Display Error Codes

If any error codes are active, the lowest numbered error code will scroll across the display until the error is cleared.
NOTE: Errors can be cleared by placing the dispense switch in the OFF position (errors will only clear if the error
condition is resolved).
NOTE: The system will not operate while any errors are present. A prime is required after all error conditions are
resolved before the system will be allowed to dispense on ratio again.
Error
Error Description (on
Code
Display)
E01X
SENSOR FAULT
E02A
HIGH PRESSURE DETECTED,
PUMP A
E02B
HIGH PRESSURE DETECTED,
PUMP B
E03A
PRESSURE TRANSDUCER NOT
DETECTED PUMP A
E03B
PRESSURE TRANSDUCER NOT
DETECTED PUMP B
E04A
HIGH INCOMING VOLTAGE
DETECTED
E04B
E08A
LOW INCOMING VOLTAGE
DETECTED
E08B
E09A
MOTOR ENCODER FAULT
PUMP A
E09B
MOTOR ENCODER FAULT
PUMP B
E10A
CONTROL BOARD THERMAL
PROTECTION FAILED
E10B
E12A
EXCESSIVE CURRENT
PROTECTION ENABLED PUMP
A
E12B
EXCESSIVE CURRENT
PROTECTION ENABLED PUMP
B
E15A
NO MOTOR CURRENT PUMP A
E15B
NO MOTOR CURRENT PUMP B
3B0119A
Causes
Short/fault in pressure transducer or motor
encoder wiring.
Too much restriction on pump A.
Too much restriction on pump B.
Pressure transducer A unplugged.
NOTE: This error will not occur while the
pump mode knob is set to park.
Pressure transducer B unplugged.
NOTE: This error will not occur while the
pump mode knob is set to park.
Supply voltage too high.
Supply voltage too low. Battery low.
A motor calibration failed. Invalid output from
encoder A.
B motor calibration failed. Invalid output
from encoder B.
Motor controller too hot.
Motor current too high.
Motor disconnected.
Display Error Codes
Solution
Check motor encoder wiring. Check
pressure transducer wiring.
Follow pressure relief procedure.
Replace mix hose. Clean check valve.
Clean pump.
Follow pressure relief procedure.
Replace mix hose. Clean check valve.
Clean pump.
Check A pressure transducer wiring.
Replace A pressure transducer.
Check B pressure transducer wiring.
Replace B pressure transducer.
Check supply voltage, see inverter
troubleshooting flow chart.
Charge battery. Check supply voltage.
See inverter troubleshooting flow chart.
Relieve pressure and recalibrate
motors. Check A encoder wiring.
Relieve pressure and recalibrate
motors. Check B encoder wiring.
Let motor controller cool down. Ensure
airflow to the unit is not restricted and
system is in allowable temperature
range.
Call Graco technical assistance.
Check A motor wiring.
Check B motor wiring.
43