Page 1
Installation Owner’s Manual 7, 10, 13, 16 & 18kW Air-cooled, Automatic Standby Generators LISTED Not intended for use as Primary Power in place of utility or in life-support applications. DANGER DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
INTRODUCTION This symbol points out potential explosion haz- Thank you for purchasing this compact, high per- ard. formance, air-cooled, engine-driven generator. It is This symbol points out potential fire hazard. designed to automatically supply electrical power to operate critical loads during a utility power failure. ...
Table of Contents Air-cooled Generators Introduction ......Inside Front Cover Section 3 – Operation ........15 Read This Manual Thoroughly ......IFC Using the AUTO/OFF/MANUAL Switch ..15 Contents ............IFC Automatic Transfer Operation ..... 15 Operation and Maintenance ......IFC Sequence of Automatic Operation ....15 How to Obtain Service ........
IMPORTANT SAFETY INSTRUCTIONS Air-cooled Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all opera- tors and potential operators of this equipment. ...
IMPORTANT SAFETY INSTRUCTIONS Air-cooled Generators • Keep a fire extinguisher near the generator at all ELECTRICAL HAZARDS times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for • All generators covered by this manual produce use on the standby electric system.
Section 1 — General Information Air-cooled Generators There are LED readouts on the control panel to notify DANGER personnel that one of these faults has occurred. There is also a System Set LED that is lit when all Only qualified electricians or contractors should of the conditions described in section "System Set attempt such installations, which must comply LED"...
Section 1 — General Information Air-cooled Generators THE GENERATOR Figure 1.1 – 7kW, Single Cylinder, GH-410 Engine Figure 1.2 – 10kW, V-twin, GT-530 Engine Control Panel de Panel contrrol Data Label Etiqueta de datos Varilla medidora (see sample) (consulte la muestra)
Section 1 — General Information Air-cooled Generators SYSTEM SET LED Special considerations should be given when install- ing the unit where local conditions include flooding, The “System Set” LED is lit when all of the following tornados, hurricanes, earthquakes and unstable conditions are true: ground for the flexibility and strength of piping and 1.
Section 1 — General Information Air-cooled Generators RECONFIGURING THE NOTE: Use an approved pipe sealant or joint compound FUEL SYSTEM on all threaded fittings to reduce the possibility of leakage. 1.9.1 7 KW, 410CC ENGINE 9. Reverse procedure steps 1-6 to reinstall demand To reconfigure the fuel system from NG to LP , follow regulator.
Section 1 — General Information Air-cooled Generators 1.10 LOCATION 3. Close the roof. 4. Reverse the procedure to convert back to natural 1.10.1 GENERATOR gas. Install the generator set, in its protective enclosure, Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back) outdoors, where adequate cooling and ventilating air is always available (Figure 1.9).
Section 1 — General Information Air-cooled Generators • Install the generator as close as possible to the fuel supply, to reduce the length of piping. • Install the generator as close as possible to the If the AUTO/OFF/MANUAL switch is not set to its transfer switch.
Section 1 — General Information Air-cooled Generators NOTE: The following procedures are to be observed: • Wear full eye protection and protective clothing; Dielectric grease should be used on battery posts • Where electrolyte contacts the skin, wash it off to aid in the prevention of corrosion.
E1 tion until all power voltage supplies to the and E2. 7kW voltage should be 242-252 volts at transfer switch have been positively turned off. a frequency of 61-63 Hertz. 10, 13, 16 and 18kW...
E1 and E2. • About one minute after retransfer, the engine • 7kW voltage should be greater than 230 volts and should shut down. frequency should be greater than 58 Hz.
Then, tighten the governor lever clamp bolt to 70 inch-pounds ADJUSTMENT (8 N-m). 2.7.1 7KW UNITS Figure 2.1 — Engine Governor Adjustment With the frequency between 62-63 Hertz at no-load, Single Cylinder Engines slowly turn the slotted potentiometer (Figure 2.2) until line voltage reads 248-252 volts.
Section 3 — Operation Air-cooled Generators USING THE AUTO/OFF/MANUAL AUTOMATIC TRANSFER SWITCH (FIGURE 3.1) OPERATION To select automatic operation, do the following: 3.1.1 “AUTO” POSITION 1. Make sure the transfer switch main contacts are Selecting this switch position activates fully automatic set to their UTILITY position, i.e., loads con- system operation.
Section 3 — Operation Air-cooled Generators C. Standby Voltage Sensor 7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source • This sensor monitors generator AC output volt- now powers the loads. age. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby Figure 3.2 –...
Section 3 — Operation Air-cooled Generators SETTING THE EXERCISE TIMER • If utility is still lost after 10 seconds, run the engine up to 3600 RPM and transfer the load. This generator is equipped with an exercise timer. At this time the controller will exit the exercise Once it is set, the generator will start and exercise routine and assume full automatic operation.
If the RPM signal is detected, the engine will start 3.7.3.1 Approximate Crank Cycle Times and run normally. If the RPM signal is subsequent- 7kW Units: ly lost again, the control board will try one more • 15 seconds ON re-crank attempt before latching out and flashing •...
The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL ” MARK. Figure 4.2 — Oil Dipstick and Fill, 7kW Oil Fill Oil Dipstick and Fill CHANGING THE ENGINE OIL 4.3.1 OIL CHANGE INTERVALS...
1. Start the engine by moving the AUTO/OFF/ cleaner. Use the following procedures (Figure 4.6, MANUAL switch to MANUAL and run until it 7kW; Figure 4.8, 13/16kW): is thoroughly warmed up. Then shut OFF the engine by moving the switch to the OFF position.
