CLIVET MSAN8-Y Series Technical Bulletin

CLIVET MSAN8-Y Series Technical Bulletin

Mini vrf
Hide thumbs Also See for MSAN8-Y Series:

Advertisement

Quick Links

Mini VRF
MSAN8-Y 80M÷180T

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MSAN8-Y Series and is the answer not in the manual?

Questions and answers

Summary of Contents for CLIVET MSAN8-Y Series

  • Page 1 Mini VRF MSAN8-Y 80M÷180T...
  • Page 2 CONTENTS Part 1 General Information ................3 Part 2 Outdoor Unit Engineering Data ............10 Part 3 System Design and installation ............76...
  • Page 4 Part 1 General Information 1 Indoor and Outdoor Unit Capacities ............. 4 2 External Appearance ..................5 3 Nomenclature ....................6 4 Combination Ratio ..................8...
  • Page 5: Indoor And Outdoor Unit Capacities

    1 Indoor and Outdoor Unit Capacities 1.1 Indoor Units Table 1-1.1: Indoor unit abbreviation codes Abbreviation Abbreviation Type Type code code Q1DN One-way Cassette CNT2 Medium Static Pressure Duct Q2DN Two-way Cassette High Static Pressure Duct Q4AN Compact Four-way Cassette GWMN Wall-mounted Floor standing...
  • Page 6: External Appearance

    2 xternal Appearance 2.1 Indoor Units Table 1-2.1: Indoor unit appearance One-way Cassette Two-way Cassette Q1DN Q2DN Compact Four-way Cassette Four-way Cassette Q4AN Q4DN Slim Duct Medium Static Pressure Duct CNT3 CNT2 High Static Pressure Duct Wall-mounted GWMN Floor standing 2.2 Outdoor Units Table 1-2.2: Outdoor unit appearance 8-18KW...
  • Page 7: Nomenclature

    3 Nomenclature 3.1 Indoor Units 3.1.1 Standard indoor units Legend Code Remarks Indoor unit type Q1DN: One-way Cassette Q2DN: Two-way Cassette Q4AN: Four-way Cassette Compact Q4DN: Four-way Cassette Q1DN CNT2: Medium Static Pressure Duct CN: High Static Pressure Duct GWMN: Wall-mounted CNT3: Slim Duct DZ: Floor Standing 3rd generation indoor unit...
  • Page 8 3.2 Outdoor Units...
  • Page 9: Combination Ratio

    4 Combination Ratio Sum of capacity indexes of the indoor units Combination ratio = Capacity index of the outdoor unit Table 1-4.1: Indoor and outdoor unit combination ratio limitations Type Minimum combination ratio Maximum combination ratio V8 Mini outdoor units 160% Table 1-4.2: Combinations of Indoor and outdoor units Outdoor unit capacity...
  • Page 10 5 Selection Procedure 5.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Room(i) area Adjust the piping length, Mc≤12kg reduce the refrigerant charge Determine applicable standards...
  • Page 11 Provisionally select outdoor unit capacity based on combination ratio limitations Confirm that the number of indoor units connected to the outdoor unit is within limitation Correct cooling and heating capacities of the outdoor unit for the following items: 1. Room(i) with larger airflow Outdoor air temperature / Indoor air temperature WB / indoor units Combination ratio / Piping length, level difference / Piping...
  • Page 12 5.2 Example The following is a selection example based on total heat load for cooling. Figure 1-5.1: Room plan Room B (10m Room C(10m Room A (20m Room D(15m Step 1: Establish design conditions  Indoor air temperature 25°C DB, 18°C WB; outdoor air temperature 33°C DB. ...
  • Page 13 V8 Mini VRF 50Hz Step 2: Select indoor units  In this example, a safety factor is not used (i.e. the safety factor is 1).  Select indoor unit models using the medium static pressure duct cooling capacity table. Each indoor unit's corrected capacity needs to be greater than or equal to the peak load of the relevant room.
  • Page 14 Table 1-5.5: Combinations of Indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of connected indoor units Capacity index (standard indoor units only) 40 to 115.2 45 to 144 12.3 61.5 to 196.8 14.0 70 to 224 15.5 77.5 to 248 17.5 87.5 to 280...
  • Page 15 that the outdoor unit is below the indoor unit. Calculate the corrected capacity of MSAN8-Y 160M (“C”) by using K1: C = B × K1 = 16.75 × 0.927 =15.53kW  The corrected capacity 15.53 kW is lower than required total heat load 16.5kW, so selection is complete. (In the event that the corrected capacity is lower than the required total heat load, Step 3 should be repeated from the point where the outdoor unit capacity is provisionally selected.) Step 4: R32 refrigerant solution recommendation...
  • Page 16: Table Of Contents

    Part 2 Outdoor Unit Engineering Data 1 Specifications ....................11 2 Dimensions....................13 3 Installation Space Requirements ..............14 4 Piping Diagrams ..................15 5 Wiring Diagrams ..................18 6 Electrical Characteristics ................19 7 Functional Components and Safety Devices ..........20 8 Capacity Tables ...................
  • Page 17 1 Specifications Table 2-1.1: 80M/100M/120M model specifications Sale Model MSAN8-Y 80M MSAN8-Y 100M MSAN8-Y 120M Power supply 220-240V~ 50Hz Capacity 12.3 Input 1.95 2.77 3.73 Cooling 3.70 3.25 3.30 3.70 3.25 3.30 Capacity 1.80 2.31 2.86 Input Heating 4.00 3.90 4.30 4.00 3.90...
  • Page 18 Table 2-1.2: 140M/160M/180M model specifications Sale Model MSAN8-Y 140M MSAN8-Y 160M MSAN8-Y 180M Power supply 220-240V~ 50Hz Capacity 14.0 15.5 17.5 Power Input 4.67 5.34 6.46 Cooling 3.00 2.90 2.71 3.23 3.28 3.25 Capacity 14.0 15.5 17.5 Power Input 3.29 3.73 4.49 Heating...
  • Page 19 Table 2-1.3: 120T/140T/160T/180T model specifications Sale Model MSAN8-Y 120T MSAN8-Y 140T MSAN8-Y 160T MSAN8-Y 180T Power supply 380-415V, 3N~, 50Hz Capacity 12.3 14.0 15.5 17.5 Power Input 3.37 4.67 5.34 6.46 Cooling 3.30 3.00 2.90 2.71 3.30 3.23 3.28 3.25 Capacity 12.3 14.0...
  • Page 20: Dimensions

