Specifications - 4200Fa 75Kva Without Internal Transformer - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 75 / 80 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

5.2
Specifications – 4200FA 75kVA without Internal Transformer
Model Number
Rated Output Capacity
External Dimensions
Weight
Rated Voltage
Voltage Variation
Rated Frequency
Number Phases / Wires
* Power Factor
Main Input
Required Input Power
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
Rated Voltage
Optional
Voltage Variation
Bypass
Rated Frequency
Input
Number Phases / Wires
DC Nominal (Voltage Range)
Float Charge (Regulation)
Battery
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Number Phases / Wires
Voltage Regulation
(phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Output
Frequency Synchronous
Operation Range
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 mS)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
Efficiency
Heat loss to be removed
Audible Noise
Environment
Operating Temperature
Operating Humidity
Altitude ***
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. An initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult factory for higher elevations).
(****) Prolonged operation at this level requires derating of the maximum operating temperature to 35°C.
T O S H I B A
T42F3F750@AXXN
44 inch W x 31 inch D x 74 inch H
+10% to –15% ; (-15% to –30%) ****
3 Phase / 3 Wire
Greater than 0.99 when in inverter mode
70kW when in inverter mode
From 20% to 100% over 5 seconds
Less than 12 times rated current under synchronous operation
115% maximum
Less than 3% THD
@ = (X-n/a, F-208)Vac
+10% to –15%
3 Phase / 4 Wire + GND
288VDC (230 to 332VDC)
328VDC (±2%) with 2.28V/cell
Refer to Battery System Manual
20.0 Amps ****
208 / 120 VAC
3-phase / 4 Wire + GND
± 2% (0-100% balanced load)
± 3% (0-100% unbalanced load)
± 5V Manually from front key pad
± 2° (0-100% balanced load)
± 4° (unbalanced load)
± 0.1% in free running mode
± .5/1.0/1.5 Hz (± 1.0 Hz. std.)
switch selectable by qualified technician
1 Hz/s to 3 Hz/s
± 3% (100% load step change)
± 5% (loss or return of input voltage)
± 3% (transfer of bypass to inverter)
125% 30sec ; 150% 5sec
1000% 10msec; 125% 10min.
1.73 times line rating
1.5% max (linear load)
Automatic transfer to bypass, then retransfer to inverter
AC/DC/AC: 87% typical; DC/AC: 90% typical
40,000Btu/hr (10kcal·kg/hr)
75 dB (A) at 1 meter from the units front display
0 to 40°C; optimal operating temperature is 25°C
Less than 90% RH (non-condensing)
Less than 1000 meters
33
75kVA
1560 pounds
208 Vac
50/60 Hz
50/60 Hz
2% R.M.S.
208 Amps
0.8 lagging
50 / 60 Hz
2.5