FPA-5000 OPC-Server Table of Contents | en Table of contents Purpose Preconditions Installation Installation of FSM-5000-OPC Software Remote Access to the FSM-5000-OPC Server from the Building Integration System (BIS) Backward Compatibility 3.3.1 Package: BIS600StateConversion.msi 3.3.2 Package: LanguageDependentCommand.msi Step-by-Step Configuration FSP-5000-RPS...
Purpose This document contains information on accessing and controlling FPA-5000 networks via OPC using the FSM-5000-OPC server. It is designed to aid in successfully configuring the FPA-5000 network and the corresponding FSM-5000-OPC server to enable communication between the two via a single or redundant Ethernet connection. In completing these steps successfully a functional interface is provided for a subsequent connection to BIS 2.x which functions as...
| Preconditions FPA-5000 OPC-Server Preconditions The following must be available to set up an OPC server in an FPA-5000 network: – FPA-5000 network with MPC-xxxx-B or MPC-xxxx-C – ADC-5000-OPC license card – Latest FSP-5000-RPS installation CD – The correct FSM-5000-OPC Server version for the respective FPA-5000 release (available on FSP-5000-RPS installation CD or download from Extranet).
On the setup disc open the folder that contains the FSM-5000-OPC installation. Click “FPA5000OPCServer.msi” and follow the installation instructions. Open the Configuration Editor: Start → All Programs → Bosch → FPA5000OPC-Server and run Configuration Editor or open Windows Explorer, navigate to C:\Program Files\Bosch\FPA 5000OPC-Server and run ConfigEditor.exe or for FSM-5000-OPC version 1.2 right click on the respective icon in the taskbar...
| Installation FPA-5000 OPC-Server All of the following settings refer to the PC running the OPC server. Notice! The following steps are based on the Windows XP operating system. For all other operating systems the paths to the respective dialogs might be slightly different.
FPA-5000 OPC-Server Installation | en Select on the right side: Network access: Sharing and security model for local accounts. Right click on this selection to open Properties and choose Classic– local users authenticate as themselves. Close all windows and restart the PC.
In an existing 2.x configuration select “Nodes” in the tree view and choose “Create FPA-5000 OPC- Server” in the context menu. A new node with name FPA-5000 OPC-Server is created and a dialog box for configuration is opened. Configure the OPC server node.
If the configuration was successful, all panels which are assigned to the OPC server should have the status “connected”. You can also find these information in a log file, located on C:\Program Files\Bosch \FPA5000 OPC-Server\Log (for Windows XP, might be slightly different for other operating systems).
| Troubleshooting FPA-5000 OPC-Server Troubleshooting If the configuration of the FSM-5000-OPC server doesn’t work with the FPA-5000 network try the following: – Confirm on the panel controller that the IP address is assigned and “ping” the OPC server. –...
Technical data | en Technical data Supported OPC standards: – DA 2.0 – AE 1.01 Other Standards – “BIS Common Requirements” (Bosch standard). Supported operating systems: – Windows XP Professional – Windows 2003 Server 32-bit – Windows 2008 Server 64-bit –...
Page 14
| Technical data FPA-5000 OPC-Server at the end stands for full duplex-capable cable. at the end stands for fiber optic cable. For example: 100BASE-TX indicates a Fast Ethernet connection (100 Mbps) that uses a twisted pair cable capable of full-duplex transmissions.
FPA-5000 OPC-Server Appendices | en Appendices Appendix A.1 - State Table 1 OPC Item Value Internal Panel Description Compound State Invalid Normal Fault Fire Fire Pre state AND / Cross zoning Fire verify Alarm Verification Heat Supervisory Supervisory Error Smoke...
Page 16
| Appendices FPA-5000 OPC-Server Not enough address Address card changed and now there are less space addresses licensed than points configured Address card tamper The countdown after address card removal is finished, addresses are to be switched off Fire internal Internal fire, results from a usage type “FIRE_INT”...
FPA-5000 OPC-Server Appendices | en Isolate Activation failed Isolate Alarm Normal Day Mode Fault Day Mode Alarm Day Mode Table 7.1: Appendix A.1 - State Table 1 Appendix A.2 - State Table 2 OPC Item Value Description LZ Name Missing Zone...
Page 18
| Appendices FPA-5000 OPC-Server Acknowledgement Malfunction Malfunction power supply Switch Off Alarm verification Address Blocking Triggering generic R-FG Maint.-Stand-by OMM R-GE Maint.-Light Pollution R-G0 Maint.-Heavy Pollution R-G2 Maint.-Alarm OMM R-AL Maint.-Stand-by/Control Off R-GE Maint.-Breakdown Centr. Part R-G8 Maint.-Control On R-STE Maint.-Malfunction Ground...
Need help?
Do you have a question about the FPA-5000 and is the answer not in the manual?
Questions and answers