Defrost (Only Air-Cooled Heat Pump Type) - Hitachi RCUE40AG2 Service Manual

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Control System
Defrost (only air-cooled

4.16. Defrost (only air-cooled heat pump type)

heat pump type)
pag. 72
SMGB0003 rev.0-01/2007
Ambient temperature, evaporating temperature and evaporating pressure are detected
during heat operation to detect the frost volume. By the changeover of 4 way valve,
reverse-cycle defrosting is performed.
Defrosting start conditions
2 min from starting unload
Compressor operation >
designed time (limitation of
defrost interval)*
Evaporating temp≤-6 ºC
(air side HE inlet refrigerant)
(ambient temp) - (evaporating
temp) ≥ ambient temp corrected
value (detection of frost vol.)
Low pressure Ps ≤ 0.1MPa
Manual defrost SW ON
Not during defrost operation
Defrosting is performed for 6 minutes at longest. (automatic stop when all frost is
taken out).
In case that all frost is taken out very quickly, the period till next frost is extended
automatically in order to avoid too much defrost.
Warm water outlet temperature is lower than inlet temperature due to the reverse
cycle defrost.
(*) Normal: 55min. At longest: 115min.
AND
AND
OR
AND
Defrost