Page 1
Addressable Fire Alarm Control Panel IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. PN: 52750:E1 MS-9200UDLS MS-9200UDLSE Document 01/27/09 ECN 09-062 #52750 Revision: PN: 52750:E1...
Fire Alarm System Limitations An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Installation Precautions WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and asso- ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
ANN-LED Connection to FACP ...37 ANN-RLY Annunciator Module ...38 ANN-RLY Board Layout ...38 Specifications ...38 Mounting/Installation ...38 ANN-RLY Connection to FACP ...39 ANN-BUS Audio Panel Control ...39 Legacy ACS Series LED Zone Type Annunciators ...41 Getting Started ...41 MS-9200UDLS P/N: 52750:E1 01/27/09...
Page 6
Disable ...93 Zone 97, 98 and 99 ...93 Zones Installed ...94 Zones Enabled ...94 Zones Disabled ...94 Zone Type ...95 Zones Available ...96 Zone Message ...96 Loop Setup ...96 Style ...96 Loop Protocol ...97 System Setup ...97 MS-9200UDLS P/N: 52750:E1 01/27/09...
Page 7
Printer/PC ...142 Password Change ...143 Clear Program ...144 Program Check ...145 Maintenance Programming Level ...147 Disable Point ...148 History ...149 Program Check ...150 Walktest ...151 System ...153 Zone Setup ...154 Operating Instructions ...156 Panel Control Buttons ...156 MS-9200UDLS P/N: 52750:E1 01/27/09...
Page 8
Print ...178 Time-Date ...180 Central Station Communications ...181 Transmittal Priorities ...182 Remote Site Upload/Download ...184 Remote Download ...184 Transferring a Program ...185 Security Features ...186 Power Supply Calculations ...187 Overview ...187 Calculating the AC Branch Circuit ...187 MS-9200UDLS P/N: 52750:E1 01/27/09...
Page 9
HVAC SHUTDN ...208 Monitor Module Operation ...208 HVAC RESTART ...208 HVAC OVRRIDE ...209 Ademco Contact ID Format Event Code Descriptions ...210 Transmission Format Between DACT and Receiver ...210 Ademco Contact ID Typical Printout ...210 Central Station Points ...215 MS-9200UDLS P/N: 52750:E1 01/27/09...
Contact Technical Support with any questions about software and the appropriate version for a specific application. MS-9200UDLS PN 52750:E1 01/27/09...
Page 11
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ). MS-9200UDLS PN 52750:E1 01/27/09 Document #15384...
Page 12
CAUTION! HIGH VOLTAGE TRANSFORMER 2 TRANSFORMER 1 MS-9200UDLS PN 52750:E1 01/27/09...
The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer. Refer to the battery calculations section for additional information. Figure 1.1 Current Availability MS-9200UDLS PN 52750:E1 01/27/09 Note: If NACs are 6.0 amps with optional second configured as two Style Z XRM-24B(E) transformer.
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 012102 AC POWER MAINTENANCE ALARM FIRE ALARM SILENCED SUPERVISORY DISABLED TROUBLE BATTERY GROUND ACK/STEP EVENT ALARM SILENCE ENTER DRILL HOLD 2 SEC MODE RESET RECALL Figure 1.2 Membrane/Display Panel MS-9200UDLS PN 52750:E1 01/27/09...
The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly. • Communicate in the following formats: MS-9200UDLS PN 52750:E1 01/27/09 24 VDC Resettable (smoke detector power) output - 0.300 amps maximum 24 VDC Nonresettable or Resettable power output - 0.300 amps maximum...
Cabinet See Page The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
1.6.3 300 Series Intelligent Addressable Devices Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.8.2 DP-9692 Dress Panel An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox.
1.8.5.2 CHG-120F Battery Charger The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If current draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices from Auxiliary Power Supply" on page 27. Model Number 0.040 amps 0.040 amps 0.200 amps 0.068 amps 0.075 amps MS-9200UDLS PN 52750:E1 Worst Case Current Draw 01/27/09...
Page 25
Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below) Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations: MS-9200UDLS PN 52750:E1 01/27/09 22 Gauge 18 Gauge 16 Gauge 1,852 ft.
6 and above must be set to OFF. Address not valid Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized. MS-9200UDLS PN 52750:E1 01/27/09 Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults) ANN-BUS and power wiring are...
Swing the cover closed, snapping it shut 4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key Normal/Standby (no activity): 37.0 mA Trouble: 39.0 mA Alarm: 40.0 mA AC Fail ( not backlit): 15.0 mA MS-9200UDLS PN 52750:E1 01/27/09...
7. After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any excess wire pushed back through hole into electrical box MS-9200UDLS PN 52750:E1 01/27/09 Press in latch and pull...
Page 30
Product Description The following table shows the ANN-80 connections to the MS-9200UDLS Programming Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must added to the system via FACP programming. Refer to the programming section titled "ANN-BUS Options" on page 118 in this manual for detailed programming information.
It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains information on connecting a printer to the control panel and setting the printer options. MS-9200UDLS PN 52750:E1 01/27/09 ANN-BUS and power wiring are...
Page 32
Character Set Exec 10.5 SI.Zero Auto LF PAPER BIN 1 BIN 2 SINGLE PUSH TRA PULL TRA PAP ROLL MS-9200UDLS PN 52750:E1 Setting 10CPI Epson FX-850 9600 or 2400 7 Bit, Even, 1 Stop XON/XOFF Standard 12/72” 12/72” 12/72” 12/72”...
