Mitsubishi Electric 700 Series Instruction Manual page 10

Safety stop function
Hide thumbs Also See for 700 Series:

Advertisement

Example 2
START
Emergency
stop button
+24V
X0
COM0
X1
COM1
Internal
DC24V
Safety
Circuit
24G
MITSUBISHI ELECTRIC
MELSEC Safety relay module
QS90SR2SN-Q
Fig.6 Safety system example 2 – STOP synchronous with emergency stop button and fault
For safety stop, configure the wiring as shown in Fig.6 above.
NOTE
XS0 should be connected to RUN terminal and XS1 should be connected to SE, because polarity of
XS0 is positive, XS1 is negative.
Pr.190 (RUN terminal function selection) must be set to "81". This setting makes the RUN output to
turn off in case of failure.
The above wiring is configured to prevent restart in case of a fault.
In the event of reset of 'safe-condition' the motor rotation will not occur until STF is pressed. (for
normal 'non-safety' STF/STOP function, please refer to your drive's User Manual)
After the power-up of the system, to reset the safety stop mode, press the START switch, and also
press the STF switch, then start the motor rotation.
 To prevent restart in case of recovering from input power loss of drive, 3-wired connection for
STF/STOP control is recommended. In case of 2-wire connection and using latching type switch to short
between STF and SD/PC for starting, ensure the compliance with safety requirement for the restarting
when the drive recover from input power loss.
Inverter connection
Do not connect the FR-E700-SC/NF/NC (source logic) or the FR-D700-SC (source logic) together with the
FR-D700 (sink logic). If connected together, the safety stop function does not work properly.
FR-E700-SC/NF/NC
(source logic)
FR-D700-SC
(source logic)
FR-D700 (sink logic)
RUN (SAFE2)
STF
STOP
XS0
XS1
Z00
Z10
Z20
K1
K2
Z01
Z11
Z21
* If the control logic is SINK logic, the common
terminal is terminal SD.
detection through RUN output.
FR-E700-SC/NF/NC
(source logic)
SE
STF
STOP
CPU
+24V
S1
+24V
S2
SC
PC*
CAUTION
FR-D700-SC
(source logic)
8
R/L1 S/L2 T/L3
IGBTs
Gate
Gate
Driver
Driver
G
G
U
V
FR-D700
M
FR-D700 (sink logic)
: Enabled,
: Disabled
W