16.2. VM-3360VA Voice Alarm System Amplifier
Power Source
Power Consumption
Rated Output
Frequency Response
Distortion
S/N Ratio
Audio Input/Output
Characteristic
Input
Output
RM Link
Network I/F
VM Link
EXT PA Link
General Control
Emergency Control
ATT Control
Power Input/Output
24 V DC Output
Ds Link
230 V AC, 50/60 Hz
850 W (at rated output), 380 W (according to EN60065)
360 W
50 Hz – 20 kHz, ±3 dB (at 1/3 rated output)
0.7% or less (at rated output, 1 kHz)
85 dB or more
Sampling frequency: 48 kHz
A/D D/A converter: 24 bit
Input 1 – 3:
–50 dB* (MIC) / –10 dB* (LINE) (changeable), 600 Ω,
electronically balanced,
combined XLR connector (female) / phone jack
Input 4:
–50 dB* (MIC) / –10 dB* (LINE) (changeable), 600 Ω,
electronically balanced, removable terminal block (14 pins)
BGM 1 – 2:
–10 dB*, 10 kΩ, unbalanced, RCA pin jack
External AMP Input: 100 V line, removable terminal block (14 pins)
Speaker output 1 – 2: Max. (360 W) per output
Speaker output 3 – 6: Max. (120 W) per output
Speaker output 1 – 6: Total within 360 W, removable terminal block (14 pins)
Allowable minimum load:
Direct output:
Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
Input 1 – 2:
Connecting the RM-300MF/200M Remote Microphone,
RJ45 female connector
Maximum distance: Total 800 m between this unit and remote microphones
Link cable:
Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
10BASE-T/100BASE-TX (selectable by automatic negotiation), RJ45 female connector
Maximum distance: 100 m between this unit and a switching hub
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector
Maximum distance: Total 800 m
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Connecting the VP-2421, RJ45 female connector
Maximum distance: 5 m
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Input 1 – 8:
No-Voltage make contact input, open voltage: 24 V DC,
short-circuit current: 2 mA or less, removable terminal block (14 pins)
Output 1 – 8: Isolated open collector output, withstand voltage: 30 V DC,
operating current: 10 mA or less, removable terminal block (14 pins)
Input 1 – 5:
No-Voltage make contact input, open voltage: 24 V DC,
short-circuit current: 2 mA or less, RJ45 female connector
Input 6:
Isolated voltage input, Inactive: –24 V ±20%, Active: +24 V ±20%,
RJ45 female connector
Status out:
Relay contact output, withstand voltage: 40 V DC,
operating current: 2 – 300 mA, RJ45 female connector
Relay contact 1 – 6, 125 V AC or 30 V DC, total under 5 A,
removable terminal block (16 pins)
Power in: Connecting the VX-2000DS only (operating range: 20 – 40 V DC)
PS out:
28 V DC / 24 A
M4 screw terminal, distance between barriers: 11 mm
24 V DC, Maximum feeding current 0.3 A
Connecting the VX-2000DS, RJ45 female connector
Maximum distance: 5 m
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
500 Ω (20 W) at 100 V line for speaker line failure
detection
Direct output from internal or external amplifier,
removable terminal block (16 pins)
140
Need help?
Do you have a question about the VM-3000 Series and is the answer not in the manual?
Questions and answers
Tengo problemas al intentar ingresar por contraseña, sigo los pasos del manual pero no me funciona
The manual does not provide specific instructions for resetting the password for the TOA VM-3000 Series. However, it mentions that password settings can be accessed in the Configuration Setting screen under "1: PASSWORD CONFIGURATION SETTING." If a password has been set, the password input screen appears before entering the settings. If further details are needed, refer to the separate software instruction manual.
This answer is automatically generated