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40). ANN-I/O Module 24 VDC nonresettable MS-9200UDLS Figure 1.8 ANN-I/O Connection to FACP ANN-BUS/ACS BUS ANN-BUS and power wiring are supervised and power-limited MS-9200UDLS PN 52750:E1 01/27/09...
(yellow) indication for up to ten input zones or addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full system coverage. MS-9200UDLS PN 52750:E1 01/27/09...
The ANN-LED Module is supplied mounted to the DP-9692LED Dress Panel. Install the dress panel as described in the documentation supplied with the DP- 9692LED. ANN-BUS Connector Figure 1.10 ANN-LED Board Layout Alarm: 68 mA Standby: 28 mA F to 120 F (0 C to 49 MS-9200UDLS PN 52750:E1 01/27/09...
1.8.7.6.4 ANN-LED Connection to FACP Figure 1.10 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. MS-9200UDLS PN 52750:E1 01/27/09 ANN-LED ANN-BUS and power wiring are...
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis. Refer to documentation supplied with the relay module. ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 1.12 ANN-RLY Board Layout Alarm: 75 mA Standby: 15 mA F to 120 F (0 C to 49 MS-9200UDLS PN 52750:E1 01/27/09...
FACP input zone goes into alarm (refer to "Zone Message" on page 96). The message will play over the corresponding audio panel output circuit. MS-9200UDLS PN 52750:E1 01/27/09 ANN-BUS and power wiring are...
Page 40
A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the audio panel. Figure 1.1 FACP Connection to ACC-25/50ZS Series Audio Panel ACC-ZPMK on ACC-25/50ZS Series B (-) A (+) ANN-BUS FACP MS-9200UDLS PN 52750:E1 01/27/09...
• Go to Point Program to Enter Specific Data (refer to "Point Program" on page 65). Use the right and left arrow keys to navigate between devices. MS-9200UDLS PN 52750:E1 01/27/09 Annunciator Control Module annunciates 16 zones with 16 red...
Fire•Lite Alarms, Inc. One Fire-Lite Place Northford, CT 06472 (203) 484-7161 Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL11B9200UDLS Ringer Equivalence: 1.1B Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX.
FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre- mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant. MS-9200UDLS PN 52750:E1 01/27/09...
See Page mounting studs mounting slots grounding stud Figure 2.1 MS-9200UDLS Chassis Removal MS-9200UDLS PN 52750:E1 01/27/09 Mark and predrill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.3 on page 47...
14. Complete the installation as detailed in the following sections. Optional XRM-24B(E) Transformer mounting slot Standard XRM-24B(E) Transformer Mounting Studs Mounting Slot Figure 2.2 MS-9200UDLS Main Board/Chassis Installation Optional XRM-24B(E) Transformer Installation Slide top flange of XRM-24B(E) into slot at top left of chassis.
Page 47
Trim Ring Semi-flush mounting hole Hinge Slot for optional Dress Panel MS-9200UDLS PN 52750:E1 01/27/09 Figure 2.3 MS-9200UDLS Cabinet Mounting Installation Semi-Flush Mounting Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
Page 48
Installation Figure 2.4 MS-9200UDLS Cabinet Dimensions An optional Trim Ring (P/N TR-CE-) is also available for semi-flush mount installations. MS-9200UDLS PN 52750:E1 01/27/09...
2.3.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9200UDLS or 240 VAC, 50 Hz, 1.5 amps for the MS-9200UDLSE. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes.
Series field charger/power supplies. The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9200UDLS main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs"...
NACKEY must be inserted with text side facing in toward center of main circuit board and key into key- slot as illustrated to the right. It is keyed to prevent incorrect insertion. Top edge of MS-9200UDLS Main Circuit Board NACKEY card slot Figure 2.7 NAC Configuration Using NACKEY 2.5.2 Style Y (Class B) NAC Wiring...
FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB2 of the MS-9200UDLS to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics, the signal on NAC1.
Connection and wiring of two phone lines is required as shown below. Customer Premises Equipment and Wiring Unused RJ-11 Jack FACP with DACT Fax Machine Answering System Telephone Figure 2.12 DACT Installation Figure 2.13 Wiring Phone Jacks Computer Telephone Unused RJ-11 Jack MS-9200UDLS PN 52750:E1 01/27/09...
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. MS-9200UDLS Keypad/Display Removal Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display or access jumpers JP5 and JP7 or switch SW1,...
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
4XTMF module 3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-9200UDLS main circuit board, being careful not to bend any pins 4. Secure 4XTMF module to standoffs with supplied screws. 5. Reapply power to the FACP 6.
Page 58
Installation" on page 31 for installation details. Refer to "ANN-BUS Options" on page 118 for programming information. CAUTION! Do not connect a printer or PC to the MS-9200UDLS FACP if a ground fault (zero impedance to ground) exists on the control panel. Circuit damage may result.
Trouble Call Limit Remote Download 3.1 Programming Data Entry Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board.
Programming 3.2 User Programming The MS-9200UDLS is completely field programmable and requires no special software skills. While programming the MS-9200UDLS, the fire protection capabilities of the ! ! ! control panel are enabled. Site-specific programming may be accomplished in any of the following ways: •...
Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is followed to view all option choices. MS-9200UDLS PN 52750:E1 01/27/09 TROUBL IN SYSTEM NO DEVICES INSTALLED...
