Kenmore 229.960330 Owner's Manual page 6

Continuous pilot/electronic intermittent ignition gas-fired cast iron steam boiler
Table of Contents

Advertisement

Provision for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustionand
Ventilation, of the National Fuel Gas Code, ANSI Z223.1-1atest revision, or applicable provisions of the local building codes.
WARNING
Be sure to provide enough fresh air for combustion.
Enoughair insuresproper combustionand assures that
no hazardwilldevelopdue to the lackof oxygen.
You must provide for enough fresh air to assure proper
combustion. The fire in the boiler uses oxygen. It must have
a continuous supply. The air in a house contains only enough
oxygen to supply the burner for a short time. Outside air
must enter the house to replace that used by the burner.
Study following examples 1 and 2 to determine your fresh
air requirements,
EXAMPLE 1: Boiler Located in Unconfined Space
If your boiler is in an open area (unpartitioned
basement)
in a conventional house, the air that leaks through the cracks
around doors and windows will usually be adequate to provide
air for combustion. The doors should not fit tightly. Do not
caulk the cracks around the windows,
An unconfined space is defined as a space whose volume
is not less than 50 cubic feet per 1,000 Btu per hour of
the total input rating of all appliances installed in that space.
EXAMPLE 2: Boiler Located in Confined Space
A. All Air from Inside the Building: The confined space
shall
be provided
with two permanent
openings
communicating
directly
with an additional
room(s) of
sufficient volume sothat the combined volume of all spaces
meets the criteria for an unconfined space. The total input
of all gas utilization equipment installed in the combined
space shall be considered
in making this determination.
Each opening shall have a minimum free area of one
square inch per 1,000 Btu per hour of the total input rating
of all gas utilization equipment in the confined space, but
not less than 100 square inches. One opening shall be
within 12 inches of the top and one within 12 inches of
the bottom of the enclosure,
B, All Air from
Outdoors:
The confined space shall be
provided with two permanent openings, one commencing
within 12 inches of the top and one commencing
within
12 inches of the bottom of the enclosure. The openings
shall communicate directly, or by ducts, with the outdoors
or spaces (crawl or attic) that freely communicate
with
the outdoors.
1. When directly communicating
with the outdoors, each
opening shall have a minimum free area of one square
inch per 4,000 Btu per hour of total input rating of alt
equipment in the enclosure.
NOTE
If you use a fireplace or a kitchen or bathroom exhaust
fan, you should install an outside air intake. These devices
will rob the boiler and water heater of combustion air.
2. When communicating with the outdoorsthrough
vertical
ducts, each opening shall have a minimum free area
of one square inch per 4,000 Btu per hour of total
input rating of all equipment in the enclosure.
3. When
communicating
with the
outdoors
through
horizontal ducts, each opening shall have a minimum
free area of one square inch per 2,000 Btu per hour
of total input rating of all equipment in the enclosure.
4. When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular
air ducts shall be not less than three inches.
Fresh Air Duct Capacities for Ducts Supplying Fresh Air to
boiler in tightly constructed houses. British Thermal Units per
hour Input (Btuh)*.
Fresh Air
1/,- Mesh
Wood
Metal
Duct
Screen
Louvers
Louvers
Size
Btuh
Btuh
Btuh
3' x 12'
144,000
36,000
108,000
8" x
8'
256,000
64,000
192,000
8' x 12"
384,000
96,000
288,000
8V2' x 16'
512,000
128,000
384,000
*Based
on opening covered by
V4" meshscreen,wood Iouvers, o r metallouvers.
FRESH
AIR
DUCT
FOR
TIGHTLY
SEALED
HOUSE
FRESH
AIR
DUCT
,_,*
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents