Powerware Series ® Eaton 9140 UPS 7.5–10 kVA User's Guide...
Page 2
Association, Inc. All other trademarks are property of their respective companies. ECopyright 2006–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Page 3
92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact: Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland...
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
— causing hours of lost productivity and expensive repairs. With the Eaton 9140, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Eaton 9140 UPS with an optional Extended Battery Module (EBM).
Page 8
INTRODUCTION Providing outstanding performance and reliability, the Eaton 9140's unique benefits include the following: Online, double-conversion, high-frequency UPS design with pure sine wave output and power-factor correction. The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery.
To comply with international standards and wiring regulations, the sum of the leakage current of the UPS and the total equipment connected to the output of this UPS must not have an earth leakage current greater than 3.5 milliamperes. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 10
60 ampere (10 kVA-modeller) eller 50 ampere (7,5 kVA-modeller) i overensstemmelse med National Electrical Code, ANSI/NFPA 70. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Zelfs in de modus Standby of REPO kunnen de uitgangsaansluitingen onder spanning staan. Bij lijn-naar-lijn bekabeling (208V lijn-naar-lijn, eenfase), bijvoorbeeld, bedraagt de spanning bij de uitgangsaansluitingen 110–120V (gemeten vanaf neutraal- naar-aarde). 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 12
Houd onbevoegden uit de buurt van de accu's. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 13
50 ampeeria kansallisten sähkösäännösten ANSI/NFPA 70:n mukaan. Kansainvälisten standardien mukaan UPS:n ja kaikkien sen lähtöön kytkettyjen laitteiden vuotovirran summan maavuotovirta ei saa ylittää 3,5 milliampeeria. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 14
La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d'eau ou dans une atmosphère excessivement humide (95 % maximum). 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 15
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Leitung anschließen, die mit einem Überlaststromschutz von 60 Ampere (10 kVA-Modelle) oder 50 Ampere (7,5 kVA-Modelle) in Übereinstimmung mit dem National Electrical Code, ANSI/NFPA 70 ausgestattet ist. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All'interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL'UTENTE. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 18
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
50 ampere (7.5 kVA modeller) klassifisering i henhold til National Electrical Code, ANSI/NFPA 70. For å overholde internasjonale standarder og ledningsføringsregelverk må summen av lekkasjestrømmen til UPS og totalutstyret tilkoblet UPS-utgangen ikke ha en jordlekkasjestrøm over 3,5 milliampere. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 20
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%). 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 21
Î Ï À Ñ Í Î Â äàííîì ÈÁÏ èìåþòñÿ ÑÌÅÐÒÅËÜÍÎ ÎÏÀÑÍÛÅ ÍÀÏÐ߯ÅÍÈß. Âñå ðàáîòû ïî ðåìîíòó è îáñëóæèâàíèþ äîëæíû âûïîëíÿòüñÿ ÒÎËÜÊÎ ÓÏÎËÍÎÌÎ×ÅÍÍÛÌ ÎÁÑËÓÆÈÂÀÞÙÈÌ ÏÅÐÑÎÍÀËÎÌ. Âíóòðè ÈÁÏ íåò óçëîâ, ÎÁÑËÓÆÈÂÀÅÌÛÕ ÏÎËÜÇÎÂÀÒÅËÅÌ. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 22
äîïóñêàéòå ê ðàáîòå ñ áàòàðåÿìè ïîñòîðîííèõ. Íåîáõîäèìî ñîáëþäàòü ïðàâèëà óòèëèçàöèè àêêóìóëÿòîðîâ. Îáðàòèòåñü ê ìåñòíûì íîðìàòèâíûì àêòàì çà èíôîðìàöèåé î òðåáîâàíèÿõ ê óòèëèçàöèè. Íèêîãäà íå áðîñàéòå àêêóìóëÿòîðû â îãîíü. Àêêóìóëÿòîðû ìîãóò âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
60 amperios (modelos 10 kVA) o 50 amperios (modelos 7.5 kVA) de acuerdo con el Código Eléctrico Nacional, ANSI/NFPA 70. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 24
Uttagen kan vara spänningsförande även i vilo- eller REPO-läget. Med ingångskopplingen ledare-till-ledare (208 V ledare-till-ledare, enfas) är till exempel spänningen i uttagen 110–120 V (mätt från nolla till jord). 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 25
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
UPS directly above the EBM(s). If installing optional EBM(s), continue to the following section, “EBM Setup.” Otherwise, continue to “UPS Setup” on page 32. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
INSTALLATION EBM Setup The Eaton 9140 EBM comes with all hardware required for installation in a standard EIA or JIS seismic rack-mount configuration with square or round mounting holes. The rail assemblies adjust to mount in 19-inch panel racks from 24 to 33 inches deep (28.5 to 32 inches deep if installing the optional seismic mounting brackets).