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD PROGRAMMING ENTER PASSWORD ***** PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK MS-9200UDLS PN 52750:E1 01/27/09...
If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen. MS-9200UDLS PN 52750:E1 01/27/09 PROGRAMMING 1=AUTOPROGRAM...
Pressing the ESC key will return the display to Programming Screen #1. AUTOPROGRAM AUTOPROGRAMMING! PLEASE WAIT Autoprogram Progress Screen # OF DET LOOP1 055 # OF MON LOOP1 035 # OF CON LOOP1 030 Autoprogram Result Screen #1 MS-9200UDLS PN 52750:E1 01/27/09...
When the last digit is keyed-in, the following screen will be displayed: Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector. MS-9200UDLS PN 52750:E1 01/27/09 POINT PROGRAM SELECT TYPE...
ADD DETECTOR DETECTOR# IS ADDED DELETE DETECTOR ENTER DETECTOR# Delete Detector Screen DELETE DETECTOR DETECTOR# IS DELETED EDIT DETECTOR ENTER POINT ADDRESS Edit Detector Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 67
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to view the Edit Detector screens. In the preceding example: MS-9200UDLS PN 52750:E1 01/27/09 NO DETECTOR INSTALLED...
Page 69
Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause 3=PRE-SIGNAL the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on Edit Detector Screen #3 page 167. MS-9200UDLS PN 52750:E1 01/27/09 DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1...
Page 70
Program an output, such as a control module, for Pre-signal activation by assigning zone Z98 to it. This control module may be connected to a signaling device used to indicate a Pre-signal condition (do not use a Notification Appliance Circuit for this purpose) MS-9200UDLS PN 52750:E1 01/27/09...
Page 71
2=DESCRIPTION Detector Screen #5 will cause the following screen to be displayed: ***************** Edit Detector Screen #5 MS-9200UDLS PN 52750:E1 01/27/09 Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre- signal delay timer to some value...
Page 74
0. If the last character is 9 it goes to 0 • The above increment function may be repeated with each press of the zero key DESCRIPTION 1D002 NOUN/ADJECTIVE ******************** Adjective/Noun Screen MS-9200UDLS PN 52750:E1 01/27/09...
005. When the last digit is keyed-in, the following screen will be displayed: Pressing 1 for Control Module or 2 for Monitor Module will cause the following MS-9200UDLS PN 52750:E1 01/27/09 MODULES...
3 in the Modules Screen. The following screen will be displayed: ADD MODULE MODULE# IS ADDED Add Module Screen #3 DELETE MODULE ENTER MODULE# Delete Module Screen DELETE MODULE MODULE# IS DELETED EDIT MODULE ENTER MODULE ADDRESS Edit Module Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 77
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Monitor screens. In the preceding example: MS-9200UDLS PN 52750:E1 01/27/09 NO MODULE...
Page 79
The display will return to the Edit Monitor Screen #2 which will show the new type selection. Table 3.1 on page 80 lists the Monitor Types and their respective functions. MS-9200UDLS PN 52750:E1 01/27/09 MONITOR TYPE...
Page 80
Acts like panel Acknowledge Key Acts like panel Silence Key Acts like panel Reset Key Acts like panel Drill Key PAS Disable Switch (see note 2) Acts like panel Drill Key, nonlatching (tracking) MS-9200UDLS PN 52750:E1 01/27/09...
Page 81
Pressing 1 while viewing ***************** Edit Monitor Screen #5 will cause the following screen to be displayed: Edit Monitor Screen #5 MS-9200UDLS PN 52750:E1 01/27/09 MON ZONE ASSIGN Z00 Z** Z** Z** Z**...
Page 83
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools utility. MS-9200UDLS PN 52750:E1 01/27/09 Programming **********************...
Page 84
0. If the last character is 9 it goes to 0 • The above increment function may be repeated with each press of the zero key DESCRIPTION 1M012 NOUN/ADJECTIVE ******************** Noun/Adjective Screen MS-9200UDLS PN 52750:E1 01/27/09...
In the preceding example: MS-9200UDLS PN 52750:E1 01/27/09 EDIT MODULE ENTER MODULE ADDRESS...
Page 86
EDIT CONTROL 1=ENABLED 2=TYPE CONTROL 3=SILENCEABLE Edit Control Screen #2 EDIT CONTROL 1=WALKTEST 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Control Screen #3 EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Control Screen #4 MS-9200UDLS PN 52750:E1 01/27/09...
Page 87
1. When using a control relay module to supply resettable power to conventional 2- wire smoke detectors, the addressable monitor module must be programmed for Smoke-Conventional operation 2. For HVAC SHUTDN description, refer to "Control Module Operation" on page MS-9200UDLS PN 52750:E1 01/27/09 CONTROL TYPE 1=BLANK...
Edit Control Screen #4 will cause the following screen to be displayed: Edit Control Screen #4 ZONE ASSIGNMENT Z00 Z** Z** Z** Z** Zone Assignment Screen 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 90
Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools programming utility. ********************** 1=KITCHEN 2=LOBBY 3=OFFICE Noun Screen #5 ********************** 1=PATIENT 2=RESTROOM 3=ROOM Noun Screen #6 ********************** 1=STAIRWAY 2=STOREROOM 3=WING Noun Screen #7 ********************** 1=ZONE Noun Screen #8 MS-9200UDLS PN 52750:E1 01/27/09...
Page 91
4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones MS-9200UDLS PN 52750:E1 01/27/09 DESCRIPTION...
