Installer System Test - Honeywell FocusPRO TH5220D Installation Manual

Non-programmable digital thermostat
Hide thumbs Also See for FocusPRO TH5220D:
Table of Contents

Advertisement

FocusPRO
TH5220D Non-programmable Digital Thermostat

Installer system test

Follow the procedure below to test the heating, cooling and fan.
To begin, press and hold the
buttons until the display changes
System Test
10
Heating system
20
Emergency
heating system
30
Cooling system
40
Fan system
70
Thermostat
information
(for reference only)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
and
System Status
0 Heat and fan turn off
1 Heat turns on. Fan also turns on immediately if Function 1 is set
to "1" or "5," or if Function 3 is set to "1"
2 Second stage heat turns on
0 Heat and fan turn off
1 Heat and fan turn on
2 Second stage heat turns on (Aux)
0 Compressor and fan turn off
1 Compressor and fan turn on
2 Second stage compressor turns on
0 Fan turns off
1 Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System test
number
10
Done
Press
Press
Press
N N E E X X T T
Press
D D O O N N E E
13
System
status
Next
to turn on system
to turn off system
to advance to next test
to terminate system test
**See page 11
0

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FocusPRO TH5220D and is the answer not in the manual?

Questions and answers

Cindy Toney
February 6, 2025

I have a loose brown wire in my thermostat. They’re all have wires connect except for the L and RC. Do I need to try and hook it

User image 67a4fa0898be5
Chip
January 16, 2025

Is there a way to adjust thermostat accuracy? Thermostat reads 74 degrees but with thermo tester all rooms are 71 degrees.

Table of Contents