Technical Data - ABB SROUT Technical Reference Manual

Router option card for lon star coupler rer 111
Table of Contents

Advertisement

SROUT
6.
18
Router Option Card for Lon® Star Coupler
RER 111

Technical data

Interfaces
Transformer-isolated twisted pair interface
Communication speed
Max. number of router option cards in one
RER 111 unit
Fibre-optic interface
Communication speed
Connection to mother board
Power source
From the mother board
Power consumption
SROUT-C-MM option card
SROUT-C-BB option card
Size
E1 card
Front plate
Disturbance tests
High frequency interference test
according to IEC 60255-22-1
- common mode
- differential mode
Fast transient test according to
IEC 61000-4-4 and IEC 60255-22-4, cl. 4
Electrostatic discharge test according to
IEC 61000-4-2 and IEC 60255-22-2, class III
- contact discharge
- air discharge
Environmental conditions
Specified ambient service temperature range -10...+55
Transport and storage temperature range
Climatic environmental tests
Dry heat test according to IEC 60068-2-2
Dry cold test according to IEC 60068-2-1
Damp heat test according to IEC 60068-2-30 RH = 93%, 55°C, 6 cycles
9-pin D-type female connector
78 kb/s or 1.25 Mb/s
2
glass fibre with ST-type connectors
plastic fibre with snap-in-type connectors
1.25 Mb/s
64-pin E1 connector
+8 VDC
<1.4 W
<1.4 W
100 mm x 160 mm
116.4 mm x 19.8 mm
2.5 kV, 1 Mhz
1.0 kV, 1 Mhz
4 kV
6 kV
8 kV
°
C
°
-40...+70
C
+55°C
-10°C
1MRS 750109-MUM