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 108 for a description of this feature. MS-9200UDLS PN 52750:E1 01/27/09 ZONE TO DISABLE...
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central Station. MS-9200UDLS PN 52750:E1 01/27/09 ZONE TYPE PROG...
LiteSpeed Protocols. Device Addressing It is important to note that the MS-9200UDLS addressable device capacity is 99 detectors and 99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS.
2=BANNER 3=TIME-DATE System Setup Screen #1 SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS System Setup Screen #2 SYSTEM SETUP 1=CANADIAN OPT. 2=WATERFLOW SIL. System Setup Screen #3 BANNER 1=FACTORY 2=USER DEFINED Banner Screen FACTORY BANNER Factory Banner Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 99
When all characters have been entered, press the Enter key to store the information. The display will return to the Banner Screen. MS-9200UDLS PN 52750:E1 01/27/09 USER DEFINED BANNER...
CLR key to delete the entire entry and beginning again. TIME AND DATE 1=TIME 10:00 AM 2=DATE 04-07-2006 3=CLOCK FORMAT 12HR Time-Date Screen #1 TIME AND DATE 1=DAYLIGHT SAVINGS Time-Date Screen #2 ENTER TIME 10:00 AM 1=AM 2=PM Time Screen MS-9200UDLS PN 52750:E1 01/27/09...
In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May. MS-9200UDLS PN 52750:E1 01/27/09 ENTER DATE MONTH DAY YEAR...
Delay Screen which will indicate the new delay time. TIMERS 1=PAS DELAY 2=PRE SIGNAL 3=WATERFLOW Timer Screen #1 TIMERS 1=AC LOSS DELAY Timer Screen #2 PAS DELAY RANGE 0-180 SECONDS PAS Delay Screen MS-9200UDLS PN 52750:E1 01/27/09...
25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9200UDLS PN 52750:E1 01/27/09 PRESIGNAL DELAY...
NACKEY card is installed for Class A operation. AC LOSS DELAY 1=NO DELAY 2=ENTER DELAY AC Loss Delay Screen #1 AC LOSS DELAY RANGE 00-23 AC Loss Delay Screen #2 NACS 1=NAC 1 3=NAC 3 2=NAC 2 4=NAC 4 NAC Selection Screen MS-9200UDLS PN 52750:E1 01/27/09...
Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No. Note: The programming for NAC 1 will determine the operation of the remote power supply sync. MS-9200UDLS PN 52750:E1 01/27/09 NAC # 1=ENABLED...
NAC TYPE 1=BELL 2=HORN 3=STROBE Type Screen #1 Special Function None None None Synchronized to manufacturer Same as Synced Strobe but Silence turns off audible & visual devices None None None None MS-9200UDLS PN 52750:E1 01/27/09...
The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear: MS-9200UDLS PN 52750:E1 01/27/09 AUTO SILENCE...
Page 108
2nd stage activation will not be affected direct mapping of an input device programmed to Zone 99 or if the timer counts down to zero or when any NAC goes into 2nd stage coding device will not be delayed for activation MS-9200UDLS PN 52750:E1 01/27/09...
Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded: MS-9200UDLS PN 52750:E1 01/27/09 ZONE ASSIGNMENT...
When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors. MS-9200UDLS PN 52750:E1 01/27/09 SYSTEM SETUP 1=CANADIAN OPT.
After the History file has been erased, the display will return to the History Screen. HISTORY 1=VIEW EVENTS 2=ERASE HISTORY History Screen HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS View Events Screen ERASE HISTORY PROCEED ? 1=YES 2=NO Erase History Screen ERASING HISTORY PLEASE WAIT Erase History Wait Screen MS-9200UDLS PN 52750:E1 01/27/09...
All stored events can be scrolled on the screen by pressing the up or down arrow keys. To return to the first event, press the 1st Event key. MS-9200UDLS PN 52750:E1 01/27/09 WALKTEST...
Page 114
Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. UNTESTED POINTS 1D001 SMOKE (PHOTO) ********************* NOT TESTED WALKTEST RESULTS View Result Screen MS-9200UDLS PN 52750:E1 01/27/09...
A Terminal Mode annunciator, ACS Mode annunciator or ANN-BUS annunciator/ module can be installed in the MS-9200UDLS system. Do not use a mix of ACS annunciators and ANN annunciators since they use different communication protocols. ACS or ANN annunciators use the same TB9 terminal block connection.
No and Yes. The address of each installed annunciator must be enabled to allow communication between the FACP and annunciator. ACS OPTIONS 1=ACS ENABLED 2=ACS INSTALLED ANNUNCIATOR 1=ADDRESS 1 2=ADDRESS 2 3=ADDRESS 3 ACS Installed Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 117
ACS Annunciator Address The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to "Annunciators" on page 115 for information on annunciator programming. Make certain to program the annunciator addresses that have been physically installed on the system.
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module and relay module can be programmed into the MS-9200UDLS system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
Page 119
Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS Address Screen will display the available options as described below. MS-9200UDLS PN 52750:E1 01/27/09 ANN-BUS MODULE TYPE 1=NOT INSTALLED...
Page 121
40 LEDs on the remaining modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assignments for each ANN-I/O module will be as follows. Module LED MS-9200UDLS PN 52750:E1 01/27/09 Zone Range 0-29 Zone Range 30-69...
