Electrical Connection - Kenmore 110,84182 Use & Care Manual

240-volt compact electric dryer
Hide thumbs Also See for 110,84182:
Table of Contents

Advertisement

Available languages

Available languages

Electrical
Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
This dryer is manufactured
ready to install with a 3-wire
electrical supply connection.
The green cabinet-grounding
conductor is permanently connected to the neutral conductor
(white wire) within the dryer. If the dryer is installed with a
4-wire electrical supply connection, the green cabinet-
grounding conductor
must be removed from the external
ground conductor
screw (green screw), and secured under
the neutral terminal (center or white wire) of the terminal
block. When the green cabinet-grounding
conductor
is
secured under the neutral terminal (center or white wire) of
the terminal block, the dryer cabinet is isolated from the
neutral conductor.
If local codes do not permit the connection of a cabinet
ground conductor to the neutral wire, see "Optional 3-wire
connection"
section.
Use a 4-wire conductor
cord when the dryer is installed in a
mobile home or an area where local codes do not permit
grounding through the neutral.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL listed 30 amp power supply cord, rated
120/240-volt
minimum. The cord should be type SRD or
SRDT and be at least 4 ft (1.22 m) long. The wires that
connect to the dryer must end in ring terminals or spade
terminals with upturned ends.
A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle
(14-30R)
Then choose a 4-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 4-wire power supply
cord, at least 4 ft (1.22 m) long, must have 4, 10-gauge copper
wires and match a 4-wire receptacle of NEMA Type
14-30R. The ground wire (ground conductor) may be either green
or bare. The neutral conductor
must be identified by a white
cover.
If your outlet looks like this:
3-wire receptacle
(10-30R)
Then choose a 3-wire power supply cord with ring or spade
terminals and UL listed strain relief. The 3-wire power supply
cord, at least 4 ft (1.22 m) long, must have 3, 10-gauge copper
wires and match a 3-wire receptacle of NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic
sheathed copper cable
(with ground wire), protected with flexible metallic conduit. All
current-carrying
wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
At least 5 ft (1.52 m) long.
GROUNDING
INSTRUCTIONS
m For a grounded, cord-connected
dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The piug must be plugged
into an appropriate outlet that is properly installed and
grounded in accordance with aiI local codes and ordinances.
i For a permanently connected dryer:
This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding
conductor must be run with the circuit conductors and
connected to the equipment-grounding
terminal or lead on
the dryer.
WARNING-"
Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug on the power
supply cord: if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.