Hitachi WJ200 Series Quick Reference Manual page 52

Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Standard Functions
NOTE:. Mark " " in b031=10 shows the accessible parameters when b031 is set "10", high
level access.
Func.
Name
Code
Frequency source
A001
Frequency source,
A201
nd
2
motor
Run command source
A002
Run command source,
A202
nd
2
motor
Base frequency
A003
Base frequency,
A203
nd
2
motor
Maximum frequency
A004
Maximum frequency,
A204
nd
2
motor
[AT] selection
A005
[O] input active range start
A011
frequency
[O] input active range end
A012
frequency
[O] input active range start
A013
voltage
[O] input active range end
A014
voltage
"A" Function
Description
Eight options; select codes:
00 ...POT on ext. operator
01 ...Control terminal
02 ...Function F001 setting
03 ...ModBus network input
04 ...Option
06 ...Pulse train input
07 ...via EzSQ
10 ...Calculate function output
Five options; select codes:
01 ...Control terminal
02 ...Run key on keypad,
operator
03 ...ModBus network input
04 ...Option
Settable from 30 Hz to the
maximum frequency(A004)
Settable from 30 Hz to the 2
maximum frequency(A204)
Settable from the base
frequency to 400 Hz
Settable from the 2
frequency to 400 Hz
Three options; select codes:
00...Select between [O] and [OI]
at [AT] (ON=OI, OFF=O)
02...Select between [O] and
external POT at [AT]
(ON=POT, OFF=O)
03...Select between [OI] and
external POT at [AT]
(ON=POT, OFF=OI)
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0
The output frequency
corresponding to the analog
input range ending point,
range is 0.0 to 400.0
The starting point (offset) for the
active analog input range,
range is 0. to 100.
The ending point (offset) for the
active analog input range,
range is 0. to 100.
50
Run
Mode
Edit
or
digital
nd
nd
base
Defaults
Lnitial data
Units
02
02
02
02
60.0
Hz
60.0
Hz
60.0
Hz
60.0
Hz
00
0.00
Hz
0.00
Hz
0.
%
100.
%

Advertisement

Table of Contents
loading