Page 122
Point 93 Point 94 Point 95 Point 96 Point 97 Point 98 Point 99 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used MS-9200UDLS PN 52750:E1 01/27/09...
Page 123
Point Option - Alarm Only (for use with ANN-RLED module)" on page 126. Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or addressable modules to be annunciated. MS-9200UDLS PN 52750:E1 01/27/09 ANN-LED ADDR # LOOP1 DET 1-10...
Page 124
Zone 33 Zone 34 Active/Alarm Active/Alarm Zone 38 Zone 39 Active/Alarm Active/Alarm Zone 43 Zone 44 Active/Alarm Active/Alarm Zone 48 Zone 49 Active Alarm Active/Alarm Zone 53 Zone 54 Active/Alarm Active/Alarm Zone 58 Zone 59 Active/Alarm Active/Alarm MS-9200UDLS PN 52750:E1 01/27/09...
Page 125
The LED assignments for the modules annunciating Zone Ranges 20 - 29, 30 - 39, 40 - 49, 50 - 59, 60 - 69, 70 - 79, 80 - 89 and 90 - 99, will follow the same pattern as the second ANN-LED module. MS-9200UDLS PN 52750:E1 01/27/09 ANN-LED Module #1...
Page 126
Point 34 Point 35 Active/Alarm Active/Alarm Point 39 Point 40 Active/Alarm Active/Alarm Point 44 Point 45 Active/Alarm Active/Alarm Point 49 Point 50 Active/Alarm Active/Alarm Point 64 Point 55 Active/Alarm Active/Alarm Point 59 Point 60 Active/Alarm Active/Alarm MS-9200UDLS PN 52750:E1 01/27/09...
Page 127
41 - 50, 51 - 60, 61 - 70, 71 - 80, 81 - 90 and 91 - 99, will follow the same pattern as the second ANN-LED Module. MS-9200UDLS PN 52750:E1 01/27/09 ANN-LED Module #1 (Point Range 01 - 10)
Page 128
ANN-RLY - ADDR. # 1=RELAY 1 ZONE 00 2=RELAY 2 ZONE 01 3=RELAY 3 ZONE 02 ANN-RLY Options Screen ANN-BUS AUTO-CONGFIGURE IN PROGRESS PLEASE WAIT Auto-Configure Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 129
Baud Rate of 19200, 9600 or 2400. Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select 7 or 8 Data Bits. MS-9200UDLS PN 52750:E1 01/27/09 ANN-S/PG OPTIONS...
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38. MS-9200UDLS PN 52750:E1 01/27/09 ON BOARD DACT...
Pressing 1 while viewing On Board DACT Screen #2 will cause the following screen to appear: ON BOARD DACT SECONDARY PHONE LINE 1=TYPE TOUCHTONE Secondary Phone Line Screen PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38 Secondary Phone Type Screen SERVICE TERMINAL 1=RING COUNT Service Terminal Screen MS-9200UDLS PN 52750:E1 01/27/09...
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle the display between Reporting Disabled and Reporting Enabled. MS-9200UDLS PN 52750:E1 01/27/09 RING COUNT RANGE 0-25 RANGE...
Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the Central Station an unlimited number of times. BACKUP REPORTING 1=BACKUP ONLY 2=FIRST AVAILABLE Backup Reporting Screen TROUBLE CALL LIMIT 00-99 RANGE Backup Reporting Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 135
1=PRIMARY Note that the following information must be entered for both the Primary and 2=SECONDARY Secondary Central Station Phone Numbers. 3=REPORT STYLE Central Station Screen #2 MS-9200UDLS PN 52750:E1 01/27/09 CENTRAL STATION # 1=TEST TIME INT 2=ACCOUNT CODE 0000 3=24HR TST TIME...
Enter the supplied account code using 0 - 9 and A- F keys. TEST TIME INTERVAL 1=24 HOURS 2=12 HOURS 3=8 HOURS Test Time Interval Screen #1 TEST TIME INTERVAL 1=6 HOURS Test Time Interval Screen #2 ACCOUNT CODE 4 CHAR RANGE 0-F Account Codes Screen MS-9200UDLS PN 52750:E1 01/27/09...
9. Enter 9 followed by D for a three second pause or E for a five second pause then the phone number followed by an F to indicate the end of the number. MS-9200UDLS PN 52750:E1 01/27/09 24 HOUR TEST TIME...
On Board DACT Screen #2 following screen to be displayed: Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone Line 2 Yes and No. MS-9200UDLS PN 52750:E1 SUPERVISE PHONE LINE 1=PHONE LINE 2 Panel ID Screen...
Yes will disable communications with the LCD-80F. The printer must be installed in the same room and within 50 feet of the FACP. PRINTER-PC 1=PRINTER NO SU 2=PRINTER SU 3=PC Printer-PC Screen PRINTER BAUD RATE 1=2400 BAUD 2=4800 BAUD 3=9600 BAUD Printer Baud Rate Screen MS-9200UDLS PN 52750:E1 01/27/09...
(such as 10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed: Re-enter the new password to accept the change. The display will return to the initial Password Change Screen. MS-9200UDLS PN 52750:E1 01/27/09 PASSWORD CHANGE 1=MASTER...
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared. CLEAR PROGRAM 1=WHOLE SYSTEM 2=ALL POINTS Clear Program Screen #1 WARNING! SYSTEM CHANGE PROCEED? 1=YES 2=NO MS-9200UDLS PN 52750:E1 01/27/09...
