Because controlled system applications vary widely, you should satisfy yourself as to the acceptability of this equipment for your intended purpose. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
Safety Precautions CAUTION Turn off power to the PLC (T2, T2E or T2N) and to this module (AD268, DA264 or TC218) before removing or mounting this module. Failure to do so can cause electrical shock or damage to this product.
About This Manual About This Manual This manual describes the specification and the operations of Toshiba's analog I/O modules (AD268, DA264 and TC218) for PROSEC T2 series programmable controllers. Read this manual carefully for your correct operation of these modules.
PART 1 AD268 1. Introduction The AD268 is an 8 channel analog input module for the T2 series programmable controllers. The AD268 converts external analog signals (voltage or current) into digital values cyclically so that the T2 can process the analog signals.
2. Specifications PART 1 AD268 2. Specifications This section describes the AD268 specifications. The general specification for the AD268 conforms to the specification for the T2 PLC. 2.1 Specifications Item AD268 Input type Voltage input Current input -5 to 5V...
The converted digital data reaches to the internal control circuit through optical isolator. Every time when the T2 CPU requests to read the converted data, the internal control circuit sends the data to the T2 CPU. The AD268's parameters are stored in the EEPROM. User’s Manual...
3. Input Type Setting The AD268 supports multiple input ranges, 5V, 10V, 0 to 5V, 0 to 10V, 1 to 5V, 0 to 20mA, or 4 to 20mA. The input range is selected by jumper plug setting and the parameter writing by the T2 program.
PART 1 AD268 3.2 Parameter setting by software The input range of the AD268 is specified by writing the following parameter data into the AD268's buffer memory. To access the buffer memory, T2 user program (READ and WRITE instructions) is required.
4. Wiring PART 1 AD268 4.2 Signal wiring Voltage input AD268 Voltage source Set the jumper +15V plug to Side 1 Shielded twisted-pair cable -15V n : Channel number (1 to 8) Internal circuit AG : Analog ground FG : Frame ground...
(6) If the converted data is not stable owing to electrical noise, it is recommended to use the input averaging function to reduce the noise interference. For the averaging function, refer to section 6. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
In this case, the AD268 is mounted in the slot 0 of base unit BU218. In the above example, the AD268 is allocated on the unit-0, slot-0. And 8 I/O registers, XW000 to XW007 are assigned to the AD268.
PART 1 AD268 5.2 A/D conversion data The analog signals received by the AD268 are converted into the digital data in this module. These converted digital data are read by T2 CPU in the batch I/O processing and stored in the assigned input registers as follows.
Page 21
5. I/O Allocation and Programming PART 1 AD268 5V range: A/D conversion data Input voltage Resolution Hexadecimal Integer Upper limit +5.1196 V H3FFF 16383 Full scale (positive) +5 V H3E80 16000 +0.3125 mV H0001 H0000 0.3125 mV / bit -0.3125 mV...
Page 22
32000 H3FFF 16383 Analog input -10.2V +5.1196V +10.2V D = 3200 D: Digital data A: Analog signal (V) Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 23
5. I/O Allocation and Programming PART 1 AD268 0 to 5V / 0 to 20mA range: Input voltage/current A/D conversion data Resolution 0 to 5 V 0 to 20 mA Hexadecimal Integer Upper limit +5.1196 V +20.479 mA H3FFF 16383...
Page 24
4 to 20mA range: +5.1196V 20.479mA D = 800 A - 3200 D: Digital data A: Analog signal (mA) Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
To read the A/D conversion data, there is no need to use special instruction. The A/D conversion data are automatically stored in the assigned input registers (XW registers). For example, when the AD268 is allocated to XW000 to XW007, the A/D conversion data of each channel is stored as follows.
PART 1 AD268 6. Parameters The AD268 has the memory that stores the control parameters, input type designation, module status information, etc. This memory is called the buffer memory. To access (read/write) this memory from the T2 program, READ and WRITE instructions are used.
