Motorola V186 - Cell Phone - GSM System Planner Manual page 38

Remote terminal unit (rtu)
Hide thumbs Also See for V186 - Cell Phone - GSM:
Table of Contents

Advertisement

AI Module Value Representation:
In ± 20 mA current inputs
In 4 - 20 mA current inputs
In ± 5 V current inputs
In 0 - 5 V current inputs
In 1 - 5 V current inputs
Decimal Value
Input Current
< -32256
< -20.16 mA
-32000
0
32000
> 32256
> +20.16 mA
Decimal Value
Input Current
< 6144
< 3.84 mA
6400
0
32000
> 32256
> +20.16 mA
Decimal Value
Input Voltage
< -32256
-32000
0
32000
> 32256
> +5.04 V
Decimal Value
Input Voltage
< -256
0
32000
> 32256
> +5.04 V
Decimal Value
Input Voltage
< 6144
6400
32000
> 32256
34
Analog Input Modules
Indication
Underflow LED ON
-20 mA
Rated range (no LED
0 mA
active)
+20 mA
Overflow LED ON
Indication
Underflow LED ON
+4 mA
Rated range (no LED
0 mA
active)
+20 mA
Overflow LED ON
Indication
<-5.04V
Underflow LED ON
-5 V
Rated range (no LED
0 V
active)
+5 V
Overflow LED ON
Indication
< -0.04 V
Underflow LED ON
0 V
Rated range (no LED
active)
+5 V
Overflow LED ON
Indication
< 0.96 V
Underflow LED ON
1 V
Rated range (no LED
active)
+5 V
> 5.04 V
Overflow LED ON