Note: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC 2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in the test. MS-9200UDLS PN 52750:E1 01/27/09 PROGRAM CHECK...
Page 146
Use the up and down arrow keys to view all the zones without output assignments. ZONES NO INPUT 05 07 09 10 11 1M001 ZONES NO OUTPUT 05 07 09 10 11 1D001 MS-9200UDLS PN 52750:E1 01/27/09...
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen. MS-9200UDLS PN 52750:E1 01/27/09 1=READ STATUS 2=PROGRAMMING...
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled POINT PROGRAM 1=DETECTOR 2=MODULE Device Select Screen EDIT DETECTOR ENTER POINT ADDRESS Address Select Screen EDIT DETECTOR 1D001 1=ENABLED Enable/Disable Select Screen MS-9200UDLS PN 52750:E1 01/27/09...
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will cause the display to return to the History Screen without erasing the History file. MS-9200UDLS PN 52750:E1 01/27/09 HISTORY 1=VIEW EVENTS...
PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Program Check Screen NACS NO INPUT NAC 1 25 31 44 55 67 ZONES NO INPUT 05 07 09 10 11 1M001 MS-9200UDLS PN 52750:E1 01/27/09...
The walktest session will not end until the Unit In Walktest screen is exited by pressing the Escape key to return to the Walktest Screen. MS-9200UDLS PN 52750:E1 01/27/09 ZONES NO OUTPUT...
Page 152
Pressing 3 for View Results while viewing the Walktest screen, after a walktest session has been completed, will allow the operator to view the final results of the most recent walktest. ALARM: MONITOR NORTH CLASSROOM 10*15A 012308 1M006 UNTESTED POINTS 1D001 SMOKE (PHOTO) ********************* NOT TESTED MS-9200UDLS PN 52750:E1 Z001 01/27/09...
The cursor will move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date Screen which will show the new date. MS-9200UDLS PN 52750:E1 01/27/09 SYSTEMS...
The next zone to be disabled can then be entered. Press Esc (Escape) to return to the previous screen. ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99 Zone Setup Screen ZONE TO ENABLE Enable Screen ZONE TO DISABLE Disable Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 155
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 108 for a description of this feature. MS-9200UDLS PN 52750:E1 01/27/09 SPEC PURPOSE ZONE...
It also performs a lamp test by turning on all LEDs (except the Ground LED), piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that exists after a reset will resound the system. MS-9200UDLS PN 52750:E1 01/27/09...
This is a green LED that blinks when a Central Station has acknowledged receipt of each transmitted message or when a portion of upload or download data has been accepted from a Service Terminal MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions...
To set the time and date, refer to the appropriate section in this manual. The MS-9200UDLS performs the following functions at regular intervals while in Normal mode: 4.4 Trouble Operation With no alarms in the system, the detection of a trouble will cause the following: •...
Page 159
• Third line in display: INVREP indicates an invalid reply from the addressable device. Other possible troubles include: • Fourth line in display: MS-9200UDLS PN 52750:E1 01/27/09 TROUBL SMOKE (PHOTO) <ADJ> <NOUN> 10:00A 010806 1D001 The type of event; in this example TROUBL indicating a device trouble Device type identifier;...
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. <NOUN>; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. Z000 MS-9200UDLS PN 52750:E1 01/27/09...
Refer to "Alarm Operation" on page 160, for a description of the information displayed on the control panel LCD. MS-9200UDLS PN 52750:E1 01/27/09 Time; the current time in this example is 10:00A which represents 10:00 AM Date;...
4.10 NAC Operation There are four Style Y (Class B) or two Style Z (Class A) programmable NACs (Notification Appliance Circuits) resident on the MS-9200UDLS main circuit board. All NACs may be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded operation.
4.15 Time Functions: Real-Time Clock The MS-9200UDLS includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset.
(NACs and control modules) of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs MS-9200UDLS PN 52750:E1 01/27/09...
PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling devices will immediately place the control panel into alarm. This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions...
73 seconds of the first alarm (13 second retard plus 60 second confirmation), the timer resets and the panel is ready to verify any new detector alarms which may occur. The following is a graphic representation of Alarm Verification. MS-9200UDLS PN 52750:E1 01/27/09...
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. MS-9200UDLS PN 52750:E1 01/27/09 CONFIRMATION (60 seconds) Control Panel Processes Alarm if Same Detector is Still in Alarm...
Read Status Screen #3 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Read Status Screen #5 READ STATUS 1=TIME-DATE Read Status Screen #6 MS-9200UDLS PN 52750:E1 01/27/09...
V - Alarm Verification Enabled (V = Yes, * = No) • S - Silenceable for control modules (S = Yes, * = No) • W - Walktestable for control and monitor modules (W = Yes, * = No) MS-9200UDLS PN 52750:E1 01/27/09 READ SYSTEM POINT SELECT TYPE 1=DETECTOR...
Zone Type - the Type assigned to each installed zone (default is Alarm) • Zone Message - the Message assigned to each installed zone ZONES 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zones Screen #1 ZONES 1=SPECIAL PURPOSE 2=ZONE TYPE 3=ZONE MESSAGE Zones Screen #2 MS-9200UDLS PN 52750:E1 01/27/09...
The following table lists the circuit being measured, possible conditions and their respective voltage ranges: Circuit Battery 24V Resettable 24V Nonresettable Charger NAC 1 or NAC 2 MS-9200UDLS PN 52750:E1 01/27/09 POWER BATTERY 27.21V 24 V RST 25.31 Power Screen #1...
