Hitachi L300P Series Quick Reference Manual page 25

Three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

"B" Group: Fine-tuning Functions
Func.
Code
B001
Selection of automatic restart mode
• 00 Alarm output after trip, automatic restart
disabled
• 01 Restart at 0Hz
• 02 Resume operation after frequency
matching
• 03 Resume previous freq. after freq. matching,
then decelerate to stop and display trip info
B002
Allowable under-voltage power failure time
B003
Retry wait time before motor restart
B004
Instantaneous power failure / under-voltage trip
alarm enable
• 00 Disable
• 02 Disable during stop and ramp to stop
B005
Number of restarts on power failure / under-
voltage trip events
• 00 Restart 16 times • 01 Always restart
B006
Phase loss detection enable
• 00 Disable – no trip on phase loss
• 01 Enable – trip on phase loss
B007
Restart frequency threshold
B012/
Level of electronic thermal setting
B212
B013/
Electronic thermal characteristic
B213
• 00 Reduced torque • 01 Const. torque
• 02 V/f free-setting
B015
Free setting, electronic thermal freq. (1)
B016
Free setting, electronic thermal current (1)
B017
Free setting, electronic thermal freq. (2)
B018
Free setting, electronic thermal current (2)
B019
Free setting, electronic thermal freq. (3)
B020
Free setting, electronic thermal current (3)
B021
Overload restriction operation mode
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
Name / Description
• 01 Enable
23
Default
Value
Set
–FE2/–FU2/
Value
–FR
00
1.0
1.0
00
00
0.00
1.0
Rated
current of
each inverter
01 / 00 / 00
0.
0.0
0.
0.0
0.
0.0
01