Page 27
6. Parameters PART 1 AD268 Address Contents H8028 Analog input actual value for channel 1 H8029 Analog input actual value for channel 2 H802A Analog input actual value for channel 3 H802B Analog input actual value for channel 4 H802C...
Page 28
Gain calibration value & Offset calibration value: (Gain: H8000 to H8007, Offset: H8008 to H800F) At the factory shipment, the AD268 is calibrated for each input range. Therefore, there is no need for user to calibrate normally. However, depending on the usage condition, field adjustments are required. For this purpose, the AD268 has the gain and offset calibration function.
Page 29
6. Parameters PART 1 AD268 Averaging times: (H8010 to H8017) This parameter is for the averaging processing for the analog input data. The moving average is calculated by the given averaging times parameter. For example, if the averaging times parameter is 10, the average value of latest 10 times conversion is output as the A/D conversion data.
Page 30
6. Parameters PART 1 AD268 Command register: (H8020) This register is used to issue the following commands to the AD268. To issue the command, write the command value by using WRITE instruction. Value Command Description Write 0 after the command processing is completed.
Page 31
1 when the AD268’s processor is not normal. ROM status 1 when the AD268’s EEPROM is not normal. DP-RAM status 1 when the AD268’s DP-RAM (buffer memory) is not normal. Reserved External 24V error 1 when the external 24Vdc is not normal.
When you change the AD268 parameters, such as input type settings, gain/offset calibrations and averaging times, use the following procedure. Step (1) Write the value "0" into the command register of the AD268 buffer memory (address H8020) by WRITE instruction. H8020...
This is an example to set the input type as 0 to 10V range (type = 1) for each channel. In this sample program, it is assumed that he AD268 is allocated to XW000 to XW007. For details of READ and WRITE instructions, refer to the T-series Instruction Set manual.
PART 1 AD268 7. Troubleshooting 7.1 RAS information The RUN LED is provided on the front of the AD268. When the AD268 is operating normally, this LED is lit. Also the module status information is provided in the AD268‘s buffer memory (addresses H8030 to H8037).
7. Troubleshooting PART 1 AD268 7.2 Troubleshooting The table below shows the trouble and its remedy. Trouble Module Module operation Cause Remedy status info Input type Bit 7 is ON The error channel Invalid input type Set the correct setting error...
2. Specifications PART 2 DA264 2.2 Internal block diagram Amplifier Buffer Voltage (V V) output Amplifier Current T2 CPU (V I) output Amplifier Buffer Voltage (V V) output Amplifier Current (V I) output Reference voltage Regulator +15V -15V Voltage check circuit The DA264 performs the following operations.
The factory setting is 0 to 5V / 0 to 20mA range. Refer to section 6 for the sample program to set the output type. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
4. Wiring PART 2 DA264 4. Wiring 4.1 Terminal arrangement DA264 terminal block Terminal Signal Function name Channel 1 Voltage output Channel 1 Current output Channel 2 Voltage output Channel 2 Current output Channel 3 Voltage output Channel 3 Current output Channel 4 Voltage output Channel 4 Current output External 24Vdc power (+)
4. Wiring PART 2 DA264 4.3 Wiring precautions (1) Use shielded twisted-pair cables for analog output signal lines and wire them in shortest distance. Connect the cable shield to ground in shortest distance for EMC conformity. Normally the grounding method (a) is recommended. However, depending on the condition, method (b) or (c) may be useful for stable operation.
In the above example, the DA264 is allocated on the unit-0, slot-0. And 4 I/O registers, YW000 to YW003 are assigned to the DA264. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
5. I/O Allocation and Programming PART 2 DA264 5.2 D/A conversion data To output the desired analog signals from the DA264, simply write the appropriate data into the assigned I/O registers YW(n) to YW(n+3) for the DA264. The data of YW(n) to YW(n+3) are transferred to the DA264 at the T2’s batch I/O processing. Then in the DA264, these D/A conversion data are converted into the analog signals and output from the DA264.