    2 Dimensions Figure 2-2.1: Front view dimensions (unit: mm) Figure 2-2.:Top view dimensions (unit: mm)
  • Page 21: Installation Space Requirements

    3 Installation Space Requirements Figure 2-3.1: Single unit installation (unit: mm) Figure 2-3.3: Multiple unit installation top view (unit: mm) > 300 > 600 > 200 0 Figure 2-3.4: Multiple unit installation side view (unit: mm)
  • Page 22: Piping Diagrams

    4 Piping Diagrams Figure 2-4.1: 80/100 Single phase piping diagram Legend Parts name Parts name Compressor Electronic expansion valve (EEVC) Oil separator Low pressure sensor High pressure switch Gas-liquid separator High pressure sensor Sensor Code Description Check value Heat exchanger deicer temperature sensor Four-way valve Outdoor air temperature sensor Liquid pipe temperature sensor...
  • Page 23 Figure 2-4.1: 120/140/160/180 Single / Tripahse piping diagram Only for single phase Legend Parts name Parts name Compressor Electronic expansion valve (EEVC) Oil separator Low pressure sensor High pressure switch Gas-liquid separator High pressure sensor Sensor Code Description Check value Heat exchanger deicer temperature sensor Four-way valve Outdoor air temperature sensor...
  • Page 24 Key components: 1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Gas-liquid separator: Separates liquid refrigerant from gas refrigerant, stores liquid refrigerant and oil to protect compressor from liquid hammering.
  • Page 25: Wiring Diagrams

    5 Wiring Diagrams - 220-240V~50Hz...
  • Page 26 5 Wiring Diagrams - 380-415V 3N~50Hz...
  • Page 27: Electrical Characteristics

    6 Electrical Characteristics Table 2-6.1: Outdoor unit electrical characteristics Power Supply Compressor Model Min. Max. Volts TOCA volts volts MSAN8-Y 80M 50Hz 220-240 21.3 15.9 MSAN8-Y 100M 50Hz 220-240 17.9 MSAN8-Y 120M 50Hz 220-240 24.8 MSAN8-Y 140M 50Hz 220-240 26.8 MSAN8-Y 160M 50Hz 220-240...
  • Page 28: Functional Components And Safety Devices

    7 Functional Components and Safety Devices Table 2-7.1: 80/100/120/140/160/180 model functional components and safety devices Item Discharge pipe temperature sensors 90°C = 5kΩ ± 3% Compressor Crankcase heater Inverter module Inverter module temperature sensor 90°C = 5kΩ ± 5% 100°C Fan motor Safety thermostat 80°C...
  • Page 29: Capacity Tables

