5000
5001
5020
5021
5059
4580
4581
4583
5089
1590
EBL512 G3 Article number = Type number plus required parameters, e.g. 5000xxPRTCC-aaa.
xx
= Design style (customer option, e.g. colour)
PRT = With printer
CC
= Country Code
aaa
= 128, 256 or 512 alarm points (customer option, e.g. 512)
Voltage
primary (V AC)
secondary / system voltage (V DC)
Current consumption (A)
Ambient temperature (C)
operating
storage
Ambient humidity (% RH)
Ingress Protection rating
Inputs
Outputs
Size W x H x D (mm)
Weight (kg)
Colour (metal cabinet)
Approvals
Note! All voltages are nominal.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW01251
Type numbers
EBL512 G3 c.i.e. with or without a printer and 128, 256 or 512 alarm points are
depending on the article number. Supplied with a standard mounting plate
approved for an incombustible wall (e.g. concrete).
EBL512 G3 c.i.e. No front, no display & no door with plexiglass. 128, 256 or
512 alarm points are depending on the article number. Supplied with a standard
mounting plate approved for an incombustible wall (e.g. concrete).
Mounting plate for 19'' mounting rack. For one 5000 / 5001.
Mounting plate for inflammable wall (e.g. wood). For one 5000 / 5001.
Paper rolls (spare part for the printer mounted in 5000). Four pieces.
8 zones expansion board (8 zone line inputs for conventional detectors).
8 relays expansion board (8 programmable relay outputs).
In- and outputs expansion board.
Connection cable for up to six expansion boards (4580-4583).
TLON connection board – required for a TLON network. One board in each
c.i.e. NOTE! For redundant network two 1590 boards are required in each c.i.e.

Technical data

230 (50 Hz)
24 (By backup battery 21 – 30.)
AC current: 1.6.
DC current: Depending on type (5000 / 5001), expansion board(s), etc.
see EBL512 G3 Planning Instructions (MEW01182).
0 to +40
-40 to +70
max. 90, non-condensing
IP30
4 COM loops for 1020 addresses. 128, 256 or 512 alarm points.
4 programmable
4 programmable supervised voltage outputs
2 programmable relay outputs
Relay outputs for routing equipment (Fire alarm and Fault condition)
Power supply (6 x 24 V DC) for Web-server, routing equipment, external
equipment, etc.
5000: 438 x 628x 187
5000: 20 / 5001: 19
Light grey (NCS S1500-N, PMS Cool Grey 2)
EC certificate no. 0786-CPD-20982
EN54-2:1997 / A1:2006, EN54-4:1997 / A2:2006
The Swedish front conforms to SS3654.
Date of issue
2010-06-08
5001: 418 x 625 x 177
Revision / Date of revision
1 / 2010-09-30