Section 4 — Maintenance Air-cooled Generators 4.4.2 10KW GENERATORS SPARK PLUG(S) Reset the spark plug(s) gap or replace the spark See Figure 1.2 for the location of the air cleaner. Use plug(s) as necessary. See the Service Schedule section the following procedure (Figure 4.7): for maintenance requirements.
Section 4 — Maintenance Air-cooled Generators ADJUSTING GH-410/GT-530/990 • Remove the 15A fuse from the generator control panel. VALVE CLEARANCE • Remove watches, rings or other metal objects; • Use tools with insulated handles; After the first six (6) months of operation, check •...
Section 4 — Maintenance Air-cooled Generators • Re-attach the spark plug wire to the spark plug. • On the GT-530 and GT-990, repeat the process for the other cylinder. The exhaust from this product gets extremely Figure 4.10 - Valve Clearance Adjustment hot and remains hot after shutdown.
Page 26
Section 4 — Maintenance Air-cooled Generators 7. Attach a tag to the engine indicating the viscosity 4. Clean and wipe the entire generator. and classification of the oil in the crankcase. 5. Make sure the 15A fuse is removed from the 8.
Section 4 — Maintenance Air-cooled Generators 4.12 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Dealer. SYSTEM/COMPONENT PROCEDURE FREQUENCY X = Action W = Weekly R = Replace as Necessary M = Monthly Inspect Change Clean...
Section 5 — Troubleshooting Air-cooled Generators TROUBLESHOOTING GUIDE Problem Cause Correction The engine will not crank. 1. Fuse blown. 1. Correct short circuit condition, replace 15A fuse in generator control panel. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables.
Section 7 — Exploded Views and Parts Lists Air-cooled Generators Enclosure – Drawing No. 0G5050-E SHEET METAL PAINT/MATERIAL CODE LEGEND The following exploded views contain part numbers of various sheet metal components. Only the base part number is listed. When ordering sheet metal, the correct color and material information must be included as a suffi...
Page 41
049813 NUT HEX M6-1.0 G8 0D1840 BRACKET, BOTTOM SUPPORT 0A1658 LOCK WASHER SPECIAL 1/4 047411 SCREW HHC M6-1.0 X 16 G8.8 (7KW) 0G0617 EXTERNAL CONNECTION BOX 047411 SCREW HHC M6-1.0 X 16 G8.8 092079 SCREW TAPTITE M6-1.0 X 25 BP 0F0710 RIVET POP 0.125”...
Page 42
Section 7 — Exploded Views and Parts Lists Air-cooled Generators Control Panel – Drawing No. 0F9695-F...
Page 43
Section 7 — Exploded Views and Parts Lists Air-cooled Generators Control Panel – Drawing No. 0F9695-F ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V (7KW) 0D8502 NEUTRAL BLOCK 0E7886D CIRCUIT BREAKER 45A X 2P 240V 031879...
Page 44
Section 7 — Exploded Views and Parts Lists Air-cooled Generators Transfer Switch Assembly – Drawing No. 0F9774-C...
Page 45
Section 7 — Exploded Views and Parts Lists Air-cooled Generators Transfer Switch Assembly – Drawing No. 0F9774-C ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0F8278 BOX LOAD CENTER 074138 LUG QUICK DISCONNECT NI-S 10X45 0D4800 COVER, 8 CIRCUIT LOAD CENTER DEG BRASS / TIN 0F5211 COVER, 10 CIRCUIT LOAD CENTER...
Page 46
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 13, 16 & 18kW, GT-990 Engine – Drawing No. 0G3071-L - Part 1...
Page 47
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 13, 16 & 18kW, GT-990 Engine – Drawing No. 0G3071-L - Part 1 ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0C5729 ASSY, CRANKCASE WITH SLEEVE 043790A BARBED ELBOW 90 3/8NPT X 3/8 VS 0E9843A SEAL, 38 I.D.
Page 48
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 13, 16 & 18kW, GT-990 Engine – Drawing No. 0G3071-L - Part 2...
Page 49
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 13, 16 & 18kW, GT-990 Engine – Drawing No. 0G3071-L - Part 2 ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 022145 WASHER FLAT M8 – 5/16 0D1143 WRAPPER, UPPER CYLINDER 2 0C5136A KNOB, AIR CLEANER...
Page 50
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 1...
Page 51
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 1 ITEM PART NO. QTY. DESCRIPTION 0E9428B CRANKCASE 0E3812 SEAL D 35 X 48.2 0C8566 SCREW HHFC M6 – 1.0 X 20 0E9367A ASSY, BREATHER 0E9366...
Page 52
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 2...
Page 53
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 2 ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 022097 WASHER LOCK M6-1/4 094090 THERMAL SWITCH 0E9561 INTAKE ADAPTER 0F2094 SCREW PPHM M3-0.5 X 6 SEMS 0E9472...
Page 54
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 1...
Page 55
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 1 ITEM PART NO. QTY. DESCRIPTION 0E3221 ASSEMBLY, CONNECTING ROD 0E1466 PIN, PISTON D20 021533 SET, PISTON RING 90MM 0E2985 PISTON, HC...
Page 56
Section 7 — Exploded Views and Parts Lists Air-cooled Generators 7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 2...
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
Page 67
Section 10 – Warranty Air-cooled Generators EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
Page 68
® GENERAC POWER SYSTEMS, INC. P.O. BOX 297 • WHITEWATER, WI 53190 Part No. 0G4869 Revision C (09/25/07) Printed in U.S.A. Catalog No. OMASPB07-3...