Page 27
Advanced Function Advanced Function Advanced Function Parallel Modbus SN Parallel Modbus SN Parallel Modbus SN Master Master Master Paral. Paral. Paral. Set3 Set3 Set3 Slave Slave Slave EX_Meter For CT EX_Meter For CT EX_Meter For CT Meter Select Meter Select Meter Select No Meter No Meter...
Page 28
4. OPERATION 4.1 Power ON/OFF LED Indicator Messages...
Page 32
Li-BMS Mean Voltage:170.0V Charging Voltage :180.0V Batt Total Current:37.00A Discharging Voltage :160.0V Data Mean Temp :23.5C Charging current :30A Total SOC :38% Discharging current :25A Battery 1 Stand by Dump Energy:57Ah Details Data U:170V I:2.04A Li-BMS Power: 101W Charge Volt Curr Temp Energy...
Page 33
System Setup System Work Mode Battery Setting Gen Port Grid Setting Basic Advanced Device Info. Setting Function Basic Setting Time Syncs Beep Auto Dim Year Month Basic 2019 Hour Minute 24-Hour Factory Reset Lock out all changes PassWord 9999 7777 X--X--X--X CANCEL...
Page 34
Battery Setting Batt Mode Lithium Batt Capacity Batt Mode Use Batt V Max A Charge No Batt Max A Discharge Parallel bat1&bat2 Battery Setting Start Batt Set2 Grid Charge Gen Charge Gen Signal Grid Signal Gen Max Run Time 24.0 hours Gen Down Time 0.0 hours...
Page 36
System Work Mode 12000 Selling First Max Solar Power Work Zero Export To Load Solar Sell Mode1 Zero Export To CT Solar Sell Max Sell Power 12000 Zero-export Power Energy pattern BattFirst LoadFirst Grid Peak Shaving 8000 Power Solar Backup Load On-Grid Home Load Grid Battery...
Page 37
Time Of Use Time Power Batt Work 05:00 12000 160V Mode2 08:00 160V 12000 10:00 12000 160V 15:00 12000 160V 15:00 18:00 12000 160V 18:00 00:00 160V 12000 Battery Setting Start Batt Set2 Grid Charge Gen Charge Gen Signal Grid Signal Gen Max Run Time 24.0 hours Gen Down Time...
Page 38
Grid Setting/Grid code selection Grid Mode General Standard 0/23 Grid Frequency Phase Type 50HZ Grid G98 G99 Set1 0/120/240 60HZ 0/240/120 Grid Level LN:220V/LL:380V(AC) IT system-neutral is not grounded Grid Setting/Grid code selection Grid Mode General Standard 0/23 Phase Type Grid Frequency 50HZ Grid...
Page 39
Grid Setting/F(W) F(W) Over frequency Droop F %PE/Hz Grid Set4 Start freq F Stop freq F 50.20Hz 51.5Hz Stop delay F Start delay F 0.00s 0.00s Under frequency Droop F %PE/Hz Start freq F Stop freq F 49.80Hz 49.80Hz Stop delay F Start delay F 0.00s 0.00s...
Page 40
GEN PORT USE Mode Generator Input GEN connect to Grid input Rated Power PORT Set1 8000W SmartLoad Output On Grid always on AC Couple Frz High 55.00Hz 151.0V Micro Inv Input 154.0V Ml export to Grid cutoff Note Advanced Function Solar Arc Fault ON Backup Delay Func...
Page 41
Advanced Function Modbus SN Parallel Master Paral. Set3 Slave EX_Meter For CT Meter Select No Meter Li-BMS Li-BMS Device Info. Inverter ID: 2102199870 Flash Charge Charge Volt Volt Curr Curr Temp Temp Energy Energy Fault Fault HMI: Ver 1001-8010 MAIN:Ver2002-1046-1707 Volt Volt Curr...
Page 42
AC cable DC cable Solar Backup Load On-Grid Home Load Grid Battery Smart Load AC cable DC cable Solar Backup Load On-Grid Home Load Grid Battery On-Grid Inverter...
Page 54
Models: SUN-5K-SG01HP3-EU-AM2;SUN-6K-SG01HP3-EU-AM2;SUN-8K-SG01HP3-EU-AM2; SUN-10K-SG01HP3-EU-AM2;SUN-12K-SG01HP3-EU-AM2;SUN-15K-SG01HP3-EU-AM2; SUN-20K-SG01HP3-EU-AM2;SUN-25K-SG01HP3-EU-AM2; Name and address of the manufacturer: Ningbo Deye Inverter Technology Co., Ltd. No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China This declaration of conformity is issued under the sole responsibility of the manufacturer. Also this product is under manufacturer’s warranty.