Mitsubishi Electric PUHZ-W85VHA2 Service Manual page 36

Air to water heat pump
Hide thumbs Also See for PUHZ-W85VHA2:
Table of Contents

Advertisement

SW2 setting
Sub cool (SC)
ON
0~130
Cooling: SC = T
1
2 3 4 5 6
Heating: SC = T
Input current of outdoor unit
0~500
ON
1
2 3 4 5 6
LEV-B opening pulse
0~500
ON
1
2 3 4 5 6
U9 error detail history (latest)
ON
1
2 3 4 5 6
Direct current bus voltage
150~400
ON
1
2 3 4 5 6
Capacity save
0 ~ 100
ON
When there is no setting
of capacity save, "100" is
1
2 3 4 5 6
displayed.
Deferred error history (2)
ON
of outdoor unit
1
2 3 4 5 6
Deferred error history (3)
of outdoor unit
ON
1
2 3 4 5 6
Display detail
-TH3
63HS
-TH6
63HS
Explanation for display
0~130
(When the SC is 100°C or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0~500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
Cause
Error details
(No error)
Over voltage
Power PCB
Insufficient
Power PCB
voltage
Input current
Control PCB
sensor error
ACTM error
Control PCB
150~400
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~100
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 secs.
Deferred error code display
Blinking: being deferred
Lighting: deferment is cancelled
"00" is displayed in case of no deferment.
Deferred error code display
Blinking: being deferred
Lighting: deferment is cancelled
"00" is displayed in case of no deferment.
36
Code
00
01
02
04
20
0.5 secs. 2 secs.
1
00
Unit
°C
0.1 A
Pulse
Code
display
V
%
Code
display
Code
display