    8 Capacity Tables 8.1 Cooling Capacity Tables Table2-8.1:MSAN8-Y 80M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.79 0.87 1.02 1.10 10.1 1.17 11.5 1.37 13.0 1.59 0.82 0.88 1.02 1.10 10.1 1.18...
  • Page 30 Table2-8.3:MSAN8-Y 80M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.68 0.73 0.85 0.92 0.98 1.11 11.0 1.27 0.68 0.75 0.85 0.92 0.98 1.11 11.0 1.27 0.71 0.75 0.86 0.92 0.98 1.12 11.0...
  • Page 31 Table2-8.5:MSAN8-Y 80M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.55 0.60 0.69 0.74 0.79 0.90 1.01 0.59 0.61 0.69 0.75 0.80 0.90 1.03 0.59 0.62 0.70 0.76 0.81 0.90 1.04 0.59 0.63...
  • Page 32 Table2-8.7:MSAN8-Y 80M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.48 0.50 0.55 0.57 0.61 0.69 0.77 0.50 0.51 0.56 0.58 0.61 0.69 0.78 0.50 0.52 0.56 0.59 0.62 0.69 0.78 0.50 0.52...
  • Page 33 Table2-8.9:MSAN8-Y 80M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.42 0.44 0.46 0.47 0.49 0.52 0.54 0.42 0.44 0.47 0.48 0.49 0.52 0.55 0.44 0.44 0.47 0.49 0.50 0.53 0.55 0.44 0.46...
  • Page 34 Table2-8.10:MSAN8-Y 100M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 1.00 1.09 10.8 1.31 11.7 1.44 12.6 1.69 14.4 1.95 14.9 2.14 1.06 1.15 10.8 1.32 11.7 1.54 12.6 1.70 14.4 2.02 14.9...
  • Page 35 Table2-8.12:MSAN8-Y 100M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.83 0.91 1.06 1.15 10.7 1.25 12.2 1.45 13.7 1.88 0.87 0.95 1.13 1.22 10.7 1.29 12.2 1.55 13.7 1.97 0.89 0.97 1.15...
  • Page 36 Table2-8.14:MSAN8-Y 100M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.69 0.75 0.87 0.92 1.00 10.0 1.12 11.2 1.29 0.70 0.76 0.88 0.94 1.02 10.0 1.19 11.2 1.33 0.73 0.79 0.91 0.99 1.09...
  • Page 37 Table2-8.16:MSAN8-Y 100M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.54 0.57 0.67 0.70 0.75 0.85 0.96 0.54 0.60 0.68 0.72 0.78 0.87 1.00 0.58 0.62 0.71 0.76 0.82 0.88 1.01 0.60 0.63...
  • Page 38 Table2-8.18:MSAN8-Y 100Mcooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.44 0.46 0.49 0.51 0.53 0.59 0.66 0.44 0.46 0.50 0.52 0.56 0.62 0.68 0.45 0.47 0.52 0.55 0.56 0.63 0.70 0.45 0.47 0.53...
  • Page 39 Table2-8.19:MSAN8-Y 120M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 11.1 1.07 12.3 1.22 14.8 1.52 16.0 1.86 17.2 2.22 19.7 2.71 21.2 3.36 11.1 1.09 12.3 1.23 14.8 1.64 16.0 1.98 17.2...
  • Page 40 Table2-8.21:MSAN8-Y 120M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.88 10.4 0.99 12.5 1.24 13.5 1.36 14.6 1.49 16.7 2.08 18.7 2.61 0.89 10.4 1.02 12.5 1.25 13.5 1.37 14.6 1.52 16.7...
  • Page 41 Table2-8.23:MSAN8-Y 120M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.70 0.78 10.2 0.96 11.1 1.07 11.9 1.16 13.6 1.36 15.3 1.57 0.71 0.80 10.2 0.97 11.1 1.08 11.9 1.18 13.6 1.37 15.3...
  • Page 42 Table2-8.25:MSAN8-Y 120M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.54 0.60 0.73 0.80 0.86 10.6 1.00 11.9 1.16 0.55 0.61 0.73 0.81 0.86 10.6 1.02 11.9 1.18 0.55 0.62 0.75 0.82 0.88...
  • Page 43 Table2-8.27:MSAN8-Y 120M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.39 0.42 0.51 0.55 0.59 0.70 0.78 0.39 0.43 0.51 0.56 0.61 0.70 0.79 0.39 0.44 0.52 0.56 0.61 0.71 0.79 0.40 0.44...
  • Page 44 Table2-8.28:MSAN8-Y 140M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 12.6 1.25 14.0 1.41 16.8 2.19 18.2 2.56 19.6 2.93 21.8 3.73 22.4 3.51 12.6 1.25 14.0 1.46 16.8 2.39 18.2 2.62 19.6...
  • Page 45 Table2-8.30:MSAN8-Y 140M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 10.7 1.01 11.8 1.15 14.2 1.43 15.4 1.71 16.6 2.18 19.0 2.58 21.3 3.59 10.7 1.03 11.8 1.16 14.2 1.51 15.4 1.99 16.6...
  • Page 46 Table2-8.32:MSAN8-Y 140Mcooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.79 0.89 11.6 1.12 12.6 1.23 13.6 1.34 15.5 1.69 17.4 2.44 0.80 0.90 11.6 1.13 12.6 1.24 13.6 1.36 15.5 1.98 17.4 2.46...
  • Page 47 Table2-8.34:MSAN8-Y 140M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.60 0.68 0.81 0.89 10.6 0.98 12.1 1.15 13.6 1.32 0.62 0.68 0.83 0.90 10.6 0.99 12.1 1.16 13.6 1.34 0.62 0.69 0.83...
  • Page 48 Table2-8.36:MSAN8-Y 140M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.42 0.47 0.56 0.61 0.67 0.77 0.87 0.43 0.47 0.58 0.62 0.68 0.77 0.90 0.44 0.48 0.58 0.63 0.68 0.78 0.91 0.44 0.49...
  • Page 49 Table2-8.37:MSAN8-Y 160M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 13.9 1.33 15.5 1.75 18.6 2.47 20.1 2.94 21.7 3.31 23.9 3.81 24.4 3.87 13.9 1.42 15.5 1.92 18.6 2.58 20.1 2.98 21.7...
  • Page 50 Table2-8.39:MSAN8-Y 160M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 11.8 1.08 13.1 1.22 15.7 1.81 17.0 2.19 18.4 2.43 21.0 3.08 23.0 4.00 11.8 1.09 13.1 1.24 15.7 1.93 17.0 2.23 18.4...
  • Page 51 Table2-8.41:MSAN8-Y 160M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.83 10.7 0.95 12.9 1.18 13.9 1.31 15.0 1.48 17.2 2.20 19.3 2.81 0.86 10.7 0.98 12.9 1.20 13.9 1.36 15.0 1.78 17.2...
  • Page 52 Table2-8.43:MSAN8-Y 160M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.63 0.70 10.0 0.86 10.9 0.95 11.7 1.05 13.4 1.23 15.0 1.58 0.65 0.70 10.0 0.88 10.9 0.97 11.7 1.06 13.4 1.25 15.0...
  • Page 53 Table2-8.45:MSAN8-Y 160M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.44 0.49 0.59 0.64 0.70 0.80 10.7 0.93 0.45 0.50 0.59 0.65 0.70 0.81 10.7 0.95 0.45 0.50 0.61 0.65 0.71 0.82 10.7...
  • Page 54 Table2-8.46:MSAN8-Y 180M cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 15.8 1.92 17.5 2.27 21.0 3.16 22.8 3.61 24.5 4.07 25.6 4.41 26.2 4.18 15.8 1.97 17.5 2.37 21.0 3.19 22.8 3.71 24.5...
  • Page 55 Table2-8.48:MSAN8-Y 180M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 13.3 1.26 14.8 1.47 17.8 2.31 19.3 2.66 20.7 3.02 23.7 3.84 24.7 4.29 13.3 1.27 14.8 1.77 17.8 2.42 19.3 2.71 20.7...
  • Page 56 Table2-8.50:MSAN8-Y 180M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 10.9 0.97 12.1 1.10 14.5 1.38 15.8 1.80 17.0 2.14 19.4 2.64 21.8 3.51 10.9 1.00 12.1 1.12 14.5 1.60 15.8 1.91 17.0...
  • Page 57 Table2-8.52:MSAN8-Y 180M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.72 0.81 11.3 1.00 12.3 1.11 13.2 1.23 15.1 1.47 17.0 2.23 0.73 0.81 11.3 1.02 12.3 1.12 13.2 1.23 15.1 1.78 17.0...
  • Page 58 Table2-8.54:MSAN8-Y 180M cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.50 0.56 0.68 0.73 0.79 10.8 0.94 12.1 1.09 0.51 0.56 0.68 0.74 0.80 10.8 0.95 12.1 1.10 0.51 0.57 0.69 0.75 0.82...