If access to the sides of your rack is difficult, adjust the length of the rails (see Figure 4) and loosely install the fasteners (see Figure 6) before continuing to Step 3. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 31
Adjust the rail size on the rail assembly for the depth of your rack (see Figure 4). Rear Front Figure 4. Adjusting the Rail Depth (Right Rail Assembly Shown) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 32
7 mm (9/32”) nut driver. See Figure 6. Repeat for the other rail. M4 Locknuts M4 Screws Figure 6. Tightening the Rail Adjustment (Right Rail Assembly Shown) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 33
If the rack holes are round, use two clip nuts. 13. Slide the EBM into the rack. Verify that the rear mounting brackets engage in and slide easily along the inside of the rails. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 34
EBM above the rear mounting brackets. Loosely secure the brackets with four supplied wing bolts. See Figure 9. Do not tighten the wing bolts. Figure 9. Installing the Optional EBM Seismic Mounting Brackets 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 35
EBM to the rack using four M6 machine screws as shown in Figure 10. Tighten the wing bolts on the seismic mounting brackets. M6 Screws Figure 10. Securing the Optional EBM Seismic Mounting Brackets 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Slide the battery trays into the cabinet (see Figure 12). Push each tray in until the battery tray lock on the handle catches to lock the tray in place. Battery Tray Lock Figure 12. Installing the Battery Trays 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 37
INSTALLATION Replace the EBM front cover and tighten the two front cover screws (see Figure 13). Figure 13. Replacing the EBM Front Cover 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
INSTALLATION UPS Setup The Eaton 9140 UPS comes with all hardware required for installation in a standard EIA or JIS seismic rack-mount configuration with square and round mounting holes. The rail assemblies adjust to mount in 19-inch panel racks from 24 to 33 inches deep (28.5 to 32 inches deep if installing the optional seismic mounting brackets).
Rail and Lower Front Mounting Bracket Position 4 Position 3 Position 2 Bottom of Rack or Top of Other Cabinet Figure 14. Front Rail Screw Positions for the UPS 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 40
(see Figure 14 and Figure 15). Do not tighten the screws. Front M5 Screws Position 6 Position 5 Position 4 Position 1 Adapter Plate Figure 15. Securing the Front Rail 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 41
Position 6 Position 5 Position 4 Bottom of Rack or Position 3 Top of Other Cabinet Position 2 Position 1 Figure 17. Securing the Rear Rail (Right Rail Assembly Shown) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 42
7 mm (9/32”) nut driver. See Figure 18. Repeat for the other rail. M4 Locknuts M4 Screws Figure 18. Tightening the Rail Adjustment (Right Rail Assembly Shown) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 43
UNLOCK position. Grasp the handle at the bottom of the module and pull the module slowly out of the cabinet. Use two hands to support the module. Figure 19. Removing the UPS Front Cover and Electronics Module 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 44
UPS and secure with four supplied M4 flat-head screws. Rear Mounting Brackets (2) Front Mounting Brackets (4) Figure 20. Installing the UPS Front and Rear Mounting Brackets 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 45
Position 17 (M6 screw and cage/ clip nut) Position 11 Position 8 Position 3 (M5 screw) Position 2 (M5 screw) Optional Figure 21. Securing the Front of the UPS 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 46
UPS above the rear mounting brackets. Loosely secure the brackets with the eight supplied wing bolts. See Figure 22. Do not tighten the wing bolts. Figure 22. Installing the Optional UPS Seismic Mounting Brackets 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 47
18. Replace the electronics module by sliding it carefully into the cabinet. Verify that it seats against the rear of the cabinet. Turn the module lock switch to the LOCK position. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Figure 25. Replacing the UPS Front Cover If you are installing an optional EBM, continue to the following section, “EBM Installation.” Otherwise, continue to “UPS Installation” on page 45. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
EBM cable firmly in place. Continue to the following section, “UPS Installation.” NOTE After UPS installation, ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 72). 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Eaton 9140 plug-receptacle models require a dedicated branch circuit that meets the following requirements: 60A (10 kVA models) or 50A (7.5 kVA models) circuit with short circuit and overcurrent protection 200–240 Vac...
