Installation Instructions
10X Line
Electrified Bored Lock
1
Installation Notes
•
Doors manufactured by ASSA ABLOY Group Companies are available pre-wired with ElectroLynx® connectors.
•
Wire colors are consistent with all ASSA ABLOY products.
•
Doors without ElectroLynx connectors will have to be hard wired.
•
For Non ElectroLynx Connector System Door:
»
Install available Retrofit Harness and use with ElectroLynx Hinge.
»
Follow installation instructions for ElectroLynx Connector System.
•
For Non ElectroLynx Connector System Door and Hinge:
»
Remove connector on lock.
»
Use proper crimp splices or wire nuts in accordance with local code for terminating connections.
»
Lock is polarity sensitive.
•
The system shall not be installed in fail secure mode unless permitted by the local authority having jurisdiction
and shall not interfere with the operation of Listed panic hardware.
•
Power shall be by UL294 and ULC-60839 Class 2 Power Limited power supplies or Listed Access Control units.
•
ULC-60839-11-1 - Grade 1 and Environmental class: indoor only.
•
UL294 access control performance levels (Endurance Level IV, Line Security Level I, Attack Level I, Power Stand-
by Level I).
•
Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), CSA 22.1, Canadian
Electrical Code (CEC), Part I, Safety Standard for Electrical Installations, local codes and the authorities having
jurisdiction.
2
Electrical Specifications
•
Operating voltage range: 10.2VDC to
26.4VDC
•
Current draw: 10mA continuous.
•
Peak current draw: 500mA.
WARNING
This product can expose you to
lead which is known to the state of
California to cause cancer and birth
defects or other reproductive harm.
For more information go to www.
P65warnings.ca.gov.
1-800-727-5477 • www.sargentlock.com
Copyright © 2022-2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or in part without the express
written permission of SARGENT Manufacturing Company is prohibited. Patent pending and/or patent www.assaabloydss.com/patents.
Wire Gauge Chart
Total One-Way
Length of Wire
Run (ft)
100
150
200
250
Note: The minimum permissible wire size to be used shall not be less than 26 AWG.
When calculating voltage drop, use 0.5A as the recommended current draw.
WARNING
Attention Installer: Improper
installation may result in dam-
age to the product and void the
factory warranty.
12VDC
Load Current @ 12VDC
Load Current @ 24VDC
1/2A
1A
1/2A
18
14
16
12
14
12
14
10
A8351 03/23
24 VDC
1A
20
18
18
16
18
14
16
14