52750:A 11/04/05...
4.10 NAC Operation There are four Style Y (Class B) or two Style Z (Class A) programmable NACs (Notification Appliance Circuits) resident on the MS-9200UDLS main circuit board. All NACs may be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded operation.
4.15 Time Functions: Real-Time Clock The MS-9200UDLS includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset.
Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. MS-9200UDLS PN 52750:A 11/04/05...
This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. MS-9200UDLS PN 52750:A 11/04/05...
If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdiction. MS-9200UDLS PN 52750:A 11/04/05...
Walktest, then shut them off after eight seconds. While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. MS-9200UDLS PN 52750:A 11/04/05...
V - Alarm Verification Enabled (V = Yes, * = No) • S - Silenceable for control modules (S = Yes, * = No) • W - Walktestable for control and monitor modules (W = Yes, * = No) MS-9200UDLS PN 52750:A 11/04/05...
PAS, 98 reserved for Pre-signal and 99 reserved for Two Stage • Zone Type - the Type assigned to each installed zone (default is Alarm) • Zone Message - the Message assigned to each installed zone MS-9200UDLS PN 52750:A 11/04/05...
Page 143
21.25 to 27.50 VDC 24V Nonresettable Normal 21.25 to 27.50 VDC Charger Normal 21.87 to 29.84 VDC Normal -1.3 to -1.6 VDC NAC 1 or NAC 2 Open Circuit -2.3 to -2.5 VDC Short Circuit 0 to 1.0 VDC MS-9200UDLS PN 52750:A 11/04/05...
PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY These screens will indicate the delay time, in seconds, for each of the first three possible delay options. The AC Loss Delay time is displayed in hours. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 1 while viewing Read Status Screen #3 will display the following screen: 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 RELAY 1=RELAY 1 2=RELAY 2 3=RELAY 3 The operator can view the programmed option for each relay by pressing the corresponding number key. MS-9200UDLS PN 52750:A 11/04/05...
1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories, by pressing the corresponding number key. MS-9200UDLS PN 52750:A 11/04/05...
Pressing 2 while viewing Read Status Screen #4 will display the following screen: PHONE LINE PRIMARY TOUCHTONE SECONDARY TOUCHTONE This screen indicates the both the Primary and Secondary phone lines have been configured for touchtone dialing operation. MS-9200UDLS PN 52750:A 11/04/05...
Central Station Screen #2 provides information on the Primary and Secondary Central Station programming which includes: • Test Time Interval • Account Code • 24 Hour Test Time • Phone Number • Communication Format • Event Codes MS-9200UDLS PN 52750:A 11/04/05...
The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. MS-9200UDLS PN 52750:A 11/04/05...
If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. MS-9200UDLS PN 52750:A 11/04/05...
Page 151
Dust accumulation above the allowed limit. DIRTY2 Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: DIRTY Maintenance Urgent Maintenance Alert Acceptable Range Low Chamber Reading VALUE Figure 4.1 Diagram of Maintenance Levels MS-9200UDLS PN 52750:A 11/04/05...
Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED START MONTH START WEEK WEEK-1 DAYLIGHT SAVINGS END MONTH END WEEK LAST-W MS-9200UDLS PN 52750:A 11/04/05...
Central Station phone number. The MS-9200UDLS meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is: 1.
Page 154
Upload or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2 Refer to Table 5.2 for an explanation of each letter code in Table 5.1 . Refer to Table 5.3 for a list of compatible receivers. MS-9200UDLS PN 52750:A 11/04/05...
Page 155
Upload/download (1st digit) Upload/download (2nd digit) Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number and the second digit corresponding to any system trouble condition. Only the first digit is programmable. MS-9200UDLS PN 52750:A 11/04/05...
Also, a green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted reports to the Central Station. The Kissoff LED may turn on several times during communications with a Central Station. The table below shows UL listed receivers which are compatible with the MS- MS-9200UDLS PN 52750:A 11/04/05...
Page 157
Changes in the hardware and/or software by the receiver manufacturers may affect the receiver compatibility with the FACP DACT. After completing the installation, communication between the DACT and Central Station Receiver must be tested and verified. MS-9200UDLS PN 52750:A 11/04/05...
Download with callback disabled - the Service Terminal calls the control panel. No hang-up sequence occurs. Data transfers proceed. Note that Callback enable/disable is controlled by the master user at the Service Terminal on a per call basis. MS-9200UDLS PN 52750:A 11/04/05...
Callback to Service Terminal Any time the control panel is requested to allow an upload or download, it will confirm the source of the incoming call, hang-up and call back the calling party (Service Terminal phone number). MS-9200UDLS PN 52750:A 11/04/05...
Page 160
These blocks of data are protected from partial programming due to faulty phone connections, line noise and other errors. This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors. MS-9200UDLS PN 52750:A 11/04/05...
7. Return call to Service Terminal 8. After security clearance, begin downloading 9. Upon completion of download, call Central Station(s) back and report either a successful download or failed upload/download message (if programmed to do MS-9200UDLS PN 52750:A 11/04/05...
During the uploading process, the fire protection remains active. Should a system trouble or alarm condition occur, the control panel immediately terminates uploading and processes the trouble or alarm locally and transmits the information to the Central Station(s). MS-9200UDLS PN 52750:A 11/04/05...