Page 52
Plug the UPS input power cord into an IEC 309-60A power outlet. indicator flashes, indicating the UPS is in Standby mode with the equipment offline. The fans run and the LCD illuminates and displays the UPS startup screens. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 54
EBMs” on page 72. NOTE The batteries charge to 80% capacity in less than 5 hours. However, it is recommended that the batteries charge for 48 hours after installation or long-term storage. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Eaton 9140 hardwired models require a dedicated branch circuit that meets the following requirements: For single-phase: 60A (10 kVA models) or 50A (7.5 kVA models) circuit with short circuit and overcurrent protection For three-phase: 30A (10 kVA models) or 20A (7.5 kVA models) circuit...
Page 57
NOTE Neutrals are bonded inside the terminal block. Wire the input and bypass terminal blocks so they share the same ground and neutral and have inputs of the same frequency. NOTE Install no more than one wire per terminal. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 59
Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 1.5 cm (0.5”) of insulation from the end of each incoming wire. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 60
10. Connect the input bypass and ground wires to the input bypass terminal block according to Figure 33 and Table 2. Line In Neutral In Input Bypass L1-JP Ground Figure 33. UPS Input Bypass Terminal Block 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 61
11. Connect the output and ground wires to the output terminal block according to Figure 34 and Table 3. Neutral or L2 Out Line/L1 Output Ground Figure 34. UPS Output Terminal Block 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 62
15. Plug the equipment to be protected into the UPS output receptacles, but do not turn on the protected equipment (see Figure 28 on page 50). 16. Make any necessary provisions for cord retention and strain relief. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 63
EBMs” on page 72. NOTE The batteries charge to 80% capacity in less than 5 hours. However, it is recommended that the batteries charge for 48 hours after installation or long-term storage. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
INSTALLATION REPO and ROO Installation The Eaton 9140 includes a two-position terminal (see Figure 35) that can be either left open or configured one of two ways: As a remote emergency power-off (REPO) contact that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location.
Page 65
Verify that the externally-connected REPO or ROO switch is not activated to enable power to the UPS output receptacles. Plug in or apply utility power to the UPS. The UPS enters Standby mode. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 66
10. Activate the external REPO or ROO switch to test the function. Verify the status change on the UPS display. 11. REPO only. De-activate the external REPO switch and restart the UPS. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Chapter 4 Operation This chapter contains information on how to use the Eaton 9140, including front panel operation, operating modes, UPS startup and shutdown, configuring the UPS for Extended Battery Modules (EBMs), initiating the battery test, and transferring the UPS between modes.
To change the language setting, select MENU from the system status screen, then select SETUP, USER SETUP, and LANGUAGE. Scroll through the available options and press the button to select the language. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
OPERATION Display Functions When the UPS starts up, the LCD displays the Eaton logo and the type of UPS. About 5 seconds after startup or after 15 minutes of inactivity, the LCD displays the system status screen. The system status screen shows the output voltage, output frequency, output load percent, and the current operating mode (see Figure 36 on page 61).
NOTE This option is not used. * Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise, the changes do not take effect. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 71
Contact Type: [N/O][N/C] * Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise, the changes do not take effect. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
OPERATION Operating Modes The Eaton 9140 front panel indicates the UPS status through the UPS indicators. Figure 36 on page 61 shows the UPS front panel indicators and controls. Figure 37 shows the internal circuit configuration. Bypass Figure 37. Internal Circuit Configuration...