These screens will indicate the delay time, in seconds, for each of the first three possible delay options. The AC Loss Delay time is displayed in hours. TROUBLE REMINDER TROUBLE REM TIMERS PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY MS-9200UDLS PN 52750:E1 01/27/09...
Pressing 1 while viewing Read Status Screen #3 will display the following screen: 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 The operator can view the programmed option for each relay by pressing the corresponding number key. MS-9200UDLS PN 52750:E1 01/27/09 1=NAC 1 3=NAC 3 2=NAC 2 4=NAC 4 RELAY...
2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS ANNUNCIATORS TERM ENABLED 2=ACS OPTIONS 3=ANN-BUS OPTIONS Annunciator Screen MS-9200UDLS PN 52750:E1 01/27/09...
Page 175
Pressing 3 for ANN-S/PG Options while viewing ANN-BUS Screen #1 will display the options selected for the installed serial or parallel printer. Pressing 1 for ANN-80 Options while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-80 annunciators. MS-9200UDLS PN 52750:E1 01/27/09 ACS OPTIONS ACS ENABLED...
PHONE LINE PRIMARY TOUCHTONE SECONDARY TOUCHTONE 3=SUPERV PHONE LINE SUPERVISE PHONE LINE PHONE LINE 2 CENTRAL STATION REPORTING ENABLED REPORT BOTH CALL LIMIT Central Station Screen #1 CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE Central Station Screen #2 MS-9200UDLS PN 52750:E1 01/27/09...
The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. MS-9200UDLS PN 52750:E1 01/27/09 SERVICE TERMINAL...
Page 179
DIRTY2 Maintenance Urgent Figure 4.1 illustrates a graphic representation of the maintenance levels: Maintenance Urgent MS-9200UDLS PN 52750:E1 01/27/09 Indicates A hardware problem in the detector Dust accumulation that is near but below the allowed limit. DIRTY 1 indicates the need for...
Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED START MONTH START WEEK WEEK-2 DAYLIGHT SAVINGS END MONTH END WEEK WEEK-1 MS-9200UDLS PN 52750:E1 01/27/09...
Note that as an option, all reports may also be sent to the secondary Central Station phone number. The MS-9200UDLS meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is: 1.
Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted reports to the Central Station. The Kissoff LED may turn on several times during communications with a Central Station. MS-9200UDLS PN 52750:E1 01/27/09...
Page 183
The table below shows UL listed receivers which are compatible with the MS-9200UDLS. Table 5.1 Compatible UL Listed Receivers Format SIA-DCS-8 SIA-DCS-20 Ademco Contact ID 1. With 685-8 Line Card with Rev. 4.4d software 2. With 124060V206B and 124063 Line Card Rev. B 3.
Pressing 3 for Remote Download while viewing the main menu will cause the following screen to be displayed: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD REMOTE DOWNLOAD ENTER PASSWORD ***** MS-9200UDLS PN 52750:E1 ™ XP or NEWER, 01/27/09...
There cannot be any active communications ongoing with a Central Station receiver All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station MS-9200UDLS PN 52750:E1 01/27/09 REMOTE DOWNLOAD 1=PROPRIETARY...
This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors. MS-9200UDLS PN 52750:E1 01/27/09...
Use Table 7.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system. Device Type MS-9200UDLS MS-9200UDLSE CHG-75 CHG-120F MS-9200UDLS PN 52750:E1 01/27/09 ) wire with 600 volt insulation for this Table 7.1 AC Branch Circuit Requirements Number of Current Draw Devices (AC amps) 3.00...
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm condition during a loss of AC power. Table 7.2 Converting to Full Amperes Multiply mA x 0.001 3 mA x 0.001 = 0.003A µ A x 0.000001 MS-9200UDLS PN 52750:E1 Example µ A x 0.000001 = 0.0003 A 01/27/09...
Page 189
Current limitations of TB3 & TB4 circuits is 2.5 amps per NAC output and 0.3 amps per special application auxiliary power output 10.Total current draw listed above cannot exceed 6.0 amps. MS-9200UDLS PN 52750:E1 01/27/09 Calculation Column 2...
18 AH. Batteries larger than 18 AH require a UL listed external battery charger and cabinet such as the BB-26, BB-55F or other UL listed external battery cabinet. Required Standby Time (24 hours) Required Alarm Time (for 5 min., enter 0.084, for 10 min., enter 0.168) X 1.2 MS-9200UDLS PN 52750:E1 01/27/09...
MMF-302 control module with address 04 CMF-300 control modules with addresses 09, 11 and 12 The example points out some of the key assignment features of the MS-9200UDLS. Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below).
Page 192
The zone correlations which are shown graphically above are also presented in Table A.1 on page 193 and Table A.2 on page 194. Zones Output Devices CMF-300 CMF-300 ZONE CMF-300 CMF-300 CMF-300 ZONE CMF-300 ZONE MS-9200UDLS PN 52750:E1 CMF-300 CMF-300 CMF-300 01/27/09...
Page 193
Table A.1 Detector Programming Sheet Example Address Device Zone Type Number SD350 SD350 CP350 CP350 SD350 SD350 SD350 MS-9200UDLS PN 52750:E1 01/27/09 DETECTOR ZONE ASSIGNMENT ADJ/NOUN Address Device Type FIRST HALL ELEV. LOBBY 2ND FLOOR ROOM 210 3RD FLOOR MEZZANINE MECH.
