Hitachi RCUE40AG2 Service Manual page 93

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Troubleshooting
PCB
RSW1,2 (SW5): Setting Temperature in Cooling Mode with to digits and the sign indicated in
B1
SW5
(PCB
RSW1,2 & SW5: No function)
B2
In case of Brine 2 Option can be set negative temperatures.
PCB
RSW3,4: Setting Temperature in Heating Mode with to digits (Only available in Heat Pump
B1
Models- RHUEXXXAG2)
(PCB
RSW3,4: No function)
B2
PCB
RSW5,6,7: CT Sensor function (Supplied as standard)
B1
(PCB
RSW5,6,7: No function)
B2
Num. "X"
Model (HP)
2
40
3
50/100
5
60/120/180
6
70/140/210/280/350
7
80/160/240/320/400
e.g.:
RCUE40AG2: Compressor load is "down" and "hold" for 30min (Y=3; 3*10min) when compressor current is
higher than 48 A (X=2; 1.2*40A).
PCB
RSW8: Temperature band for Neutral Zone (See also DSW5)
B1
(PCB
RSW8: No function)
B2
Figure
0
Band (degree)
0.5
pag. 91
SMGB0003 rev.0 - 01/2007
X
1
,
RSW5
RSW6
Y
X
RSW7
Compressor load is kept for period when CT sensor measures set current
1
2
3
4
1.0
1.5
2.0
2.5
40A
40 HP
50 HP
X
60 HP
50A
70 HP
80 HP
10 min.
5
6
7
3.0
3.5
4.0
5
5
8
9
4.5
5.0