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. The indicator flashes slowly, indicating that power is not available to your equipment. The battery recharges when necessary. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
If the indicator is flashing, check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. Turn on the protected equipment. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
The LCD displays a confirmation message and the indicator illuminates solid. The UPS is now in Battery mode and supplying battery power to your equipment. Turn on the protected equipment. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
UPS is operating in Bypass mode. The load is now powered by utility power. (Optional) Press any button to silence the alarm. Turn on the protected equipment. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
The LCD displays a confirmation message and all indicators flash slowly, indicating that the UPS is powering down and no longer supporting the load. The UPS disconnects from the batteries and powers off in approximately 10 seconds. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
90 days if this option is enabled. To enable or disable the automatic battery test, select MENU from the system status screen, then select SETUP, USER SETUP, and BATTERY TEST. Select to enable or disable the automatic test. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
From Bypass to Standby Mode. Select MENU from the system status screen, then select CONTROL, OUTPUT CONTROL, and UPS TO OFF. Confirm the selection by pressing and holding the button for three seconds to select OK. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Chapter 5 Communication The Eaton 9140 UPS is equipped with a USB port, a REPO port, two DB-9 communication ports, and an X-Slot communication bay (see Figure 38). Two parallel ports are available for future use. Either the USB port or the RS-232 DB-9 communication port may be used to monitor the UPS;...
Software Suite CD. Remote Emergency Power-off and Remote On/Off The Eaton 9140 includes a two-position terminal that can be either left open or configured one of two ways: As a remote emergency power-off (REPO) contact that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location.
Page 83
When REPO is activated for a UPS with line-to-line 208V input, the output receptacles will have 120V neutral (L2) to ground. REPO/ROO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size REPO/ROO 0.82–0.33 mm 0.82 mm (18 AWG) (18–22 AWG) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
COMMUNICATION DB-9 Communication Ports The Eaton 9140 provides two DB-9 ports on the UPS rear panel. The service port is not intended for customer use and does not support standard communication protocols. The RS-232 port is available for UPS monitoring, control, and flash upgrades.
X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 9140 has an available communication bay for one of the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Eaton 9140 UPS battery power becomes low, LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
(applicable to equipment and remote battery supplies not having a grounded supply circuit). ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them out of the EBM. Figure 41. Removing the EBM Front Cover 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 90
Lock Figure 42. Installing the Battery Trays Replace the EBM front cover (see Figure 43) and tighten the two front cover screws. Figure 43. Replacing the EBM Front Cover 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
To remove the front cover, loosen the two front cover screws. Grasp the fingergrips on both sides of the cover and pull the cover forward firmly. Figure 44. Removing the UPS Front Cover 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 92
Slide the new battery trays into the cabinet. Push each tray in until the battery tray lock on the handle catches to lock the tray in place. Replace the UPS front cover and tighten the two front cover screws. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
UPS. If you prefer to remove input power to change the electronics module, see “UPS Shutdown from Normal or Bypass Mode” on page 71. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 94
Grasp the fingergrips on both sides of the cover and pull the cover forward firmly. Turn the module lock switch to the UNLOCK position. The UPS transfers to Bypass mode. Figure 46. Removing the Electronics Module 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
(4) Internal Battery Trays: 17 kg (37 lb) each Total EBM Weight: 82 kg (179 lb) Total Plug-Receptacle UPS Weight: 110 kg (240 lb) Total Hardwired UPS Weight: 107 kg (234 lb) 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 98
Output Receptacles Plug-Receptacle Models: Hardwired Models: (4) C19, (3) C19 and (1) dual C13, each with 20A circuit breaker each with 20A circuit breaker Full Output IEC 309-60A Hardwired 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 99
Agency Markings cULus, cUL, NOM Hardwired models only: TÜV, CE EMC (Class A) EN 50091-2, FCC Part 15, ICES-003 Seismic Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 100
37.5 65.5 75% Load 86.5 50% Load 51.5 78.5 98.5 25% Load >120 >180 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Chapter 8 Troubleshooting The Eaton 9140 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Page 102
The UPS does not provide the The batteries need charging or Apply utility power for 48 hours to charge the expected backup time. service. batteries. If the condition persists, contact your service representative. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Page 103
User cancelled the battery test Reschedule the battery test if necessary. through the front panel. Battery test report shows CANCELLED. Battery charge cycle has not Wait 48 hours. completed. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
Press any button on the front panel display to silence the alarm. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Help NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 9120, 9125, 9130, 9135, 9140, and FERRUPS up to 3.1 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004, and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 108
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. 164201622 Rev 3 www.eaton.com/powerquality Eaton 9140 UPS (7.5–10 kVA) User's Guide...
In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Page 110
In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.