Strike Profile - Bosch D9210C Program Entry Manual

Access control interface module
Table of Contents

Advertisement

Access Control Interface Module
3

Strike Profile

This programming category is used to create a specific door profile on:
Door #
Default:
Selections
Enter the door you are programming.
D# Strike Time
Default:
Selections:
Enter the amount of time the relay output for the strike will activate to allow a user to open
the door. The strike will activate upon a valid token, Request to Enter [RTE], Request to Exit
[REX], and the Command Center [CYCLE DOOR?] function.
Blank Strike Time is not programmed for this door.
1-240 The strike will activate for the amount of time programmed.
D# Shunt Time
Default:
Selections:
Enter the amount of time that the door point will be shunted to allow a user to open the door
without causing the point to go into Trouble, Alarm or a faulted condition.
Blank TShunt Time is not programmed for this door.
1-240 The shunt will activate for the amount of time programmed.
D# Buzz Time
Default:
Selections:
Enter the amount of time that the buzzer output will activate to notify the user that the strike
has been activated and the door is ready to open. The buzzer will stop as soon as the door is
opened.
NOTICE!
A separate buzzer is required. Many readers have an internal buzzer that is not affected by
Buzz Time.
Bosch Security Systems, Inc.
Strike and shunt times.
Extending strike and shunt times if a door is left open.
Resetting the strike when the door opens.
Programming the interlock point.
1
1-8
10
1-240 seconds
10
Blank, 1-240
2
Blank, 1-240 seconds
Program Entry Guide
Strike Profile | en
9