Page 194
MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone Type Number MMF-300 MMF-302 1, 2 MMF-302 1, 2 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 1, 2, 3 CMF-300 CMF-300 CMF-300 CMF-300 ADJ/ Address Device NOUN Type MS-9200UDLS PN 52750:E1 Zone ADJ/NOUN Number 01/27/09...
Page 195
Table A.3 Blank Detector Programming Sheet - 1 of 2 DETECTOR ZONE ASSIGNMENT Address Device Zone Type Number MS-9200UDLS PN 52750:E1 01/27/09 ADJ/ Address Device NOUN Type Software Zones Zone ADJ/NOUN Number...
Page 196
Software Zones Table A.4 Blank Module Programming Sheet - 1 of 2 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Zone Type Number ADJ/ Address Device NOUN Type Zone ADJ/NOUN Number MS-9200UDLS PN 52750:E1 01/27/09...
NFPA Standard-Specific Requirements APPENDIX C The MS-9200UDLS has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system components required for compliance with the appropriate NFPA standard are...
Page 199
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module and circuit. 3. Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.
Page 200
NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the 4XTMF module. 2. Refer to "4XTMF Transmitter Module Installation" on page 56 for detailed information.
Page 201
Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9200UDLS and the transmitter are supervised by the transmitter. 2. This MS-9200UDLS/Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System.
*Note: The Trouble Relay is a fail-safe relay. With power applied to the FACP and no troubles in the panel, the wiring should be connected to the NO and C contacts as indicated in the illustration. FACP Main Circuit Board MS-9200UDLS PN 52750:E1 01/27/09...
24 VDC, Nonresettable *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules. MS-9200UDLS PN 52750:E1 01/27/09 NFPA Standard-Specific Requirements Connect wires to two red terminals on box.
Fire Alarm Control Panel (terminal blocks are not shown in their actual positions in order to clarify wiring connections. *Note: For more information, refer to Keltron manual. 24 VDC nonresettable power MS-9200UDLS PN 52750:E1 01/27/09...
Connecting external system accessories to the MS-9200UDLS main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each MS-9200UDLS circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200UDLS circuit.
Page 206
Refer to "ANN-BUS Wiring" on page 24 for information on device wiring 18 AWG (0.75 mm ) minimum 12-18 AWG (3.25 - 0.75 mm 12-18 AWG (3.25 - 0.75 mm 12-18 AWG (3.25 - 0.75 mm 12-18 AWG (3.25 - 0.75 mm MS-9200UDLS PN 52750:E1 01/27/09...
HVAC SHUTDN control relay module only if there are no alarm conditions. The HVAC SHUTDN control relay module can be deactivated if trouble conditions exist on the FACP. HVAC Control MS-9200UDLS PN 52750:E1 01/27/09...
HVAC Shutdown from occurring only if it is initiated prior to an alarm condition. Note: Activation of the HVAC OVRRIDE module causes a supervisory event that will be communicated to the Central Station if enabled. MS-9200UDLS PN 52750:E1 01/27/09 HVAC Control...
C001 - Zone one alarm restored C002 - smoke detector zone two restored C003 - zone three fault restored C009 - zone nine reenabled C006 - high temperature, zone six C007 - gas detected, zone seven MS-9200UDLS PN 52750:E1 01/27/09...
Page 211
140 General AlarmALARM - General Alarm - # 141 Polling loop open 142 Polling loop short 143 Expansion module failure 144 Sensor tamper 145 Expansion module tamper MS-9200UDLS PN 52750:E1 01/27/09 Ademco Contact ID Format Event Code Descriptions EVENT CODE CLASSIFICATIONS TROUBLES OPEN/CLOSE...
Page 212
TROUBLE - Sys. Peripheral - # TROUBLE - Polling Loop Open TROUBLE - Polling Loop Short TROUBLE - Exp. Module Fail - # TROUBLE - Repeater Failure - # TROUBLE - Printer Paper Out TROUBLE - Local Printer MS-9200UDLS PN 52750:E1 01/27/09...
Page 213
416 Success - upload/access Access Control - 420 421 Access denied 422 Access report by user System Disables - 500 and 510 MS-9200UDLS PN 52750:E1 01/27/09 Ademco Contact ID Format Event Code Descriptions MESSAGE TROUBLE - Communication Trouble TROUBLE - Phone Line #1...
Page 214
TEST - Periodic (restore not applicable) TEST - Fire Test (restore not used) STATUS - Status Follows (restore not applicable) LISTEN - Listen-in Active (restore not applicable) TEST - Walk Test Mode TEST - System Abnormal Test MS-9200UDLS PN 52750:E1 01/27/09...
FACP addressable device address that is reporting. The following table indicates the Central Station Report (CS Report) number that will be transmitted and the addressable device address it represents. Detector Report Address MS-9200UDLS PN 52750:E1 01/27/09 Table H.1 Addressable DETECTORS Detector Report Address...
Page 222
Maintenance Level 153 System Point 169 system power 14 System Setup 97 Telephone Circuitry 42 Telephone Company Rights and Warnings 43 telephone line 54 Terminal 133 Test Time Interval 136, 137 Time and Date Maintenance Level 153 MS-9200UDLS PN 52750:E1 Index 01/27/09...
This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc.
Page 228
World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.com...
Need help?
Do you have a question about the MS-9200UDLS and is the answer not in the manual?
Questions and answers