Page 48
H3FFF 32767 16383 A = 0.3125 D: Digital data -5.12V Lower limit A: Analog signal (mV) HC180 -16000 Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 49
5. I/O Allocation and Programming PART 2 DA264 0 to 10V range: D/A conversion data Output voltage Resolution Hexadecimal Integer Upper limit H7F80 32640 +10.2 V Full scale (positive) H7D00 32000 +10 V 0.3125 mV / bit H0001 +0.3125 mV H0000 Analog output value +10V...
Page 50
0 to 20mA range: -32768 32767 16383 A = 1.25 D: Digital data A: Analog signal ( A) Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 51
5. I/O Allocation and Programming PART 2 DA264 1 to 5V / 4 to 20mA range: D/A conversion data Output voltage/current Resolution Hexadecimal Integer 1 to 5 V 4 to 20 mA Upper limit H337F 13183 +5.1196 V +20.479 mA Full scale (positive) H3200 12800...
Rung 2: During R1001 is ON, YW000 data is decreased by 32 (channel 1 analog output is decreased by 0.01V) every scan. It is lower-limited by -32000 (-10V). Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
6. Parameters PART 2 DA264 6. Parameters The DA264 has the memory that stores the control parameters, output type designation, module status information, etc. This memory is called the buffer memory. To access (read/write) this memory from the T2 program, READ and WRITE instructions are used. These parameter data are not maintained in the DA264.
Page 54
Offset calibration value Voltage Current Upper limit +39.69 mV +158.75 A Default value Lower limit -127 -39.69 mV -158.75 A Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 55
6. Parameters PART 2 DA264 Output type setting: (H8004 to H8007) This parameter is used to select the output type. This parameter also has a function to select either clear or hold the analog output signal in case of the T2 operation stop (Halt or Error). The available setting range is as follows.
Page 56
1 when the D/A conversion data is limited because of the range over. External 24V error 1 when the external 24Vdc is not normal. Reserved Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
6. Parameters PART 2 DA264 6.2 Sample program to access the parameters To write the parameters into the DA264’s buffer memory, use the WRITE instruction. No special procedure is required. To read the parameters from the DA264’s buffer memory, use the READ instruction. A sample program to write/read the parameters is shown below.
Check the Internal 15V error is stopped. Output external 24Vdc voltage is not signal is 0V/0mA. power supply. normal. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 62
6) Burnout detection function 7) Input data averaging function 8) Gain and offset calibration function ( 100mV input only) Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 63
1. Introduction PART 3 TC218 1.2 External features Model type TC218 Status indication LED Removable terminal block Analog input terminal External power supply connection terminal Line ground and Frame ground terminal Terminal block fixing screw 2-points For thermocouple input, CH2 to CH8 are used to connect the thermocouple input wires. The CH1 is used to connect the thermistor to measure the ambient temperature for cold junction compensation.
Page 65
2. Specifications PART 3 TC218 2.2 Internal block diagram Reference voltage Buffer Jumper +15V T2 CPU Buffer Jumper +15V EEPROM Buffer Jumper Regulator +15V -15V Voltage check circuit The TC218 performs the following operations. The external analog signals come to the buffer amplifier through the filter. The multiplexer sequentially selects CH1 to CH8 to convert the input analog signals into digital data via the A/D converter.
Use a pair of tweezers to set the jumper plug. Pay attention not to touch the components on the board other than the jumper plug. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 67
3. Input Type Setting PART 3 TC218 3.2 Parameter setting by software The input type of the TC218 is specified by writing the following parameter data into the TC218's buffer memory. To access the buffer memory, T2 user program (READ and WRITE instructions) is required.
Page 69
4. Wiring PART 3 TC218 4.2 Signal wiring 100mV input (CH1 to CH8) TC218 Voltage source +15V +15V Shielded twisted-pair cable Set the jumper plug to Side 3 -15V n : Channel number (1 to 8) Internal circuit AG : Analog ground FG : Frame ground Thermocouple input TC218...