  • Page 59 8.2 Heating Capacity Tables Table 2-7.6: MSAN8-Y 80M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 2.66 2.77 2.86 2.91 2.96 3.04 -18.8 -19.0 2.71 2.81 2.91 2.96 3.00...
  • Page 60 Table 2-7.6: MSAN8-Y 80M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 2.72 2.81 2.90 2.94 2.98 3.06 -18.8 -19.0 2.77 2.86 2.95 2.99 3.03 3.12 -16.7 -17.0...
  • Page 61 Table 2-7.6: MSAN8-Y 80M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 2.86 2.95 3.02 3.06 3.14 2.88 -18.8 -19.0 2.92 3.00 3.08 3.15 3.02 2.78 -16.7 -17.0...
  • Page 62 Table 2-7.7: MSAN8-Y 100M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 2.95 3.07 3.18 3.24 3.29 3.39 -18.8 -19.0 3.00 3.12 3.23 3.29 3.34 3.44 -16.7 -17.0 3.10...
  • Page 63 Table 2-7.6: MSAN8-Y 100M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 2.97 3.08 3.18 3.23 3.28 3.38 -18.8 -19.0 3.03 3.14 3.24 3.29 3.34 3.43 -16.7 -17.0...
  • Page 64 Table 2-7.6: MSAN8-Y 100M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 3.11 3.20 3.29 3.34 3.38 3.47 -18.8 -19.0 3.17 3.26 3.36 3.40 3.45 3.47 -16.7 -17.0...
  • Page 65 Table 2-7.7: MSAN8-Y 120M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.5 4.41 10.4 4.44 10.3 4.49 10.3 4.52 10.3 4.56 10.3 4.65 -18.8 -19.0 10.8 4.42 10.7...
  • Page 66 Table 2-7.6: MSAN8-Y 120M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.2 4.47 10.2 4.53 10.2 4.61 10.2 4.66 10.2 4.71 10.2 4.83 -18.8 -19.0 10.6 4.50...
  • Page 67 Table 2-7.6: MSAN8-Y 120M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.1 4.71 10.1 4.83 4.71 4.54 4.37 4.03 -18.8 -19.0 10.4 4.77 10.6 4.95 4.60 4.43...
  • Page 68 Table 2-7.7: MSAN8-Y 140M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.8 4.29 10.7 4.33 10.6 4.39 10.6 4.42 10.6 4.46 10.5 4.54 -18.8 -19.0 11.2 4.31 11.1...
  • Page 69 Table 2-7.6: MSAN8-Y 140M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.5 4.36 10.5 4.42 10.4 4.50 10.4 4.54 10.4 4.59 10.4 4.70 -18.8 -19.0 10.9 4.39...
  • Page 70 Table 2-7.6: MSAN8-Y 140M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.2 4.57 10.2 4.67 10.3 4.79 10.3 4.86 10.3 4.87 4.48 -18.8 -19.0 10.6 4.63 10.6...
  • Page 71 Table 2-7.7: MSAN8-Y 160M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.4 4.38 11.3 4.45 11.2 4.53 11.1 4.58 11.1 4.62 11.0 4.73 -18.8 -19.0 11.8 4.42 11.7...
  • Page 72 Table 2-7.6: MSAN8-Y 160M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.1 4.49 11.0 4.57 10.9 4.67 10.8 4.72 10.8 4.77 10.7 4.89 -18.8 -19.0 11.4 4.54...
  • Page 73 Table 2-7.6: MSAN8-Y 160M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.7 4.74 10.6 4.85 10.5 4.97 10.5 5.03 10.5 5.10 10.4 4.93 -18.8 -19.0 11.0 4.81...
  • Page 74 Table 2-7.7: MSAN8-Y 180M heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 12.4 4.66 12.2 4.76 12.1 4.87 12.0 4.92 11.9 4.98 11.8 5.11 -18.8 -19.0 12.8 4.72 12.6...
  • Page 75 Table 2-7.6: MSAN8-Y 180M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.9 4.80 11.7 4.91 11.6 5.03 11.5 5.09 11.4 5.15 11.3 5.28 -18.8 -19.0 12.2 4.87...
  • Page 76 Table 2-7.6: MSAN8-Y 180M heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.3 5.09 11.1 5.21 11.0 5.34 11.0 5.41 11.0 5.48 10.9 5.62 -18.8 -19.0 11.6 5.18...
  • Page 77 8 Capacity Tables 8.1 Cooling Capacity Tables Table2-8.1:MSAN8-Y 120T Indoor air temp. (°C DB/WD) cooling capacity Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 11.1 1.07 12.3 1.22 14.8 1.52 16.0 1.86 17.2 2.22 19.7 2.71 21.2 3.36 11.1 1.09...
  • Page 78 TC: Total capacity (kW) PI: Power input (compressor + outdoor fan motor) (kW) Notes: Shaded cells indicate rating condition. Table continued on next page … Table2-8.21:MSAN8-Y 120T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp.
  • Page 79 V8 Mini Series VRF 50Hz PI: Power input (compressor + outdoor fan motor) (kW) Notes: Shaded cells indicate rating condition. Table continued on next page … Table2-8.23:MSAN8-Y 120T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24...
  • Page 80 V8 Mini Series VRF 50Hz Notes: Shaded cells indicate rating condition. Table continued on next page … Table2-8.25:MSAN8-Y 120T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.54 0.60 0.73 0.80 0.86 10.6...
  • Page 81 V8 Mini Series VRF 50Hz Shaded cells indicate rating condition. Table continued on next page … Table2-8.27:MSAN8-Y 120T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.39 0.42 0.51 0.55 0.59 0.70 0.78...
  • Page 82 Table2-8.28:MSAN8-Y 140T cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 12.6 1.25 14.0 1.41 16.8 2.19 18.2 2.56 19.6 2.93 21.8 3.73 22.4 3.51 12.6 1.25 14.0 1.46 16.8 2.39 18.2 2.62 19.6...
  • Page 83 V8 Mini Series VRF 50Hz Table2-8.30:MSAN8-Y 140T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 10.7 1.01 11.8 1.15 14.2 1.43 15.4 1.71 16.6 2.18 19.0 2.58 21.3 3.59 10.7 1.03 11.8 1.16...
  • Page 84 V8 Mini Series VRF 50Hz Table2-8.32:MSAN8-Y 14T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.79 0.89 11.6 1.12 12.6 1.23 13.6 1.34 15.5 1.69 17.4 2.44 0.80 0.90 11.6 1.13 12.6 1.24...
  • Page 85 V8 Mini Series VRF 50Hz Table2-8.34:MSAN8-Y 140T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.60 0.68 0.81 0.89 10.6 0.98 12.1 1.15 13.6 1.32 0.62 0.68 0.83 0.90 10.6 0.99 12.1 1.16...
  • Page 86 Table2-8.36:MSAN8-Y 140T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.42 0.47 0.56 0.61 0.67 0.77 0.87 0.43 0.47 0.58 0.62 0.68 0.77 0.90 0.44 0.48 0.58 0.63 0.68 0.78 0.91 0.44 0.49...
  • Page 87 V8 Mini Series VRF 50Hz Table2-8.37:MSAN8-Y 160T cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 13.9 1.33 15.5 1.75 18.6 2.47 20.1 2.94 21.7 3.31 23.9 3.81 24.4 3.87 13.9 1.42 15.5 1.92...
  • Page 88 Table2-8.39:MSAN8-Y 160T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 11.8 1.08 13.1 1.22 15.7 1.81 17.0 2.19 18.4 2.43 21.0 3.08 23.0 4.00 11.8 1.09 13.1 1.24 15.7 1.93 17.0 2.23 18.4...
  • Page 89 Table2-8.41:MSAN8-Y 160T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.83 10.7 0.95 12.9 1.18 13.9 1.31 15.0 1.48 17.2 2.20 19.3 2.81 0.86 10.7 0.98 12.9 1.20 13.9 1.36 15.0 1.78 17.2...
  • Page 90 V8 Mini Series VRF 50Hz Table2-8.43:MSAN8-Y 160T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.63 0.70 10.0 0.86 10.9 0.95 11.7 1.05 13.4 1.23 15.0 1.58 0.65 0.70 10.0 0.88 10.9 0.97...