Table 7.1 AC Branch Circuit Requirements Number of Current Draw Total Current Device Type Devices (AC amps) per Device MS-9200UDLS 3.00 MS-9200UDLSE 1.50 CHG-75 2.05 CHG-120F 2.00 Sum Column for AC Branch Current Required MS-9200UDLS PN 52750:A 11/04/05...
Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied. Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm condition during a loss of AC power. MS-9200UDLS PN 52750:A 11/04/05...
Page 165
Current limitations of TB3 & TB4 circuits is 2.5 amps per NAC output and 0.5 amps per special application auxiliary power output 10.Total current draw listed above cannot exceed 6.0 amps. MS-9200UDLS PN 52750:A 11/04/05...
18 AH. Batteries larger than 18 AH require a UL listed external battery charger and cabinet such as the BB-26, F or other UL listed external battery cabinet. MS-9200UDLS PN 52750:A 11/04/05...
Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below). Be careful to properly plan the installation prior to installing any devices. MS-9200UDLS PN 52750:A 11/04/05...
Page 168
MMF-302 CMF-300 CP350 ZONE CMF-300 CP300 SD350 CMF-300 SD350 ZONE SD350 CMF-300 MMF-302 The zone correlations which are shown graphically above are also presented in Table A.1 on page 169 and Table A.2 on page 170. MS-9200UDLS PN 52750:A 11/04/05...
Page 169
Table A.1 Detector Programming Sheet Example DETECTOR ZONE ASSIGNMENT Address Device Zone ADJ/NOUN Address Device Zone ADJ/NOUN Type Number Type Number SD350 FIRST HALL SD350 ELEV. LOBBY CP350 2ND FLOOR CP350 ROOM 210 SD350 3RD FLOOR SD350 MEZZANINE SD350 MECH. ROOM MS-9200UDLS PN 52750:A 11/04/05...
Page 170
MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MMF-300 MMF-302 1, 2 MMF-302 1, 2 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 1, 2, 3 CMF-300 CMF-300 CMF-300 CMF-300 MS-9200UDLS PN 52750:A 11/04/05...
Page 171
Correlations Software Zones Table A.3 Blank Detector Programming Sheet - 1 of 2 DETECTOR ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9200UDLS PN 52750:A 11/04/05...
Page 172
Software Zones Correlations Table A.4 Blank Module Programming Sheet - 1 of 2 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone ADJ/ Address Device Zone ADJ/NOUN Type Number NOUN Type Number MS-9200UDLS PN 52750:A 11/04/05...
Box Connected to F Transmitter Module,” on page 175. NFPA 72 Proprietary Fire Alarm System MS-9200UDLS Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3, “Proprietary Protective Signaling System,” on page 177, for installation instructions for this unit.
Page 175
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module and circuit. 3. Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.
Page 176
NFPA Standard-Specific Requirements Correlations NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the 4XTMF module. 2. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed information.
Page 177
Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9200UDLS and the transmitter are supervised by the transmitter. 2. This MS-9200UDLS/Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System.
Connecting external system accessories to the MS-9200UDLS main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, wire gauge and wire run length for each MS-9200UDLS circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200UDLS circuit.
HVAC SHUTDN control module only if the fire alarm condition has been cleared and the FACP reset to a normal condition. Pressing the switch during an alarm condition will have no effect. MS-9200UDLS PN 52750:A 11/04/05...
OVRRIDE module. Releasing the switch will allow the HVAC SHUTDN control modules to activate, turning off the fans. Note: Activation of the HVAC OVRRIDE module causes a trouble event that will be communicated to the Central Station if enabled. MS-9200UDLS PN 52750:A 11/04/05...
Page 181
14 AFM-16AF Annunciator 22 AFM-16ATF Annunciator 22 CHG-75 AFM-32AF Annunciator 22 see also battery charger 21 Alarm 132 see also remote battery charger 14 Alarm Silence 16, 128 Clasic Loop Interface Protocol 79 MS-9200UDLS PN 52750:A 11/04/05...
Page 182
Fire Alarm Control Panel 12 Features 12 monitor module 67 Detector Fire Alarm Control Panel add 48 see also FACP 12 adding description 54 Format Selection Address 154 delete 49 Form-C relay 17, 32, 41 MS-9200UDLS PN 52750:A 11/04/05...
Page 183
NFPA 72 Proprietary Protective Signaling Systems 177 Maintenance Alert 13, 135 levels 151 NFPA 72 Remote Station Protective Signaling System maintenance alert 151 Maintenance Program Level 2 44, 120 NFPA Battery Requirements 166 Manual Dial Mode 114 NFPA Standard 174 MS-9200UDLS PN 52750:A 11/04/05...
Page 184
Programming Sheet 169, 170, 171 ground fault 40 Programming Utility see also PK-CD 20 Phone Number 105 Piezo PRT/PK-CABLE see also sounder 16 for PC/Printer connection 40 PK-CD Programming Utility 20 Point Program 48 Read Status 43, 140 MS-9200UDLS PN 52750:A 11/04/05...
Page 185
Service Terminal 99, 100 System Signal rate 13 Maintenance Level 124 Signaling Line Circuit System Point 141 see also SLC 14 system power 12 Silence Inhibit 13, 91, 138 System Setup 80 Silenceable control module 71 Telephone Circuitry 24 MS-9200UDLS PN 52750:A 11/04/05...
Limited Warranty The manufacturer warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service.
Need help?
Do you have a question about the MS-9200UDLS and is the answer not in the manual?
Questions and answers