Page 70
(6) When this module is used for thermocouple input, connect the thermistor to channel 1 (CH1). The thermistor is attached with this module. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 71
5. I/O Allocation and Programming PART 3 TC218 5. I/O Allocation and Programming 5.1 Allocation to the T2 registers The I/O type of the TC218 is "X 8W". When the automatic I/O allocation operation is performed with a TC218 mounted on the rack, the TC218 is allocated as "X 8W".
-102mV +51.196mV +102mV D = 320 HC000 D: Digital data -16384 A: Analog signal (mV) H8300 -32000 -100mV Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 73
5. I/O Allocation and Programming PART 3 TC218 Thermocouple (type K) input: Input A/D conversion data Resolution temperature Hexadecimal Integer Burnout detection H7FFF 32767 Upper limit +1370 C H6B08 27400 Full scale (positive) H5DC0 24000 +1200 C H0001 +0.05 C 0.05 C / bit H0000 HFFFF...
Page 74
HF060 D = 20 -4000 +800 C Lower limit -200 C D: Digital data A: Temperature ( C) Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 75
5. I/O Allocation and Programming PART 3 TC218 Thermocouple (type E) input: Input A/D conversion data Resolution temperature Hexadecimal Integer Burnout detection H7FFF 32767 Upper limit +1000 C H4E20 20000 Full scale (positive) H2EE0 12000 +600 C H0001 +0.05 C 0.05 C / bit H0000 HFFFF...
Page 76
490 to 510 C 9800 XW001 10200 450 to 490 C 9000 XW001 9800 Less than 450 C XW001 9000 Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 77
6. Parameters PART 3 TC218 6. Parameters The TC218 has the memory that stores the control parameters, input type designation, module status information, etc. This memory is called the buffer memory. To access (read/write) this memory from the T2 program, READ and WRITE instructions are used. 6.1 Memory map The contents of the TC218's buffer memory are as follows.
Page 78
H8035 Module status for channel 6 H8036 Module status for channel 7 H8037 Module status for channel 8 Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 79
6. Parameters PART 3 TC218 Gain calibration value & Offset calibration value: ( 100mV input only) (Gain: H8000 to H8007, Offset: H8008 to H800F) For the 100mV input, the gain and offset calibration is possible. In the TC218, the A/D conversion data is calculated as follows. A/D conversion data Offset Gain...
Page 80
Type K thermocouple Type J thermocouple Type E thermocouple 100mV The default setting value (factory setting) is 5 ( 100mV). Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 81
6. Parameters PART 3 TC218 Command register: (H8020) This register is used to issue the following commands to the TC218. To issue the command, write the command value by using WRITE instruction. Value Command Description Write 0 after the command processing is completed. When this command is issued, the parameters written into Parameter set the buffer memory are saved in the TC218 ’s EEPROM, and...
Page 82
External 24V error 1 when the external 24Vdc is not normal. Initializing 1 during the TC218 is in initialization process. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
6. Parameters PART 3 TC218 6.2 Parameter setting procedure When you change the TC218 parameters, such as input type settings, gain/offset calibrations and averaging times, use the following procedure. Step (1) Write the value "0" into the command register of the TC218 buffer memory (address H8020) by WRITE instruction.
For reading the parameters from the TC218, there is no special procedure. Simply read the data from the TC218’s buffer memory by using READ instruction. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...
Page 85
7. Troubleshooting PART 3 TC218 7. Troubleshooting 7.1 RAS information The RUN LED is provided on the front of the TC218. When the TC218 is operating normally, this LED is lit. Also the module status information is provided in the TC218‘s buffer memory (addresses H8030 to H8037).
Page 86
The A/D conversion Check the Internal 15V error is stopped. external 24Vdc voltage is not power supply. normal. Analog I/O Modules (AD268 / DA264 / TC218) CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net...