  • Page 91 Table2-8.45:MSAN8-Y 160T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.44 0.49 0.59 0.64 0.70 0.80 10.7 0.93 0.45 0.50 0.59 0.65 0.70 0.81 10.7 0.95 0.45 0.50 0.61 0.65 0.71 0.82 10.7...
  • Page 92 Table2-8.46:MSAN8-Y 180T cooling capacity Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 15.8 1.92 17.5 2.27 21.0 3.16 22.8 3.61 24.5 4.07 25.6 4.41 26.2 4.18 15.8 1.97 17.5 2.37 21.0 3.19 22.8 3.71 24.5...
  • Page 93 Table2-8.48:MSAN8-Y 180T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 13.3 1.26 14.8 1.47 17.8 2.31 19.3 2.66 20.7 3.02 23.7 3.84 24.7 4.29 13.3 1.27 14.8 1.77 17.8 2.42 19.3 2.71 20.7...
  • Page 94 Table2-8.50:MSAN8-Y 180T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 10.9 0.97 12.1 1.10 14.5 1.38 15.8 1.80 17.0 2.14 19.4 2.64 21.8 3.51 10.9 1.00 12.1 1.12 14.5 1.60 15.8 1.91 17.0...
  • Page 95 Table2-8.52:MSAN8-Y 180T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 air temp. (°CDB) 0.72 0.81 11.3 1.00 12.3 1.11 13.2 1.23 15.1 1.47 17.0 2.23 0.73 0.81 11.3 1.02 12.3 1.12 13.2 1.23 15.1 1.78 17.0...
  • Page 96 Table2-8.54:MSAN8-Y 180T cooling capacity(continued) Indoor air temp. (°C DB/WD) Outdoor air 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24 temp. (°CDB) 0.50 0.56 0.68 0.73 0.79 10.8 0.94 12.1 1.09 0.51 0.56 0.68 0.74 0.80 10.8 0.95 12.1 1.10 0.51 0.57 0.69 0.75 0.82...
  • Page 97 8.2 Heating Capacity Tables Table 2-7.7: MSAN8-Y 120T heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.5 4.41 10.4 4.44 10.3 4.49 10.3 4.52 10.3 4.56 10.3 4.65 -18.8...
  • Page 98 Table 2-7.6: MSAN8-Y 120T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.2 4.47 10.2 4.53 10.2 4.61 10.2 4.66 10.2 4.71 10.2 4.83 -18.8 -19.0 10.6 4.50...
  • Page 99 Table 2-7.6: MSAN8-Y 120T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.1 4.71 10.1 4.83 4.71 4.54 4.37 4.03 -18.8 -19.0 10.4 4.77 10.6 4.95 4.60 4.43...
  • Page 100 Table 2-7.7: MSAN8-Y 140T heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.8 4.29 10.7 4.33 10.6 4.39 10.6 4.42 10.6 4.46 10.5 4.54 -18.8 -19.0 11.2 4.31 11.1...
  • Page 101 Table 2-7.6: MSAN8-Y 140T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.5 4.36 10.5 4.42 10.4 4.50 10.4 4.54 10.4 4.59 10.4 4.70 -18.8 -19.0 10.9 4.39...
  • Page 102 Table 2-7.6: MSAN8-Y 140T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.2 4.57 10.2 4.67 10.3 4.79 10.3 4.86 10.3 4.87 4.48 -18.8 -19.0 10.6 4.63 10.6...
  • Page 103 Table 2-7.7: MSAN8-Y 160T heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.4 4.38 11.3 4.45 11.2 4.53 11.1 4.58 11.1 4.62 11.0 4.73 -18.8 -19.0 11.8 4.42 11.7...
  • Page 104 Table 2-7.6: MSAN8-Y 160T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.1 4.49 11.0 4.57 10.9 4.67 10.8 4.72 10.8 4.77 10.7 4.89 -18.8 -19.0 11.4 4.54...
  • Page 105 Table 2-7.6: MSAN8-Y 160T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 10.7 4.74 10.6 4.85 10.5 4.97 10.5 5.03 10.5 5.10 10.4 4.93 -18.8 -19.0 11.0 4.81...
  • Page 106 Table 2-7.7: MSAN8-Y 180T heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 12.4 4.66 12.2 4.76 12.1 4.87 12.0 4.92 11.9 4.98 11.8 5.11 -18.8 -19.0 12.8 4.72 12.6...
  • Page 107 Table 2-7.6: MSAN8-Y 180T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.9 4.80 11.7 4.91 11.6 5.03 11.5 5.09 11.4 5.15 11.3 5.28 -18.8 -19.0 12.2 4.87...
  • Page 108 Table 2-7.6: MSAN8-Y 180T heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -19.8 -20.0 11.3 5.09 11.1 5.21 11.0 5.34 11.0 5.41 11.0 5.48 10.9 5.62 -18.8 -19.0 11.6 5.18...
  • Page 109 8.3 Capacity Correction Factors for Piping Length and Level Difference Figure 2-7.1: 80 model rate of change in cooling capacity Figure 2-7.2: 80 model rate of change in heating capacity Figure 2-7.3: 100 model rate of change in cooling capacity Figure 2-7.4: 100 model rate of change in heating capacity Figure 2-7.5: 120 model rate of change in cooling capacity Figure 2-7.6: 120 model rate of change in heating capacity...
  • Page 110 Figure 2-7.5: 160 model rate of change in cooling capacity Figure 2-7.6: 160 model rate of change in heating capacity 100 110 120 100 110 120 Figure 2-7.5: 180 model rate of change in cooling capacity Figure 2-7.6: 180 model rate of change in heating capacity 100 110 120 100 110 120 Notes:...
  • Page 111 8.4 Capacity Correction Factors for Frost Accumulation The heating capacity tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. If snow has accumulated against the outside surface of the outdoor unit heat exchanger heating capacity is reduced.
  • Page 112 9 Operating Limits Figure 2-8.1: Operating limits ℃ Note1:Outdoor operating temperature under -5 in "cooling" mode, the startup capacity of IDUs must meet at least 30% of ODU capacity. Table 2-8.1: Operating limits Mode Outdoor temperature Room temperature Cooling operation -15℃~52℃...
  • Page 113 10 Sound Levels 10.1 Overall Table 2-9.1: Sound pressure level Model dB(A) (H) Height (m) MSAN8-Y 80M MSAN8-Y 100M MSAN8-Y 120M/T MSAN8-Y 140M/T MSAN8-Y 160M/T MSAN8-Y 180M/T Notes: Sound pressure level is measured at a position 1m in front of the unit and (H)m above the floor in a semi-anechoic chamber. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.
  • Page 114 Figure 2-9.4 120 model octave band level Figure 2-9.5 140 model octave band level NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 500 1000 2000 4000 8000 500 1000 2000 4000 8000 Octave band center frequency (Hz) Octave band center frequency (Hz) Figure 2-9.4 160 model octave band level Figure 2-9.5 180 model octave band level...
  • Page 115 11 Accessories Table 2-10.1: Standard accessories Name Quantity Shape Outdoor unit operation and installation manual Water outlet connection pipe Build-out resistor Magnetic ring CN93 Auxiliary connector...
  • Page 116 Part 3 System Design and Installation 1 Preface to Part 3 ..................77 2 Unit Placement and Installation ..............78 3 Refrigerant Piping Design ................81 4 Refrigerant Piping Installation ..............86 5 Drain Piping....................97 6 Insulation ....................101 7 Charging Refrigerant .................
  • Page 117: Preface To Part 3

