11. M-NET CONTROL
11-2. Transmission cable specifications
Type of cable
Cable size
Maximum overall line length
*1 The use of cables that are smaller than 0.75 mm
recommended for easy handling.
*2 The section of the cable that exceeds 10 m [32 ft] must be included
in the maximum indoor-outdoor transmission line distance.
*3 Max. 70 m [229 ft] for PAR-CT01MA series
*4 Max. 150 m [492 ft] for PAR-FS01MA series
*5 To wire PAR-CT01MA series, PAR-FS01MA series, PAR-4"x"MA
series, PAR-3"x"MA series ("x" represents 0 or later), or Simple
MA remote controller, use a cable with a size of 0.3 mm
*6 When connected to the terminal block on the Simple remote controller,
use a cable with a size of 0.75 to 1.25 mm
MEES23K040
Transmission cables (Li)
Shielded cables (2-core)
CVVS, CPEVS, and MVVS
2
Larger than 1.25 mm
[AWG16], or
ø1.2 mm or above
Refer to 11-1.
2
(AWG18) is
2
(AWG 22).
2
(AWG18 to 16).
MA Remote controller cables
VCTF, VCTFK, CVV, VVR, VVF, VCT
2
0.3 to 1.25 mm
[AWG22 to 16] *1 *5
200 m [656 ft] *3 *4
CVVS, MVVS: PVC insulated PVC sheathed shielded control cable
CPEVS: PE insulated PVC sheathed shielded communication cable
CVV: PVC insulated PVC sheathed control cable
Y-Series
ME Remote controller cables
Shielded cables (2-core)
CVVS, CPEVS, and MVVS
2
0.3 to 1.25 mm
[AWG22 to 16] *1 *6
10 m [32 ft] *2
165