Pulse Train Input Operation
The WJ200 inverter is capable of accepting pulse train input signals, that are used for
frequency command, process variable (feedback) for PID control, and simple positioning.
The dedicated terminal is called "EA" and "EB". Terminal "EA" is a dedicated terminal, and
the terminal "EB" is an intelligent terminal, that has to be changed by a parameter setting.
Terminal Name
EA
EB
(Input terminal 7)
(1) Frequency Command by pulse train input
When using this mode, you should set
input-capture, and calculated based on the ratio of designated max. frequency (under
32kHz). Only an input terminal "EA" will be used in this case.
(2) Using for process variable of PID control
You can use the pulse train input for process variable (feedback) of PID control. In this
case you need to set
(3) Simple positioning by pulse train input
This is to use the pulse train input like an encoder signal. You can select three types of
operation.
CALL NOW 800-985-6929
http://www.automatedpt.com
RS485
comm.
SN 7
Relay contact
SP EO
AL2 AL1 AL0
Pulse
RS485
Train
comm.
output
Description
Pulse train input A
Pulse train input B
(Set
C007
to
85
)
A001
A076
to 03. Only "EA" input terminal is to be used.
http://www.automatedpt.com
Logic input
6
5
4
3
2
EA
H
O
OI
L
AM CM2
Pulse
Analog
Analog
Train
output
input
input
For frequency command, 32kHz max.
Reference voltage: Common is [L]
27Vdc max.
For frequency command, 2kHz max.
Reference voltage: Common is [PLC]
to 06. In this case the frequency is detected by
43
Email: charles@automatedpt.com
1
L
PLC
P24
Short bar
12 11
Logic
output
Ratings