    1.1 Notes for Installers Boxes The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Clivet V8 R32 Mini VRF project. Additional important information which may primarily be of use during field installation has been placed in boxes, such as the example below, titled “Notes for installers”.
  • Page 118: Unit Placement And Installation

    2 Unit Placement and Installation 2.1 Outdoor Units 2.1.1 Placement considerations Placement of outdoor units should take account of the following considerations:  Air conditioners should not be installed in places where there are gas leakage.  Air conditioners should not be exposed to direct radiation from a high-temperature heat source. ...
  • Page 119 2.1.3 Base structures Outdoor unit base structure design should take account of the following considerations: A solid base prevents excess vibration and noise. Outdoor unit bases should be constructed on solid ground or on  structures of sufficient strength to support the units’ weight. ...
  • Page 120 2.1.4 Acceptance and unpacking  Notes for installers  When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a written report to the shipping company. ...
  • Page 121 2.2 Indoor Units 2.2.1 Placement considerations Placement of indoor units should take account of the following considerations:  Sufficient space for drain piping and for access during servicing and maintenance should be allowed.  To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) should be avoided.
  • Page 122: Refrigerant Piping Design

    3 Refrigerant Piping Design 3.1 Design Considerations Refrigerant piping design should take account of the following considerations:  The amount of brazing required should be kept to a minimum.  On the two inside sides of the first indoor branch joint (“A” in Figures 3-3.4 and Figure 3-3.5) the system should, as far as possible, be equal in terms of number of units, total capacities and total piping lengths.
  • Page 123 Table 3-3.2: Summary of permitted refrigerant piping lengths and level differences Total piping length Permitted value Piping ≤150m(80/100 model) Total Pipe Length(Actual) L1+L2+L3+L4+L5+a+b+c+d+e+f ≤300m(120/140/160/180 model) ≤50m(80/100 model) Actual Length L1+L2+ max(a,b) or ≤100m(120/140/160/180 model) Maximum Piping L1+L3+L4+max(c,d) or Pipe Length ≤60m(80/100 model) L1+L3+L5+max(e,f) Equivalent Length...
  • Page 124 3.4 Selecting Piping Diameters Tables 3-3.4 to 3-3.6 below, specify the required pipe diameters for the indoor and outdoor piping. The main pipe (L ) and first indoor branch joint (A) should be sized according to whichever of Tables 3-3.4 and 3-3.5 indicates the larger size. Figure 3-3.3: Selecting piping diameters Legend Main pipe...
  • Page 125 Table 3-3.4: Main pipe ) and first indoor branch joint (A) Equivalent length to the farthest IDU < 90m Equivalent length to the farthest IDU ≥ 90m Total capacity of outdoor units Gas pipe (mm) Liquid pipe (mm) Branch joint kit Gas pipe (mm) Liquid pipe (mm) Branch joint kit...
  • Page 126 Step 2: Select indoor main pipes and indoor branch joints B to E  The indoor units (N and N ) downstream of indoor branch joint B have total capacity of 28 x 2 = 56kW. Refer to Table 3-3.5. Indoor main pipe L is Φ15.9 / Φ9.52.
  • Page 127 3.7 Refrigerant Leakage Precautions R32 refrigerant is flammable in air, so precautions should be taken to avoid danger to life in the unlikely event of a major refrigerant leakage. Precautions should be taken in accordance with all applicable legislation. Where no applicable legislation exists, the following may be used as a guide: ...
  • Page 128: Refrigerant Piping Installation

