AC Power Supply Modules
Input voltage
Total Power
Outputs
Battery Charger
Diagnostic LEDs
No Load Power
Consumption
Efficiency
Inrush Current
Power Factor
Protection
Output Protection
Insulation
Dimensions
Weight
Specifications subject to change without notice.
100-240 V AC, 50/60 Hz
100-240 V AC, 50/60 Hz with 12V smart battery charger
Maximum 60 W continuous; maximum 105 W peak @ 25% duty cycle
Motherboard connector (to CPU and I/O modules): 13.2 V DC ±20%,
max. 4 A
AUX1A/AUX1B: 13.2 V DC ±20%, max. 8 A, on/off controlled by user
program
AUX2A/AUX2B (configurable): equal to input voltage (default), max. 8
A,
or 3.3 (default), 5, 7.5, 9 V DC ±10%, max. 2.5A, on/off (default)
controlled by user program
Note: max. 8 A total current consumption from all outputs
12 V Lead Acid battery charger (in PS with charger)
Automatic charging of 6.5 or 10 Ah backup battery, battery temperature
sensing, overcharging protection, battery capacity test and diagnostics,
automatic battery switch-over
Status LED for: input voltage, AUX1 and AUX2 outputs, 12V Control for
DO modules, and battery
130 mA @ 220 V AC
80% typical @230 V AC, 76% typical @115 V AC (full load)
25 A maximum, for 2 mSec. Max, cold start at 25°C
0.98 typical at 230 V AC, 0.99 typical at 115 V AC
Internal line fuse, replaceable
AUX2A/B short circuit, automatic recovery on 3.3, 5, 7.5, 9 V
Input to case: 1500 V AC, input to output: 3000 V AC
56 mm W x 225 mm H x 180 mm D (2.2" W x 8.7" H x 7.1" D)
Approx. 1kg (2.2 lb)
Appendix A – ACE3600 Specifications
154