Hitachi WJ200 Series Quick Reference Manual page 64

Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
Maximum-limit level of window
B060
comparator (O)
Minimum-limit level of window
B061
comparator (O)
Hysteresis width of window
B062
comparator (O)
Maximum-limit level of window
B063
comparator (OI)
Minimum-limit level of window
B064
comparator (OI)
Hysteresis width of window
b065
comparator (OI)
Operation level at O
b070
disconnection
Operation level at OI
b071
disconnection
Ambient temperature setting
b075
Watt-hour clearance
B078
Watt-hour display gain
b079
Start frequency
B082
Carrier frequency
B083
Initialization mode (parameters
B084
or trip history)
Country for initialization
B085
Frequency scaling conversion
B086
factor
"b" Function
Description
Set range, {Min.-limit level (b061) +
hysteresis width (b062)x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
(b060) - hysteresis width
(b062)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
(b060) - Min.-limit level (b061)}/2 %
(Maximum of 10%)
Set range, {Min.-limit level (b064 +
hysteresis width (b065)x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
(b063) - hysteresis width
(b065)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
(b063) - Min.-limit level (b064)}/2 %
(Maximum of 10%)
Set range, 0 to 100%, or "no"
(ignore)
Set range, 0 to 100%, or "no"
(ignore)
Set range is,
-10~50 °C
Two option codes:
00...OFF
01...ON (press STR then clear)
Set range is,
1.~1000.
Sets the starting frequency for the
inverter output, range is 0.10 to 9.99
Hz
Sets the PWM carrier (internal
switching frequency), range is 2.0 to
15.0 kHz
Select initialized data, five option
codes:
00...Initialization disabled
01...Clears Trip history
02...Initializes all Parameters
03...Clears Trip history and
initializes all parameters
04...Clears Trip history and
initializes all parameters and
EzSQ program
Select default parameter values for
country on initialization, two option
codes:
00...area A
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.01 to 99.99
62
Run
Mode
Lnitial data
Edit
01...area B
Defaults
Units
100.
%
0.
%
0.
%
100.
%
0.
%
0.
%
no
-
no
-
°C
40
00
-
1.
0.50
Hz
2.0
kHz
00
00
1.00