    4 Refrigerant Piping Installation 4.1 Procedure and Principles 4.1.1 Installation procedure  Notes for installers Installation of the refrigerant piping system should proceed in the following order: Pipe Pipe brazing Pipe Gas tightness Joint Vacuum drying insulation and installation flushing test insulation Note: Pipe flushing should be performed once the brazed connections have been completed with the exception of the...
  • Page 129 4.2 Storing Copper Piping 4.2.1 Pipe delivery, storage and sealing  Notes for installers  Ensure that piping does not get bent or deformed during delivery or whilst stored.  On construction sites store piping in a designated location.  To prevent dust or moisture entering, piping should be kept sealed whilst in storage and until it is about to be connected.
  • Page 130 4.3.3 Expanding copper piping ends  Notes for installers  Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed.  Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head.
  • Page 131 4.3.5 Bending piping Bending copper piping reduces the number of brazed joints required and can improve quality and save material.  Notes for installers Piping bending methods  Hand bending is suitable for thin copper piping (Ф6. 35mm - Ф12. 7mm). ...
  • Page 132 4.5 Brazing Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even compressor failure.
  • Page 133 … box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. Figure 3-4.6: Piping orientation during brazing Piping overlap during brazing Table 3-4.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints on piping of different diameters.
  • Page 134 4.6 Branch Joints  Notes for installers  Use U-shaped branch joints as specified on the construction Figure 3-4.8: Branch joint orientation drawings – do not replace U-shaped branch joints with tee joints.  Indoor branch joints may be installed either horizontally or vertically.
  • Page 135 Liquid side stop valve Gas side stop valve Gas side piping (provided on site) Liquid side piping Gas side piping Liquid side piping (provided on site) (provided on site) (provided on site) 4.7 Pipe Flushing 4.7.1 Purpose To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the system is run, the refrigerant piping should be flushed using nitrogen.
  • Page 136 4.7.2 Procedure  Notes for installers Warning Only use nitrogen for flushing. Using carbon dioxide risks leaving condensation in the piping. Oxygen, air, refrigerant, flammable gases and toxic gases must not be used for flushing. Use of such gases may result in fire or explosion. Procedure The liquid and gas sides can be flushed simultaneously;...
  • Page 137 4.8 Gastightness Test 4.8.1 Purpose To prevent faults caused by refrigerant leakage, a gastightness test should be performed before system commissioning.. 4.8.2 Procedure  Notes for installers Warning Only dry nitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be used for gastightness testing.
  • Page 138 4.8.3 Leak detection  Notes for installers The general methods for identifying the source of a leak are as follows: 1. Audio detection: relatively large leaks are audible. 2. Touch detection: place your hand at joints to feel for escaping gas. 3.
  • Page 139 4.9.2 Procedure  Notes for installers During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C. Therefore a vacuum pump capable of maintaining a pressure of -756mmHg or lower should be used.
  • Page 140: Drain Piping

    5 Drain Piping 5.1 Design Considerations Drain piping design should take account of the following considerations:  Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced at the indoor units and installed at a slope sufficient to allow drainage. Discharge as close as possible to the indoor units is usually preferable.
  • Page 141 installed too close to indoor unit lift pumps. Figure 3-5.5: Drain piping air vents  Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should not come into direct contact with the ground. ...
  • Page 142 Table 3-5.2: Vertical drain piping diameters Nominal PVC piping Capacity (L/h) Remarks diameter (mm) PVC25 Branch piping only PVC32 PVC40 PVC50 1440 PVC63 2760 Branch or main piping PVC75 5710 PVC90 8280 5.4 Drain Piping for Units with Lift Pumps Drain piping for units with lift pumps should take account of the following additional considerations: ...
  • Page 143 5.6 Water tightness Test and Water Flow Test Once installation of a drainage piping system is compete, water tightness and water flow tests should be performed.  Notes for installers Water tightness test  Fill the piping with water and test for leakages over a 24-hour period. Water flow test (natural drainage test) ...
  • Page 144: Insulation

    6 Insulation 6.1 Refrigerant Piping Insulation 6.1.1 Purpose During operation, the temperature of the refrigerant piping varies. Insulation is required to ensure unit performance and compressor lifespan. During cooling, the gas pipe temperature can be very low. Insulation prevents condensation forming on the piping.
  • Page 145 Figure 3-6.1: Installation of joint insulation (unit: mm) 6.2 Drain Piping Insulation  Use rubber/plastic insulating tube with a B1 fire resistance rating.  The insulation should typically be in excess of 10mm thick.  For drain piping installed inside a wall, insulation is not required. ...
  • Page 146: Charging Refrigerant

