Mitsubishi Electric CITY MULTI PUHY-P72-432TNU-A Data Book page 154

Table of Contents

Advertisement

8. CAPACITY TABLES
8-4-3. How to obtain the equivalent piping length
1. PUHY-P72TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.15 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bent on the piping) [m]
2. PUHY-P96TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.38 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bent on the piping) [m]
3. PUHY-P120TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.38 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bent on the piping) [m]
4. PUHY-P144TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) [m]
5. PUHY-P168TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) [m]
6. PUHY-P192, 216, 240TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) [m]
7. PUHY-P264, 288, 312TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.62 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bent on the piping) [m]
8. PUHY-P336, 360, 384, 408, 432TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.62 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bent on the piping) [m]
MEES23K040