Toshiba RAV-GM1601ATP-E Installation Manual
Hide thumbs Also See for RAV-GM1601ATP-E:

Advertisement

Quick Links

AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Scan QR CODE to access installation and owner's manual on website.
https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/
HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR.
Outdoor Unit
Model name:
<Heat Pump Model>
RAV-GM1601ATP-E
RAV-GM1601ATJP-E
For commercial use
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-GM1601ATP-E

  • Page 1 Outdoor Unit AIR CONDITIONER (SPLIT TYPE) For commercial use Installation Manual Model name: <Heat Pump Model> RAV-GM1601ATP-E RAV-GM1601ATJP-E Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/ HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR. English...
  • Page 2: Table Of Contents

    – 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. This Manual describes the installation method of the indoor unit. Accessory parts ............. . . 3 For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
  • Page 3 Cautions for outdoor unit installation space Center of gravity • In the event that the outdoor unit is installed in a small space and refrigerant leaks, accumulation of highly concentrated (Unit: mm) refrigerant may cause a fi re hazard. Therefore, be sure to follow Center of gravity the installation space instructions in the Installation Manual, and provide open space on at least one of the four outdoor unit sides.
  • Page 4: Accessory Parts

    – 3 – Accessory parts Installation of R32 refrigerant air conditioner Part name Q’ty Shape Usage Installation Manual Booklet Hand this directly to the customer. CAUTION R32 refrigerant air conditioner installation Drain nipple This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer. Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant air conditioner cycle.
  • Page 5: Installation Conditions

    Installation conditions Bender Bending pipes Conventional tools (R410A) Refrigerant recovery equipment Refrigerant recovery Conventional tools (R32 or R410A) Before installation Electrical wiring Be sure to fix the power wires and system Torque wrench Tightening flare nuts Conventional tools (R410A) interconnection wires with clamps so that they do not Be sure to prepare to the following items before come into contact with the cabinet, etc.
  • Page 6 – 5 – Installation location Necessary space for installation (Unit: mm) CAUTION Single unit installation WARNING Install the outdoor unit in a location where the discharge air is not blocked. Install the outdoor unit properly in a location that is durable enough to support the weight of the When an outdoor unit is installed in a When there is an obstacle on the When there is an obstacle on the...
  • Page 7 Serial unit installation Installation of outdoor unit Set the out margin of the anchor bolt to 15 mm or less. * When the outdoor temperature is high, the cooling capability may be decreased because of an equipment Before installation, check the strength and protection operation.
  • Page 8: Refrigerant Piping

    – 7 – Refrigerant piping connection Refrigerant piping Flaring dia. size: A (Unit: mm) CAUTION Refrigerant Piping IMPORTANT 4 POINTS FOR PIPING WORK 1. Use the following items for the refrigerant 1. Reusable mechanical connectors and flared piping. joints are not allowed indoors. When mechanical Material : Seamless phosphorous deoxidized connectors are reused indoors, sealing parts shall Outer dia.
  • Page 9 Refrigerant pipe length (Unit: N•m) Outer dia. of copper pipe Tightening torque Single 9.5 mm (dia.) 34 to 42 (3.4 to 4.2 kgf•m) 15.9 mm (dia.) 68 to 82 (6.8 to 8.2 kgf•m) Allowable pipe length (m) Height difference (Indoor-outdoor H) (m) Total length L Indoor unit: Upper Outdoor unit: Lower...
  • Page 10: Necessary, That The Equipment Is Connected Only To A Supply With A Short-Circuit Power Ssc Greater Than Or Equal To Ssc (*1). 5 Air Purging

    – 9 – Air purge Air purging Vacuum pump With respect to the preservation of the terrestrial As shown in the figure, connect the charge hose after Airtight test environment, adopt “Vacuum pump” to purge air the manifold valve is closed completely. (Evacuate air in the connecting pipes) when installing ↓...
  • Page 11 How to open the valve Cap tightening torque Charging additional refrigerant 14 to 18 N•m Fully open the valves of the outdoor unit. (First fully Ø9.5 mm Figure of Single Figure of simultaneous twin Figure of Simultaneous triple (1.4 to 1.8 kgf•m) open the valve on the liquid side, and then fully open Valve size the valve on the gas side.)
  • Page 12: Ssc (*1) 6 Electrical Work

    – 11 – Gas leak inspection Electrical work Indoor unit inspection locations Use a leak detector manufactured specially for HFC refrigerant (piping connections) (R32, R410A, R134a, etc.) to perform the R32 gas leak inspection. Remove the service panel, and you can see electric Refrigerant WARNING parts on the front side.
  • Page 13 For the air conditioner, connect a power wire with the Stripping length power cord and system Wiring diagram following specifications. interconnection wire * For details on the remote controller wiring /installation, refer to the Installation Manual enclosed with the remote controller.
  • Page 14: Earthing

    – 13 – Earthing Air conditioner operating conditions For proper performance, operate the air conditioner under the following temperature conditions: WARNING Cooling operation Dry bulb temp. –15 °C to 46 °C Be sure to connect the earth wire. (grounding work) Heating operation Wet bulb temp.
  • Page 15 Refrigerant recovery Steps taken to recover the refrigerant 1. Operate the indoor unit in the fan mode. 2. Check that the LED displays are placed in their initial status. If not, place them in the initial status. When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit, the recovery 3.
  • Page 16 – 15 – Existing piping How to check the existing piping settings You can check whether the existing piping settings are enabled. 1. Check that the LED displays are placed in their initial status. If not, place them in the initial status. The following settings are required when using a pipe Ø19.1 mm as the existing piping at the gas pipe side.
  • Page 17: In Addition, It Is Recommended That Voltage Drops Occurring During The Unit's Operation In The Area At The Power 13 Troubleshooting

    Troubleshooting Appendix [1] Existing piping You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition 3. When the outdoor unit was left with the pipes to using the check codes displayed on the wired remote controller of the indoor unit. disconnected, or the gas leaked from the pipes and Use the LEDs and check codes for various checks.
  • Page 18 Are there scratches or dents on the existing pipes? Use new pipes. In the concurrent twin system, when TOSHIBA has specified that branching pipe is to be used, it can be reused. Is it possible to operate the existing air conditioner?
  • Page 19 [2] Minimum fl oor area : A (m²) (m²) Total Ceiling Floor standing Wall mounted refrigerant mounted unit unit quantity* unit M (kg) (m²) 2.400 49.424 5.492 3.676 2.435 50.876 5.653 3.784 2.470 52.349 5.817 3.894 2.505 53.843 5.983 4.005 2.540 55.358 6.151...
  • Page 20: Specifications

    – 19 – Declaration of conformity Specifications Sound power level (dBA) Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. Model Weight (kg) Cooling Heating 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand RAV-GM1601ATP-E...
  • Page 21 Warnings on refrigerant leakage To Fix the Fluorinated Fill in the label as follows: Greenhouse Gases Label Check of concentration limit This product contains fluorinated greenhouse gases. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant Do not vent gases into the atmosphere.
  • Page 22 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand 1126901002A...