    7 Charging Refrigerant 7.1 Calculating Additional Refrigerant Charge The additional refrigerant charge required depends on the lengths and diameters of the outdoor and indoor liquid pipes, and the indoor unit capacity of the connection. Table 3-7.1 shows the additional refrigerant charge required per meter of equivalent pipe length for different diameters of pipe.
  • Page 147 … box continued from previous page Step 3 · Open the valve where the yellow hose meets the pressure gauge, and open the refrigerant tank slightly to let the refrigerant eliminate the air. Caution: open the tank slowly to avoid freezing your hand. ·...
  • Page 148 7.3 Refrigerant charge and room area limitations 7.3.1 Strategy 1: EN 60335-2-40 According to EN 60335-2-40, R32 refrigerant is class A2 and flammable. To ensure that your system meets regulatory requirements, follow these requirements:  The total amount of refrigerant in the system shall be less than or equal to the maximum refrigerant charge. The maximum refrigerant charge depends on the amount of space in the rooms being served by the system.
  • Page 149  If installation height is not less than 2.2 m, and without any conditions, the refrigerant charge is limited as shown in curve (b) in Figure 3-7.3.  If installation height is greater than or equal to 1.8 m, but less than 2.2 m, and meeting the incorporated circulation airflow requirements, the refrigerant charge is limited as shown in curve (c) in Figure 3-7.3.
  • Page 150  Notes for installers Caution  Use only the specified model of refrigerant shut-off device by Clivet: N8SV-01.  Use only the specified model of refrigerant leak sensor by Clivet: N8RS-01.  The refrigerant shut-off device shall be located outside.
  • Page 151: Electrical Wiring

    8 Electrical Wiring 8.1 General  Notes for installers Caution  All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation.  Electrical systems should be grounded in accordance with all applicable legislation. ...
  • Page 152  Notes for installers The power supply should be connected to the outdoor unit power supply terminals as shown in Figure 3-8.2. Figure 3-8.2: Outdoor unit 1-phase power supply terminals Notes for installers  The 220-240V, ~, 50Hz power supply should be connected to the outdoor unit power supply terminals as shown in Figure 3-8.2.
  • Page 153 8.3 Communication Wiring Communication wiring design and installation should adhere to the following requirements:  Do not connect the communication line when the power is on.  Connect the shielding nets at both ends of the shielded wire to the sheet metal “ ”of the electronic control box.
  • Page 154 8.3.2 Outdoor unit and indoor units’ M1, M2 communication All IDU must have uniform puwer supply. Communcation wiring design and installation should have the following requirements: two-core shielded cable should be used for communication wiring when all the indoor units are ...
  • Page 155  Communication wiring has polarity. Care should be taken to connect the poles correctly.  Only the dedicated meter of Clivet can be used on the unit.  For the wiring method of the meter, please consult Clivet’s professional service personnel.  The arrangement of OAE, XYE and PQE depends on the unit.
  • Page 156: Installation In Areas Of High Salinity

    9 Installation in Areas of High Salinity 9.1 Caution Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. Outdoor units installed in seaside locations should be placed such as to avoid direct exposure to the sea air and additional anticorrosion treatment options should be selected, otherwise the service life of the outdoor units will be seriously affected.
  • Page 157: Commissioning

    10 Commissioning 10.1 Outdoor Unit Address and Communication Type Setting Before running a system for the first time, make sure all the settings you need to configure are completed. Set each outdoor unit’s address and communication type between outdoor units and indoor unit by menu. Step 1: Power on Cover the lower panel of the ODU, and power on all IDUs and ODUs.
  • Page 158 requirements. For specific operations, please refer to related technical documents. If there is no special requirement, you can skip this step. 10.2 Multi-system Projects For projects with multiple refrigerant systems, each independent refrigeration system (i.e. each system of one outdoor unit and its connected indoor units) should be given a test run independently, before the multiple systems that make up a project are run simultaneously.
  • Page 159 After one hour, complete Sheet A of the system commissioning report then check the system parameters using the CHECK button on the outdoor unit’s main PCB and complete the cooling mode columns of one Sheet D and one Sheet E of the system commissioning report for the outdoor unit. Run the system in heating mode with the following settings: temperature 30°C;...
  • Page 160: Appendix To Part 3 - System Commissioning Report

    11 Appendix to Part 3 – System Commissioning Report A total of up to 4 report sheets should be completed for each system:  One Sheet A, one Sheet B and one Sheet C per system.  One Sheet D per outdoor unit.
  • Page 161 System Commissioning Report – Sheet A SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information OUTDOOR UNIT Compressor suction pipe Current (A) temperature System pressure at check...
  • Page 162 System Commissioning Report – Sheet B SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information OUTDOOR UNIT Compressor suction pipe Current (A) temperature System pressure at check...
  • Page 163 System Commissioning Report – Sheet C Project name and location System name RECORD OF ISSUES SEEN DURING COMMISSIONING Serial no. of Description of observed issue Suspected cause Troubleshooting undertaken relevant unit OUTDOOR UNIT FINAL CHECKLIST SW2 system check performed? Any abnormal noise? Any abnormal vibration? Fan rotation normal? Commissioning engineer...
  • Page 164 System Commissioning Report – Sheet D Project name and location System name Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode --.-- "Standby (ODU address+ IDU number)/frequency/special status" 0.-- Outdoor unit address V8 Mini series outdoor unit: 0 1.-- Outdoor unit capacity (HP) Actual value = value displayed...
  • Page 165 V8 Mini Series VRF 50Hz System Commissioning Report – Sheet D Project name and location System name … table continued from previous page Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks mode mode content 34.-- Reserved 35.-- Compressor discharge pressure (MPa) Actual value = value displayed ×...
  • Page 168 BEING OF PEOPLE AND THE ENVIRONMENT sales and service www.clivet.com CLIVET S.p.A. Via Camp Lonc 25, Z.I. Villapaiera 32032 - Feltre (BL) - Italy Tel. +39 0439 3131 - info@clivet.it Clivet South East Europe CLIVET GMBH CLIVET LLC Clivet Airconditioning Systems Pvt Ltd Jaruščica 9b...

This manual is also suitable for:

Msan8-y 80mMsan8-y 100mMsan8-y 120mMsan8-y 140mMsan8-y 160mMsan8-y 180m ... Show all

Table of Contents