Page 17
(continued) CONDUIT (if used) MAIN PANEL DISCONNECT SUB-PANEL INVERTER/CHARGER DC CONDUIT (if used) AC CONDUIT FROM MAIN PANEL AC CONDUIT TO SUB-PANEL BATTERIES VENT (outlet) BATTERY ENCLOSURE (if used) VENT (inlet) 975-0012-001 ALTERNATE DC ENERGY SOURCES SOLAR WIND AC CONDUIT MANUAL AC N.C.
Page 19
(continued) Wall studs 16 inches on center Ceiling 7–5/8" c-c 2 x 4 mounting supports Approximately 4–5 ft Wallboard Floor 975-0012-003...
Page 20
0.281 DIA 10 PLACES 0.375 DIA 4 PLACES TERMINAL AC SIDE DC SIDE – TERMINAL 1.00 inches 7.00 inches 7.00 inches 2.54 cm 0.365 inches 17.8 cm 17.8 cm 0.93 cm 8.00 inches 20.32 cm 14.00 inches 1.90 inches 35.56 cm 4.83 cm 16.00 inches 40.64 cm...
Inverter Typical 1 to 3 Feet (one-way) 3 to 5 Feet (one-way) 5 to 10 Feet (one-way) Model Amperage DR1512 150 A #2/0 AWG (67.4 mm #2/0 AWG (67.4 mm #4/0 AWG (107 mm DR2412 240 A #4/0 AWG (107 mm #4/0 AWG (107 mm NOT RECOMMENDED DR1524...
Page 22
(continued) Cable Size Rating in Maximum Rating in "Free Maximum Fuse Required Conduit Breaker Size Air" Size #2 AWG 115 amps max 170 amps max TFB200 #2/0 AWG 175 amps max DC175 265 amps max TFB300 #4/0 AWG 250 amps max DC250 360 amps max TFB400...
Page 23
(continued) Do not place anything between battery cable lug and terminal surface. Assemble exactly as shown. 2/0 Copper Compression Lug 2/0 Aluminum Mechanical Lug...
Page 25
(continued) 12 V INVERTER 24 V INVERTER (Total battery capacity = 100 Ah) (Total battery capacity = 100 Ah) 3597-F00-D21 3597-F00-D22 48 V INVERTER (Total battery capacity = 100 Ah) 3597-F00-D23 12 V 12 V 12 V 12 V 12 V 12 V 24 V INVERTER 48 V INVERTER...
Page 26
(continued) – 12 V INVERTER (Total battery capacity = 200 Ah) 3597-F00-D26 – – – – 12 V 12 V 12 V 12 V – – – – 12 V 12 V 12 V 12 V 3597-F00-D27...
Page 27
(continued) – – – – 12 V 12 V 12 V 12 V – – – – 12 V 12 V 12 V 12 V 3597-F00-D28 – – – – 12 V 12 V 12 V 12 V – – –...
(continued) UTILITY FEED FROM METER LINE EXISTING HOUSE WIRING NEUTRAL LINE OUT 120 VAC BACKUP POWER NEUTRAL TO LOAD GROUND MAIN PANEL 120 VAC 120 VAC MAIN BREAKER INVERTER/CHARGER FROM UTILITY GROUND 120 VAC LINE IN NEUTRAL LINE OUT 120 VAC INVERTER OUT NEUTRAL 120 VAC FROM INVERTER...
Page 41
(continued) Utility Power 120 VAC NEUTRAL Bonded Neutral/ Ground Bus Main Utility NEUTRAL Circuit Breaker Bond Wire Inverter Circuit Breaker Utility Service Panel COMMOMN UTILITY HOT CONTACT Manual Transfer House CONTACT (to inverter) Ground Switch GENERATOR HOT CONTACT NEUTRAL Isolated Neutral Bus Manual Start...
Page 42
MAIN PANEL HOT L1 HOT L2 BOND GROUND WIRE NEUTRAL IN HOT OUT NEUTRAL OUT NEUTRAL IN HOT IN NEUTRAL OUT COM PORT GROUND GROUND INVERTER 1 (L1) SERIES STACKING CABLE (DRI) HOT OUT NEUTRAL OUT NEUTRAL IN HOT IN COM PORT GROUND NEUTRAL OUT...
Troubleshooting Error Condition Possible Cause Solution Battery HIGH LED (red) is ON, The battery voltage is above the Use a DVM and measure the voltage at the buzzer is ON. high battery voltage input tolerance. inverter’s DC input terminals. Ensure the DC source is regulated below the High Battery Cutout voltage.
Troubleshooting Error Condition Possible Cause Solution No AC output and no warning Battery voltage at the inverter Check the battery voltage, fuses or breakers, LEDs are ON. terminals is too high or low. and cable connections. AC output is low and the inverter Low battery.
Page 74
Load Center 240 VAC from Grid Neutral Ground 25 A 25 A Breaker Breaker 25 A Black–Hot 25 A Black–Hot 120 VAC 120 VAC White–Neutral 25 A White–Neutral 25 A Bare–Ground Bare–Ground 062949-001 Load Center Load Center 240 VAC 240 VAC from Grid from Grid Neutral...
Page 75
(continued) Load Center 120 VAC Inverter (or generator) Neutral 25 A 25 A Ground Breaker Breaker (Ganged) (Ganged) 25 A Red–Hot 25 A Black–Hot 120 VAC 120 VAC 50 A Single White–Neutral The in-phase currents Bare–Ground Bare–Ground add at this point Splice exceeding wire capacity!
Page 76
(continued) 120 VAC Inverter (or generator) Load Center Auto- Neutral transformer 25 A 25 A Ground Breaker Breaker Hot-L2 (Ganged) (Ganged) Hot–L1 25 A Red–Hot White–Neutral 25 A Black–Hot 120 VAC 120 VAC Single White–Neutral The out-of-phase Bare–Ground Bare–Ground currents subtract at this Splice point 25 A White–Neutral...